1-The oil burner is suppliedwitha mountingflangefixed in position.
2 - Mountthe burner to the combustionchambercoverplate(Item5) withfour (4) 5/r6"studs and nuts provided.
BE SUREHI TEMPGASKETIS BETWEENTHE BURNERMOUNTINGFLANGEAND THE COMBUSTION CHAMBERCOVERPLATE.
3 - Caremustbe takenwhen routingthe oil lines so not to interferewith the openingand closingof the door.Flexibleoil linesor flared copperdiscon-
nects withvalves(whencopperlinesare used) may be installedto assurefull openingof the door when servicing.
4 - Oil BurnerSpecifications:
For informationpertinentto the oil burner such as nozzlesizing,fuel supply piping,adjustingor servicing,referto the charts belowand the installa-
tion manualaccompanyingthe burner.
BECKETTBURNERWITH140 PSI PUMP PRESSURE
Boiler
Burner
Burner
Static
Nozzle
Start-Up Settings
Head
ModelNo,
Model N o.
Head
Plate
Size
AirShutter
AirBand
Setting
WBV-03-085
AFG-F3*
F3
33/8"
0.7580" B HAGO
6.0
1
N/A
WBV-03-110
AFG-F4
F4
33/8 "
0.9080° B HAGO
6.0
0
N/A
WBV-04-095
AFG-F4
F4
33/8 "
0.85800B DEL
6.0
0
N/A
WBV-04-125
AFG-F4
F4
33/8"
1.10800B HAGO
5.0
2
N/A
WBV-04-150
AFG-F6
F6
23/4"
1.25800B HAGO
8.0
1
N/A
WV-05-175
AFG-MV1
V-1
1.5060° B HAGO
10.0
3
3
WV-05-200
AFG-MV1
V-1
1.7560° B HAGO
10.0
9
3
*RequiresLow F_ring
Rate Baffle
WAYNEBURNER WITH 100PSI PUMP PRESSURE
Boiler
Burner
AirCone
Nozzle **
Start-Up Settings
Model N o,
Model N o,
I,D.
Size
Flame Lock
Off-Cycle D amp,
AirShutter
WBV-03-085
HS
21/2 " NoHoles
0.85 80° B
1
t.0
0.50
WBV-03-110
HS
21/2"NoHoles
1.10 80" B
1
2.0
1.50
WBV-04-125
HS
21/2"6 Holes
1.25 80° B
1
2.0
1.75
WBV-04-150
HS
21/2 ,, 6 Holes
1.50 80° B
1!/2
2.0
2.00
WV-05-175
HS
21/2"6 Holes
1.75 80° 8
3
2.0
2,25
WV-05-200
HS
21/2"6 Holes
2.00 80° B
5
2.0
2.50
** DelavanRecommended
CARLIN99FRDOIL BURNERWITHMODEL98022PSCMOTOR
Boiler
Burner
Start-Up Settings
Model N o.
Model N o.
AirShutter
Nozzle Size
Pump Pressure
HeadDim.A
AirBand
WV-05-175
99FRD
Open
1.50x 600B HAGO
150PSi
5
10% open
WV-05-200
99FRD
Open
1.65x 600B HAGO
150PSI
5
45% open
CARLINEZ-1HPOIL BURNERWITHMODEL98022PSCMOTOR
Boiler
Burner
Start-Up S ettings
ModelNo.
Model N o.
AirShutter
Nozzle Size
Pump Pressure
AirBand
HeadBar
WBV-03-085
EZ-IHP
Blank
0.65 x 70° A DEL
150PSI
0.60
0.60- 0.65
WBV-03-f10
EZ-1HP
Blank
0.85 x 700A DEL
150 PSI
0.65
0.85- 1.00
WBV-04-095
EZ-1HP
Blank
0.75 x 70° A.DEL
150 PSI
0.60
0.75
WBV-04-125
EZ-1HP
Blank
1.00x 700A DEL
150PSI
0.85
0.85- 1.00
WBV-04-150
EZ-1HP
Blank
1.25x 60° B DEL
150 PSI
1.00
1.10- 1.25
NOTE:Start-upandAdjustment Recommendations...Adjustburner forhighest C O2 (Maximum13%)whilemaintaininga 0 Smokeand
-.01 to -.02" W.C.OverfireDraft.All adjustmentsmustbe madeusing suitableinstrumentssuch asfound in a 8acharachCombustion
TestKit.