6.10 Accessories
Have
accessories
installed
by
an
authorized
distributor/dealer
or a licensed electrician.
Follow the
installation instructions provided with each kit.
Use
separate conduit for AC and DC leads to reduce the
possibility of electrical interference. Verify that the leads
and conduit do not interfere with the operation of the
generator set or obstruct the service areas. Verify that
the electrical
installation
complies with the National
Electrical Code (NEC) and all applicable local and state
codes.
See Section 5, Wiring Diagrams,
for more
information
regarding
generator
set
electrical
connections.
6.10.1
Common
Fault and Run Relay
Board
The optional relay board provides two additional relays
to control customer-provided
equipment:
• Common fault relay
• Auxiliary run relay
The optional relay board replaces the standard relay
board. The relay board location is shown in Figure 6-17.
Connect
customer
equipment
to the
relay
board
harness.
Figure 6-18 lists the customer connections.
The common fault relay is energized on a fault.
The
auxiliary run relay is energized when the generator set is
running.
Connect to each relay's normally open or
normally closed contacts depending on the application.
1
2
\
GM30414
1. Relay board
2. Relay board harness
Figure 6-17
Common
Fault and Run Relay Board
Harness
Lead
Connector
Number
Pin Number
Connection
88
6
Common fault normally open
89
2
Common fault common
90
3
Common fault normally closed
91
4
Run relay normally open
92
1
Run relay common
93
5
Run relay normally closed
I
Figure 6-18 Common Fault and Run Relay Board
Harness Connections
TP-6195
1/04
Section 6 Installation
35