Vent Connection; Exterior Vents; Vent Sizing; Vent Connection To Boiler - PEERLESS SERIES 211A Installation, Operation & Maintenance Manual

Gas boilers-steam
Table of Contents

Advertisement

0
0
all combustion
products.
If the vent system does not
provide enough draft, combustion products will spill into
the building from the draft hood relief opening. If spillage
of combustion
products occurs, check the vent system,
the combustion
and ventilation openings and make sure
the boiler room is never under negative pressure.
Failure
to
provide
adequate
venting
can result
in severe
injury
or death.
4. Exterior Vents
a)
If the vent is outside,
make
sure it is insulated
sufficiently to ensure adequate
draft.
5. Vent Sizing:
a)
Individual vents: Use vent piping the same diameter
as the boiler vent connection. The minimum height
is I0 feet above the bottom of the draft hood (relief
opening). The vent must also extend above the roof
or any obstiructions as outlined in the current edition
of
the
National
Fuel
Gas
Code,
ANSI
Z223.1/NFPA54
or as required by local codes.
b)
Combined
vent-
breeching:
• The recommended
sizing in Section 14, "Boiler
Ratings and Dimensions",
in this Manual is based
on a minimum chimney or vent height of 20 feet
and a maximum
horizontal
run of 6 feet to the
chimney
with no more
than
one
90-degree
standard elbow.
• The minimum area of the chimney serving two or
more appliances
must be at least the area of the
largest chimney connector
plus 50% of the total
area of all other appliance
connectors.
• The vent connector
must be single wall steel or
Type B double wall vent pipe. The vent connector
must be Type B double wall if it is located in or
passes through
cold areas. The vent connector
must extend into, but not beyond, the inside wall
of the chimney.
6. Vent Connection
to Boiler (Figure 6):
a)
Provide
at least
a three
foot rise in the vent
connection
on the boiler.
b)
The vent system should provide a draft of at least
0.02" w.c. measured
at the vent connections.
c)
Support the weight of the vent system indepently of
the boiler draft hood. The draft hood is not designed
to carry structural loading.
d)
Provide support ofthe vent connector
(breeching] at
maximum
12 foot intervals to prevent sagging and
to provide a minimum upward slope of I/4" per foot.
e)
Do not connect the vent for this boiler into any vent
system which operates with positive pressure.
f)
Use Type B double-wall
pipe for vents which run
through unheated
spaces.
7.
Removing
an existing boiler from a common vent: At the
time for removal
of an existing boiler, the following
steps
shall be followed
with each appliance
connected
to the
common
venting system placed in operation,
while the
other appliances
remaining
connected
to the common
venting system are not in operation.
Recommendedsizingfor chimney and connectors is
based on maximum 6 foot connector length and
maximum one 90 degree elbow.
Frovide suppo_for I_lz_taJ secl_s to preventsagging •
Slopeve_t connectorupw_d min 1/4 inch perfoot --
T
Connlz_t or must notprotrudeinlo chimney
Boi)erven_ c0nnect0r shCuldbeh_ghet
than 0tha:connect e d app_ances
I_Do
not obs_ct
draft.hood openfn_
Figure 6:
Vent Connection
a)
Seal any unused openings
in the common
venting
system.
b)
Visually inspect the venting system for proper size
and horizontal
pitch and determine
there is no
blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.
c)
Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected
to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliance
not connected to the common venting system. Turn
on any exhaust
fans, such as range hoods
and
bathroom
exhausts,
so
they
will
operate
at
maximum speed. Do not operate a summer exhaust
fan. Close fireplace dampers.
d)
Place in operation
the appliance
being inspected.
Follow
the
lighting
instructions.
Adjust
the
thermostat so appliance will operate continuously.
e)
Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar or pipe.
f)
After it has been determined
that each appliance
remaining connected to the common venting system
propedy vents when tested as outlined above, return
doors, windows,
exhaust
fans, fireplace
dampers
and
any other
gas-burning
appliance
to their
previous condition of use.
g)
Any improper
operation
of the common
venting
system
should
be corrected
so the
installation
conforms with the current edition of the National
Fuel Gas Code,
ANSI Z223.1/NFPA54.
When
resizing any portion of the common venting system,
the common
venting system should be resized to
approach the minimum size as determined
using the
appropriate
tables located in the chapter "Sizing of
Category I Venting Systems" in the current edition
of the National Fuel Gas Code, ANSIZ223.1/NFPA54.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents