Download Print this page

Honeywell Q7300H System Integration Manual page 45

Communicating subbase system integration user address manual
Hide thumbs Also See for Q7300H:

Advertisement

Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
InvalidSetPtAlrm
One of the space temperature points in nciSetpoints is not in the valid range. The node automatically corrects
invalid values of nciSetpoints to a valid nciSetpoints value within 5 to 60 seconds. InvalidSetPtAlrm is a
temporary alarm that automatically returns to normal.
NodeDisableAlrm
Control algorithm has stopped because the controller is in Disabled or Manual StatusMode. No more alarms
are reported via nvoAlarm and nvoAlarmLog when StatusMode is Disabled and the last alarm issued is
NodeDisableAlrm.
DestBypassErr
A bound network variable has not been received for at least the failure detect time and the default has been set
to the default value.
DestSetPtOffsetErr
A bound network variable has not been received for at least the failure detect time and the default has been set
to the default value.
DestTimeErr
A bound network variable has not been received for at least the failure detect time and the default has been set
to the default value.
DuctTempSenErr
No action.
InAlarm
If alarm reporting is not suppressed and alarms are currently active, then InAlarm is set to True, otherwise
InAlarm is set to False.
MechanicalFault
Not supported, set to zero.
Table A4. Alarm Points (Right Continued).
45
Comments
(continued)
63-4366

Advertisement