Electrical Connections; Ac Load Lead Connections - Kohler 12RES Operation And Installation Instructions Manual

Residential/commercial generator sets, controller: advanced digital control
Hide thumbs Also See for 12RES:
Table of Contents

Advertisement

6.9
Electrical
Connections
6.9.1
AC Load Lead Connections
_1_ WARNING
Hazardous voltage.
Backfeed to the utility system can
cause
property
damage,
severe
injury, or death.
if the generator
set
is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnection
of
standby
and
normal sources of supply.
Grounding electrical equipment.
Hazardous voltage can
cause severe injury or death.
Electrocution
is possible
whenever
electricity
is present.
Open the
main circuit
breakers of all power sources before servicing the equipment.
Configure the installation to electrically ground the generator
set, transfer switch,
and related equipment
and electrical
circuits to comply with applicable codes and standards. Never
contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk of
electrocution.
Electrical
backfeed to the utility.
Hazardous
backfeed
voltage can cause severe injury or death. Install a transfer
switch in standby power installations to preventthe connection
of standby and other sources of power. Electrical backfeed
into a utility electrical system can cause severe injury or death
to utility personnel working on power lines.
NOTICE
Canadian installations only. For standby service connect
the output of the generator set to a suitably rated transfer
switch in accordance
with Canadian Electrical Code, Part 1.
Have an authorized
distributor/dealer
or a licensed
electrician make the following load connections.
Verify
that the electrical installation complies with the National
Electrical Code (NEC) and all applicable local and state
codes.
Connect
the
AC
output
leads
in the
controller
compartment to the AC circuit breaker. Route AC leads
through flexible conduit directly to the AC circuit breaker
box.
See Figure 6-1 for the recommended
electrical
inlet location.
Verify that the leads and conduit do not
interfere with the operation of the generator
set or
obstruct the service areas.
See Figure 6-13 and Section 5, Wiring Diagrams, for
the generator
set electrical connections.
Make the
following AC connections:
1. Connect the output leads going to the transfer
switch (L1/L2 black leads) to the AC circuit breaker
load side.
2. Connect the L0 white leads from the ATS and the
main panel to the neutral terminal.
3. Connect the green lead to the equipment ground
terminal (labeled GRD).
Verify that the electrical installation complies with the
National Electrical Code (NEC) and all applicable local
and state codes.
1
2
VIEW B-B
Bottom of Junction BOX
I
\
2,
3
GM29253A-F
1. Line circuit breaker
2, Ground terminal (GRD)
3, Neutral terminal (L0)
Figure 6-13 Field-Installed Wiring Connections
TP-6195
1/04
Section 6 Installation
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8.5res

Table of Contents