FS-8700-66 GE-SNP Driver Manual

6.3.2 Driver Specific Map Descriptor Parameters

Column Title
Function
Node_Name
Name of Node to fetch data from
Data type
Data_Type
Use one of the Data Types specified in brackets.
Length of Map Descriptor – may not exceed the table length
Length
in the PLC.
Starting address of read block / write block
Address
The 1st element of each Data type Table is referred to as
address one.

6.3.3 Timing Parameters

Column Title
Function
Specifies time Server side waits before responding to Client that Node is
Scada_Hold_Timeout
offline on FieldServer Client side.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Page 16 of 28
Legal Values
One of the Node names
specified
in
"Client
Node
Descriptor" above
Discrete Inputs (%I)
Discrete Outputs (%Q)
Discrete Temporaries (%T)
Discrete Internals (%M)
Genius Global Data (%G)
Analog Inputs (%AI)
Analog Outputs (%AQ)
Registers (%R)
%SA Discrete
%SB Discrete
%SC Discrete
%S Discrete (%S)
1 - 1000
1 , 2 , 3
Positive whole numbers
Legal Values
>1.0s