Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
SrcRmTempActSpt
Current temperature control point (i.e. the current actual space temperature setpoint that the node is trying to
maintain in the conditioned space) is reported in StatusRmTmpActSpt and SrcRmTempActSpt.
SrcRmTempActSpt is updated from StatusRmTmpActSpt according to the SGPU mechanism where a
significant change is plus or minus 0.07 degrees C.
SrcSchedOcc0
SrcSchedOcc0 is the effective occupancy arbitrated from the internal schedule of the T7300 (in local schedule
mode). SrcSchedOcc0 is used to control the occupancy of other LonWorks
SrcSchedOcc1
Same as SrcSchedOcc0.
SrcSchedOcc2
Same as SrcSchedOcc0.
SrcSchedOcc3
Same as SrcSchedOcc0.
SrcRmTempSpt
Can be bound to DestRmTempSpt in another node to affect the temperature setpoint of another node.
SrcRmTemp
SrcRmTemp is the room temperature used to control the temperature of the room. If DestRmTemp is Invalid,
then the local and/or remote sensor (as selected by TempSensor) is reported in StatusRmTemp and
SrcRmTemp. If DestRmTemp is not invalid, then DestRmTemp is reported in StatusRmTemp and
SrcRmTemp. If DestRmTemp is invalid and the local and/or remote sensor (as selected by TempSensor) is
also invalid (because of sensor failure), then StatusRmTemp and SrcRmTemp are also invalid and room
temperature can no longer be controlled by this node.
SrcSecond
Time-of-day in 24-hr format.
Table A5. Shared Points (Right Continued).
57
Comments
]
Bus devices.
(continued)
63-4366