Battery Charger Operation - Kohler 12RES Operation And Installation Instructions Manual

Residential/commercial generator sets, controller: advanced digital control
Hide thumbs Also See for 12RES:
Table of Contents

Advertisement

2.5.1
Battery Charger
Operation
Figure 2-8 illustrates the three-stage charging method.
Red and green LEDs indicate charger operation.
The
chart
in
Figure2-9
describes
the
LED
indicator
operation during each stage of the charging process.
Figure 2-8
Charging Method
Display
Operating
Condition
Red ON
When the red LED is on, it indicates the battery is discharged and the battery charger is recharging at the
Green OFF
BULK rate (stage 1). This charging rate is 6 amps,
While the red LED is on, the voltage measured (with
the battery charger on) will be 11.8-14 volts.
If the red LED stays on for more than 24 hours, refer to Section 4,5 in this manual,
Red ON
When both the green and the red LEDs are on, the battery charger is charging at an ABSORPTION
rate
Green ON
of between 1,5 and 5 amps (stage 2), This mode of charging gradually tops off your battery, and reduces
harmful sulfating.
While both LEDs are on, the voltage measured (with the battery charger on) should be
approximately
14,0-14.5
VDC.
If both LEDs stay on longer than 24 hours, refer to Section 4.5 in this manual.
Red OFF
When the green LED is on, the battery charger is charging at a FLOAT or MAINTENANCE
rate of less
Green ON
than 1.5 amps (stage 3), Your battery is now 90% charged and ready for use. This float charging current
will gradually decrease to as low as 0.1 amps as the battery reaches 100% charge.
It will now be kept at
full charge without overcharging,
If the green LED stays on when your battery is known to be low, refer to Section 4.5 in this manual.