Segmented Cr - Siemens SIMATIC S7-400 Installation Manual

Automation system, hardware and installation
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Installing the S7-400
2.3

Segmented CR

Properties
The "segmented" characteristic relates to the configuration of the CR. In the
(non-segmented) CR the I/O bus is continuous and interconnects all 18 or 9 slots;
in the segmented CR, however, the I/O bus consists of two I/O bus segments.
A segmented CR has the following important characteristics:
• The communication bus is continuous (global), whilst the I/O bus is divided into
two I/O bus segments of 10 and 8 slots respectively.
• One CPU can be inserted per local bus segment.
• The two CPUs in a segmented CR may be in different operating states.
• The two CPUs can communicate with each other via the communication bus.
• All the modules inserted in a segmented CR are powered by the power supply
module at slot 1.
• Both segments have a common backup battery.
The following figure shows a segmented CR with divided I/O bus and continuous
communication bus.
2-8
1
SEG1
1
2
3
4
5
6
SEG1
SEG1
SEG1
SEG1
SEG1
SEG1
SEG1
I/O bus
Segment 1
11
SEG2
7
8
9
10
11
12
13
SEG1
SEG1
SEG1
SEG2
SEG2
SEG2
Segment 2
Communication bus
Automation System S7-400 Hardware and Installation
14
15
16
17
18
SEG2
SEG2
SEG2
SEG2
SEG2
I/O bus
A5E00850741-01