Integrate Group - YOKOGAWA CW120 User Manual

Clamp-on power meters
Table of Contents

Advertisement

1.7.3 INTEgrate Group

The commands in the INTEgrate group set or
query electric energy measurement parameters.
:INTEgrate?
Function Queries all the settings relating to
electric energy measurement.
Syntax
:INTEgrate?
:INTEgrate:CLEAr
Function Clears integrated values to zero.
Syntax
:INTEgrate:CLEAr
:INTEgrate:DISPlay?
Function Queries all the settings relating to
measurement screen.
Syntax
:INTEgrate:DISPlay?
:INTEgrate:DISPlay:MODE
Function Sets/queries the type of
measurement screen.
Syntax
:INTEgrate:DISPlay:MODE?
:INTEgrate:DISPlay:MODE
{<NRf>}
<NRf>=
0: Display item 1
1: Display item 2
2: Display item 3
3: Display item 4
4: Display item 5
5: Display item 6
:INTEgrate:STARt?
Function Queries all the settings relating to
the start of measurement.
Syntax
:INTEgrate:STARt?
:INTEgrate:STARt:EXECute
Function Starts measurement.
Syntax
:INTEgrate:STARt:EXECute
IM CW120-E
Appendix 2. Communication Commands
:INTEgrate:STARt:METHod
Function Sets/queries the method for starting
measurement.
Syntax
:INTEgrate:STARt:METHod?
:INTEgrate:STARt:METHod
{<NRf>}
<NRf> = 0: Time
1: Manual
:INTEgrate:STARt:TIME
Function Sets/queries the starting time of
measurement.
Syntax
:INTEgrate:STARt:TIME?
:INTEgrate:STARt:TIME
{<NRf1>, <NRf2>, <NRf3>,
<NRf4>, <NRf5>}
<NRf1> = Year: 2000 to 2099
<NRf2> = Month: 1 to 12
<NRf3> = Day: 1 to 31
<NRf4> = Hour: 0 to 23
<NRf5> = Minute: 0 to 59
:INTEgrate:STATe?
Function Queries the measurement status.
Syntax
:INTEgrate:STATe?
:INTEgrate:STATe
<NR1>= 0: Stop
1: Ready for measurement
2: Integration in progress
:INTEgrate:STOP?
Function Queries all the settings relating to
the end of measurement.
Syntax
:INTEgrate:STOP?
:INTEgrate:STOP:EXECute
Function Stops measurement.
Syntax
:INTEgrate:STOP:EXECute
App
App 2-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cw121

Table of Contents