7.7

Replacing the Fuse of the Fan Subassembly

Fuse Type
The fuse of the fan subassembly is a standard 5 x 20 mm cartridge fuse to DIN and
not a spare part.
Use the following fuse:
• 160 mA slow blow if the voltage selector switch is set to 230 V
• 250 mA slow blow if the voltage selector switch is set to 120 V
Replacing the Fuse
To replace the fuse of the module, follow the steps outlined below:
1. Disconnect the power cable of the fan subassembly from the supply.
2. Use a screwdriver to unscrew the fuse cap.
3. Remove the blown fuse from the fuse cap.
4. Insert the new fuse in the fuse cap and screw the cap into the fan subassembly.
5. Connect the power cable of the fan subassembly to the supply.
Automation System S7-400 Hardware and Installation
A5E00850741-01
Voltage selector switch
Fuse cap