Reassembling The Server - Fujitsu SPARC Enterprise M3000 Service Manual

Hide thumbs Also See for SPARC Enterprise M3000:
Table of Contents

Advertisement

2. Hold the two opaque handles on both sides of the motherboard unit and slide
the unit in while lowering it to align with the predetermined position from the
front of the server.
When mounting the motherboard unit in the server, take care not to damage the
connector.
3. Install and tighten the four screws to secure the motherboard unit in position.
6.4

Reassembling the Server

1. Align the shutter unit with the securing bracket on the power supply unit, and
secure it with the two screws.
2. Reconnect all the cables to their original connection destinations on the
motherboard unit.
3. Attach the air duct.
For details, see
4. Mount the PCIe cards
For details, see
5. Attach the top cover.
For details, see
6. If the equipment rack is supplied with a Quake-Resistant Options Kit or
stabilizer, return to its original position.
For details, see
page
7. Mount the power supply unit correctly.
8. Connect all the cables to the external interface block on the rear panel.
9. Power on the server.
This procedure includes the steps of reconnecting the power cord, checking the
LED status, and turning the mode switch on the operator panel to the Locked
position. For details, see
Command" on page
Section 5.3.2, "Attaching the Air Duct" on page
Section 8.3, "Mounting a PCIe Card" on page
Section 5.2.2, "Attaching the Top Cover" on page
Section 5.1.2, "Sliding the Server into the Equipment Rack" on
5-3.
Section 4.5.3.1, "Power-on by Using the XSCF
4-13.
Chapter 6
Motherboard Unit Replacement
5-6.
8-5.
5-4.
6-9