Finishing; Hearth Extension - Heat & Glo EXCLAIM-42H-C Owner's Manual

Installation and operation
Table of Contents

Advertisement

8 8

Finishing

A. Hearth Extension
A hearth extension must be installed with all replaces to
protect the combustible oor in front of the replace from
both radiant heat and sparks. See Figures 8.1 -8.4.
High temperature
(300°F min.) continuous,
non-combustible sealant
HX3 or HX4
Hearth Ext
Tile, stone or other
or equivilent
non-combustible material
insulation
(see Table below)
Floor constructed of wood or
other combustible material
Figure 8.1
Hearth Extension Construction
WARNING
Fire Risk
Metal hearth strips MUST be installed.
Sparks or embers may ignite ooring.
This replace has been tested and approved for use with a
hearth extension insulated to a minimum R value of 1.16.
To substitute materials for the factory-available hearth ex-
tensions, see Figure 8.3 and calculate insulation alterna-
tives as per Table 8.1 and the following formulas:
Thermal conductivity per inch thickness = k
k = (BTU)(inch) / (foot
Required thickness = Rk
Thermal resistance per inch thickness = r
2
r = (foot
)(hour)(°F) / (BTU)(inch)
Required thickness = R / rB.
Table 8.1
Hearth Extension Insulation Alternatives, R Value = 1.16
Material
Hearth & Home HX3, HX4
USG Micore 300™
USG Durock™ Cement Board
Cement Mortor
Common Brick
Ceramic Tile
Armstrong Privacy Plus
Marble
28
Protective
Metal Hearth
Strip
2 in. (51 mm)
required
2
)(hour)(°F)
k per inch
r per inch
thick
thick
0.43
2.33
0.46
2.18
1.92
0.52
5.0
0.20
5.0
0.20
12.50
0.08
14.3-20.0
0.07-0.05
Heat & Glo • EXCLAIM-42C • 4013-094 Rev I • 10/06
Metal strips are placed 2 in. (51 mm) under the front
of the fireplace and must extend beyond the front
and sides of fireplace opening by 2 in. (51 mm)
Figure 8.2
Positioning the Protective Metal Hearth Strips
Minimum thickness
required
1/2 in.
1/2 in.
2-1/4 in.
5-7/8 in.
5-7/8 in.
14-5/8 in.
16-5/8 in. - 23-3/8 in.
WARNING
Fire Risk
Hearth extensions must be installed
exactly as speci ed.
High temperatures or hot embers may ignite
concealed combustibles.
1 in. overlap
.