Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
InterStgDeadBand
0 to 12 degrees F.
KeyBdLockOut
Normal
Lock
LockAll
Valid values are: 0
Temporary Setpoint adjustments).
LockOutInstaller
False
True
Valid values are: 0
MinCompOffTime
0 to 5 minutes.
MinHeatOffTime
0 to 4 minutes.
MinOnTime
0 to 2 minutes.
NoHeatCoolDsply
False
True
Valid values are: 0
NoTempDsply
False
True
Valid values are: 0
MinCoolSetPt
MaxHeatSetPt and MinCoolSetPt are the maximum allowed heating setpoint and minimum allowed cooling
setpoint used by the thermostat (see installer setup features of thermostat). MaxHeatSetPt sets the
Temperature range stops in heating parameter (Installer Setup Parameter No. 34) and MinCoolSetPt sets the
Temperature range stops in cooling (Installer Setup Parameter No. 35) in the T7300. The thermostat limits the
temporary heating setpoint to a maximum value of MaxHeatSetPt and limits the temporary cooling setpoint to a
minimum of MinCoolSetPt. The subbase also uses MaxHeatSetPt and MinCoolSetPt to limit the range of
setpoints.
NodeObjSendT
The maximum time between updates of network variable outputs (nvoStatus) from the node object is
NodeObjSendT.
HeatUnoccSpt
NciSetpoints specify the scheduled space temperature setpoint for various operating modes and effective
occupancy. Setpoints may be changed during day-to-day operation of the node by a networked operator
interface. When the local schedule is active, nciSetpoints can also be changed from the front panel of the
thermostat. The fields specify the setpoint temperature for heating and cooling modes and effective occupancy
(Occ, Standby, or UnOcc).
MaxHeatSetPt
MaxHeatSetPt and MinCoolSetPt are the maximum allowed heating setpoint and the minimum allowed cooling
setpoint used by the thermostat (see installer setup features of thermostat). MaxHeatSetPt sets the
Temperature range stops in heating parameter (Installer Setup Parameter No. 34) and MinCoolSetPt sets the
Temperature range stops in cooling (Installer Setup parameter No. 35) in the T7300. The thermostat limits the
temporary heating setpoint to a maximum value of MaxHeatSetPt and limits the temporary cooling setpoint to a
minimum of MinCoolSetPt. The subbase also uses MaxHeatSetPt and MinCoolSetPt to limit the range of
setpoints.
Table A2. Configuration Points (Right Continued).


No keyboard keys are locked out.

Lockout program keys.


Lockout the keyboard, except Time Set and Temporary Setpoint adjustments.
none; 1
lockout program keys; 2


Installer parameter has the 0 state.


Installer parameter has the 1 state.
no lockout; 1
Lockout installer setup.


Installer parameter has the 0 state.
Installer parameter has the 1 state.

Display temperature; 1


Installer parameter has the 0 state.

Installer parameter has the 1 state.
Normal display; 1
Comments

lockout total keyboard, (except Time Set and

Do not display temperature.

Suppress display of Heat on and Cool on.
29
(continued)
63-4366