AC WIRING NOTES FOR THE NON-MOBILE FX

AC HOT OUT
• AC hot output conductor (black) wire
gauge must be sized to the breakers and
loads.
AC NEUTRAL OUT/AC NEUTRAL IN
• Both neutral terminals are common with
each other within the FX.
• Only one neutral needs to connect at the
terminal if a separate common neutral bus
bar is installed.
CHASSIS GROUND
• Both CHASSIS GROUND terminals are
common within the FX.
• The AC input and AC output ground wires
can connect to these terminals or one can
be connected if a common ground bus
bar is installed.
AC HOT IN
• The AC hot input conductor (black) must
be supplied through a 60 amp maximum
AC branch rated circuit breaker.
• 6 AWG wire is required for the FX's AC
transfer switch.
13
����������
��������������
�����������������
�����������������
�������������
���������
������������
��������