CLEARANCES
1. The minimum clearance to a side wall is 4". (See Fig. 1). NOTE:
The unit may be recessed and rest directly against side studs and
the inside surface of the rear wall.
2. The minimum
clearance to the ceiling is 4". (See Figure 1).
3. The minimum clearance to the floor is 0". (See Figure 1).
4. The minimum
clearance
from the side of the vent cap to any
protruding
obstructions,
or corners is 12". (See Figure 2b).
5. The minimum clearance from any window to the side of the vent
cap is 9" for DVCF403,
404, 407 and 408 (See Figure 2), and
12" for DVCF557,
558, 653, and 654 (See Figure 2b).
6. The minimum clearance from any overhanging
projection is 24"
to top of vent cap (See Figure 2).
7. RESIDENTIAL
GARAGE
INSTALLATION:
Gas utilization
equipment
in residential
garages shall be installed
so that all
burners and burner ignition devices are located not less than 18
inches (46 cm) above the floor. Such equipment shall be located,
or protected so it is not subject to damage by a moving vehicle.
Use care in selecting
a good location within the garage.
DO
NOT locate the appliance where heated air will be directed onto
a nearby parked vehicle. Paint may discolor or rubber may harden
and crack. DO NOT allow heated discharge air to blow directly
onto open or closed containers of paint, gasoline or other liquids
having flammable vapors.
FIGURE 1
24"]/iin.
[--][--]
,
ff]D
-12" _
_,,)
)
FIGURE
2 / DVCF403B,
404B, 407B, AND 408B
24'{ Mln.
DD
DD
FIGURE
2B / DVCF557B,
558B, 653B, AND 654B
Page 5