Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
SelectedFile
The index number of the file that was last selected for data transfer.
OpenCircuit
Not supported, set to zero.
OutofLimits
Not supported, set to zero.
OutofService
Not supported, set to zero.
ProgFail
Not supported, set to zero.
ProgMode
Not supported, set to zero.
ReportMask
Internal use only.
SchedHour
The hour of the event; 0 through 23 hrs.
SchedMinutes
The minutes of the event. T7300 implements event times in 15-minute increments. If values other than 0, 15,
30, and 45 are written, SchedMinutes is changed to the nearest permitted value.
SchedOcc
The occupancy state of the schedule can be one of the states listed. In case SchedOcc is not one of the
permitted values, SchedOcc is changed to the SchedOcc(read) as listed:
NrTimeModes
There are four time mode events per day in this schedule. NrTimeModes is always four. Attempts to write
another value causes the write to the file to be ignored.
Scheduleld
ScheduleId is assigned by a tool for later schedule identification by a user interface that displays or changes
the schedule. Saved in EEPROM.
Table A1. Miscellaneous (Right Continued).


Occ, Bypass, Standby
Space is scheduled to be occupied.

UnOcc
Space is scheduled to be unoccupied.
Null and any other
Schedule entry is ignored.