COZY DVCF407B-R Installation And Operation Instructions Manual page 14

Direct vent counterflow wall furnace
Table of Contents

Advertisement

OPTIONAL
SIDE DISCHARGE
KITS
SIDE DISCHARGE
ON CASING
1.
Use Optional Kit No. 306SR-A.
2.
Cut out and remove embossed area on casing side.
3.
Remove talockout from inner liner.
4.
Place
1-1/2" boot from kit through
opening,
matching flanges of boot to knockout on inner liner.
5.
Mark screw holes and remove boot.
6.
Drill holes with a 1/8" drill.
7.
Attach inner boot with screws provided.
8.
Place grille into position, drill holes into casing,
and attach with screws provided.
KIT NO. 306SR
SIDE REGISTER - FLUSH
SIDE DISCHARGE (With Extension Boot)
NOTE: Maximum boot length is 10 inches.
1. Use Optional Kit No. 30SRB-A.
2.
Cut opening in drywall as shown in Fig. 9.
3.
Position
plaster
ground as shown in Figure
9.
(Optional).
4.
Cut out and remove embossed section on casing side.
5.
Remove kalockout on inner liner.
6.
Put heater into position.
7.
Place inner boot into position, mark and cut boot
flush with watt. Place outer boot into position, mark
and cut boot flush with wall.
8.
Place boot trim into position, slide inner boot through
wall fiom adjacent room and attach to inner liner.
Slide outer boot through wall from adjacent room
and attach to casing side.
9.
Place grill in position and secure to wall.
ROUGH-INS
FOR SIDE DISCHARGE
Install plaster mounds as shown in Figure 9. NOTE:
When
side discharge Kit No. 30SRB is being used, furnace should be
set exactly 4" fiom side wall.
14-3/8"
SIDE
FIGURE 9
KIT NO. 30SRB
SIDE REGISTER W/BOOT
Page 14