Spark Plugs; Air Cleaner Element And Precleaner; Precleaner Service; Paper Element Service - Kohler 12RES Operation And Installation Instructions Manual

Residential/commercial generator sets, controller: advanced digital control
Hide thumbs Also See for 12RES:
Table of Contents

Advertisement

d. Reconnect the generator
set engine starting
battery, negative (-) lead last.
e. Reconnect the power to the battery charger.
f. Start and run the generator set for a minute to
allow the oil pressure to reach the operating
range.
g. Stop the generator set, wait I minute, and then
recheck the oil level. Add oil to bring the level
up to the F mark on the dipstick.
4. Check for leaks.
a. Check for oil leaks.
b. Fix leaks and recheck the oil level.
c. Reinstall the housing side panel.
3.4
Spark Plugs
Reset the spark plug gap or replace the plugs with new
plugs as necessary.
1. Clean the area around the base of the spark plug to
keep dirt and debris out of the engine.
2. Remove the spark plug and check its condition.
Replace the spark plug if it is worn or if its reuse is
questionable.
3. Check the spark plug gap using a wire feeler
gauge.
Adjust the gap to 0.76 mm (0.030 in.) by
carefully
bending the ground
electrode.
See
Figure 3-3 and Figure 3-4.
Figure 3-3
Checking the Spark Plug Gap
Figure 3-4
Adjusting the Spark Plug Gap
1-514
1-511
3.5
Air Cleaner
Element and
Precleaner
The engine has a replaceable
high-density
paper air
cleaner element with an oiled foam precleaner.
See
Figure 3-5.
Check for a buildup of dirt and debris around the air
cleaner system. Keep this area clean.
Note: Operating the engine with loose or damaged air
cleaner components
could allow unfiltered air
into the engine causing
premature wear and
failure.
3.5.1
Precleaner
Service
Use the following
procedure
to wash and reoil the
precleaner as indicated in the service schedule.
Wash
and reoil the precleaner more often under extremely
dusty or dirty conditions.
1. Place the generator
set master switch
in the
OFF/RESET position.
2. Disconnect the power to the battery charger.
3. Disconnect the battery, negative (-) lead first.
4. Loosen the cover retaining knob and remove the
cover.
Remove the precleaner
from the paper
element. Wash the precleaner in warm water with
detergent. Rinse the precleaner thoroughly until all
traces of detergent are eliminated.
Squeeze out
excess water (de not wring). Allow the precleaner
to air dry.
5. Saturate
the precleaner
with new engine
oil.
Squeeze out all of the excess oil.
6. Reinstall the precleaner over the paper element.
7. Reinstall the air cleaner cover. Secure the cover
with the cover retaining knob.
8. Reconnect the power to the battery charger.
9. Reconnect
the
generator
set engine
starting
battery, negative (-) lead last.
3.5.2
Paper Element
Service
Use the following
procedure
to replace the paper
element
at the
intervals
specified
in the
service
schedule. Replace the paper element more often under
extremely dusty or dirty conditions.
12
Section 3 Scheduled
Maintenance
TP-6195
1/04

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8.5res

Table of Contents