PPX:505–6860 RS-485/RF I/O Channel Converter
About this Product
These instructions describe the installation of a
PPX:505–6860 RS-485/RF I/O Channel
Converter in the SIMATIC
controller system.
The PPX:505–6860 converter allows the use of
coaxial cables in a 505 system (extending the
maximum distance to 4 km) by converting the
RS-485 interface to an RF interface. This also
permits use of dual media from a 545/555 to the
I/O bases.
Installing a PPX:505–6860 converter also
allows you to update an existing 560/565
system, that is already using coaxial cables,
with a 545/555 and 575 CPU providing the
advantages of greater speed, dual media, and
greater remote distance.
Organization of Instructions
Compatibility Issues
Installation Procedure
Upgrading from a 560/565 system to a
545/555
Upgrading from a 560/565 system to a 575

Installation Instructions

r
505 programmable
Related Manuals
The following manuals contain information
related to the installation of the PPX:505–6860
converter and cables:
SIMATIC 505 Redundant I/O System
Manual (PPX:505–8125–x).
SIMATIC 545/555 System Manual
(PPX:555–8101–x).
SIMATIC 575 System Manual
(PPX:575–8101–x).
SIMATIC 505 Programming Reference
Manual (PPX:505–8104–x).
The user manual for your release of
TISOFT programming software.
The system manual(s) for your
controller(s).
Technical Assistance
For technical assistance, contact your Siemens
Industrial Automation, Inc., distributor or sales
office. If you need assistance in contacting your
U.S. distributor or sales office, call
1–800–964-4114.
SIMATIC is a trademark of Siemens AG.
TISOFT, Series 500, Series 505, and Peerlink are
trademarks of Siemens Industrial Automation, Inc.
BELDEN
Copyright 1995 by Siemens Industrial Automation, Inc.
1
2586546–0009
02/95
All Rights Reserved — Printed in USA

Advertisement

loading

Summary of Contents for Siemens PPX:505–6860 RS-485/RF I/O

  • Page 1: Installation Instructions

    Upgrading from a 560/565 system to a U.S. distributor or sales office, call 545/555 1–800–964-4114. Upgrading from a 560/565 system to a 575 SIMATIC is a trademark of Siemens AG. TISOFT, Series 500, Series 505, and Peerlink are trademarks of Siemens Industrial Automation, Inc. BELDEN 2586546–0009 02/95 Copyright 1995 by Siemens Industrial Automation, Inc.
  • Page 2: Compatibility Issues

    Compatibility Issues Compatibility with Power Supplies Before installing the PPX:505–6860 converter, ensure that your system hardware is The PPX:505–6860 RS-485/RF converter can be compatible with the PPX:505–6860, as defined powered by the following supplies: below: PPX:505–6660 115/230 VAC Compatibility with Bases PPX:505–6660A 115/230 VAC The PPX:505–6860 RS-485/RF converter can be...
  • Page 3: Installation Procedure

    Connector Pin Connector Pin Description RF To Ground I/O BASES (Shields D485– 505–6860 RTS485– D485 RTS485 Figure 1 PPX:505–6860 Bezel Table 1 Pin-out Specifications 2586546–0009 02/95 Copyright 1995 by Siemens Industrial Automation, Inc. All Rights Reserved — Printed in USA...
  • Page 4 Upgrading an RF-Based TI560/TI565/TI560T/TI565P to a TI545/TI555/TI575 To upgrade an existing RF-based 560, 560T, Re-number your bases between 1 and 15 so 565, 565P system, replace the existing that no two bases have the same number. programmable controller, including its chassis, Base number 0 is the local base where the its power supply, and all its installed boards CPU resides and may be used for...
  • Page 5 NOTE: No remote bases can be connected on the RS-485 link between the 545/555 and the PPX:505–6860. Figure 2 Upgrading an RF-Based 560/565/560T/565P System to a 545/555 2586546–0009 02/95 Copyright 1995 by Siemens Industrial Automation, Inc. All Rights Reserved — Printed in USA...
  • Page 6 Upgrade Path VMEbus VME Base Local I/O #8 copper ground strap Bases must be within three feet of each other and connected by a #8 copper ground strap. – – Series 505 Base Remote Series 500/505 Bases with RF RBCs NOTE: No remote bases can be connected on the RS-485 link between the 575 and the PPX:505–6860.