Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
AssignNode
Node number of the mode to which this node is bound.
AssignObjId
Assigned object number of the object in this node to which this node is bound.
AssignSchedId
Assigned object number of the schedule object in this node. This should be the same for all four entries and
should be set to SchedulId in the schedule file by the configuration tool.
AssignSubnet
Subnet number of the node to which this node is bound.
AssignNrObj
There are four entries in this field that specify which nodes are related to the schedule.The four entries specify
which node is bound to the four nvoOccSchudleX ouputs; 0 = nvoOccSchedule0, 1 = nvoOccSchedule1, 2 =
nvoOccSchedule2, 3 = nvoOccSchedule3.
ApplicationType
Future use.
BypTime
Time between the pressing of the Temporary Occupied button on the thermostat (or initiating Bypass via
DestManOcc) and return to the original scheduled state. DestBypass does not start the Bypass timer. This field
sets the duration of temporary override parameter (Installer Setup Parameter No. 26) in the T7300. When the
bypass state has been activated, the bypass timer is set to BypTime. The only valid bypass times allowed are
60 minutes, 180 minutes, 480 minutes, or 720 minutes. If BypTime is not set to one of these times, the
subbase automatically changes the BypTime to the nearest valid time.
DeviceName
18-character field that identifies the node uniquely as one object at the site or project. Contents of DeviceName
is maintained by a management node. If DeviceName is all ASCII blanks, it is unconfigured.
BugVersion
Software version per E-Bus Mechanism document.
EVObjectldin
EVObjectldin selects the object being referenced by nviRequest. All other EVObjectldin are invalid. The objects
in the node are: 0
EVObjectRqst
Normal
UpdateStatus
ReportMask
Enable
Disabled
AlarmNorifyDisabled
AlarmNotifyEnabled
ManualControl, SelfTest, Updatealarm, Override, RemoveOverride, ClearStatus ClearAlarm, RemoteControl,
ObjectID
Set to the current value of EVObjectldin.
Table A1. Miscellaneous (Right).


Node Object; 1

Report the status (via nvoStatus) of the object addressed by EVObjectldin and enable automatic

control of all outputs. (See StatusCmdMode).

Report the status (via nvoStatus) of the object addressed by EVObjectdin.
Report the status bits that are supported in nvoStatus by the object addressed by EVObjectldin.

Bits that are supported by the object are set to one. The other fields are set to False.

Enable automatic control outputs. (See StatusCmdMode).
Disable automatic control and turn off all outputs. (See StatusCmdMode).


Disable alarm reporting.
Enable alarm reporting.
Program, Null, Other Unspecified Value
status.
Comments
Thermostat Object.

Not supported. NvoStatus returns an InvalidRequest in the object