Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
NrCoolStages
0-3 stages for heat pump subbases; 0-2 stages for conventional subbases.
OBMode
False
True
Valid values are: 0
OvrdPriority
Configures the override arbitration between DestManOcc, DestBypass and the thermostat temporary occupied
and continuous unoccupied buttons. Valid values are as follows:
SensorCal
Allows the thermostat sensor to be calibrated according to the following values:
SetFactDefault
Restore the installer set up values to the factory default values.
Valid values are: 0
SystemSw
AutoManual
ManualOnly
AutoOnly
Valid values are: 0
TempSensor
Selects space temperature sensor to control room termperature using the following parameters:
TODOffset
0-15 degrees F.
RcvHrtBt
The SGPUC and SGPU time (heartbeat time) between updates of network variable outputs as listed in the
table of network variables is nciSndHrtBt. The failure detection time for network variable outputs as listed in the
table of network variables is nciRcvHrtBt.
NOTE:
SndHrtBt
The SGPUC and SGPU time (heartbeat time) between updates of network variable outputs as listed in the
table of network variables is nciSndHrtBt. The failure detection time for network variables outputs as listed in
the table of network variables is nciRcvHrtBt.
NOTE:
Table A2. Configuration Points (Right Continued).


Installer parameter has a 0 state.

Installer parameter has a 1 state.
O on in Cool, B on in Heat; 1

LastWins
Last command received from the thermostat occupancy buttons. DestBypass or DestManOcc

determines the effective override state.
NetWins
When DestManOcc is not Null, then the effective occupancy is DestManOcc regardless of
DestBypass and the thermostat occupancy buttons.
0 = adds 0 to the sensed temperature.
1 = adds 1 degree F to sensed value.
2 = adds 2 degrees F to sensed value.
3 = adds 3 degrees F to sensed value.
-1 = adds –1 degree F to sensed value.
-2 = adds –2 degree F to sensed value.
-3 = adds –3 degrees F to sensed value.

Do not set factory default values; 1


System switch choices are not restricted.

System switch choices do not allow an Auto position.


System switch has only an Auto position.
1; 1
no auto; 2


Local Sensor
The thermosat uses the local space temperature sensor to control the room temperature.
RemoteSensor
The thermostat uses the remotely wired space temperature sensor to control the room

temperature.
Average
The thermostat uses the average of the local space temperature sensor and the remotely wired
space temperature sensor to control the room temperature.
nciSndHrtBt should be set to 55 seconds and nciRcvHrtBt should be set to 300 seconds by a
management node to be compatible with a Honeywell system.
nciSndHrtBt should be set to 55 seconds and nciRcvHrtBt should be set to 300 seconds (by a
management node) to be compatible with a Honeywell system.
Comments

B on in Cool, O on in Heat.

Restore factory default values.

auto only.