Voltage Check (Additional Procedure) - HP Integrity rx7640 Installation Manual

Hp integrity rx7640 and hp 9000 rp7440 servers installation guide
Hide thumbs Also See for Integrity rx7640:
Table of Contents

Advertisement

4. Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power cord
into the server cabinet.
Step 3. Measure the voltage between A0 and B0 as follows:
1. Take the AC voltage down to the lowest scale on the volt meter.
2. Insert the probe into the ground pin for A0.
3. Insert the other probe into the ground pin for B0.
4. Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power cord
into the server cabinet.
Step 4. Measure the voltage between A1 and B1 as follows:
1. Take the AC voltage down to the lowest scale on the volt meter.
2. Insert the probe into the ground pin for A1.
3. Insert the other probe into the ground pin for B1.
4. Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power cord
into the server cabinet.

Voltage Check (Additional Procedure)

The voltage check ensures that all phases (and neutral, for international systems) are connected correctly to
the cabinet and that the AC input voltage is within limits.
Perform this procedure if the previous voltage check procedure did not yield the expected results.
NOTE
If you use an uninterrupted power supply (UPS), refer to the applicable UPS documentation for
information on connecting the server and checking the UPS output voltage. UPS user
documentation is shipped with the UPS. Documentation is also available at:
http://www.hp.com/racksolutions
Step 1. Verify that site power is
Step 2. Open the site circuit breakers.
Step 3. Verify that the receptacle ground connector is connected to ground. Refer to Figure 2-24 for
connector details.
Chapter 2
.
OFF
Installing the Server
Cabling and Power Up
77