Voltage Check (Additional Procedure) - HP 9000 Integrity rp8440 Installation Manual

Installation guide, fourth edition - hp integrity rx8640, hp 9000 rp8440 servers
Hide thumbs Also See for 9000 Integrity rp8440:
Table of Contents

Advertisement

1.
Take the AC voltage down to the lowest scale on the volt meter.
2.
Insert the probe into the ground pin for B0.
3.
Insert the other probe into the ground pin for B1.
4.
Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power
cord into the server cabinet.
3.
Measure the voltage between A0 and B0 as follows:
1.
Take the AC voltage down to the lowest scale on the volt meter.
2.
Insert the probe into the ground pin for A0.
3.
Insert the other probe into the ground pin for B0.
4.
Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power
cord into the server cabinet.
4.
Measure the voltage between A1 and B1 as follows:
1.
Take the AC voltage down to the lowest scale on the volt meter.
2.
Insert the probe into the ground pin for A1.
3.
Insert the other probe into the ground pin for B1.
4.
Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power
cord into the server cabinet.

Voltage Check (Additional Procedure)

The voltage check ensures that all phases (and neutral, for international systems) are connected
correctly to the cabinet and that the AC input voltage is within limits.
Perform this procedure if the previous voltage check procedure did not yield the expected results.
NOTE:
If you use an uninterrupted power supply (UPS), refer to applicable UPS documentation
for information on connecting the server and checking the UPS output voltage. UPS user
documentation is shipped with the UPS. Documentation is also available at:
http://www.hp.com/racksolutions.
1.
Verify that site power is OFF.
2.
Open the site circuit breakers.
3.
Verify that the receptacle ground connector is connected to ground. Refer to
connector details.
4.
Set the site power circuit breaker to ON.
Figure 2-25
Cabling and Powering On the Server
for
65

Advertisement

Table of Contents
loading

This manual is also suitable for:

9000 integrity rx86409000 rp8440

Table of Contents