OPERATION
Section 3 - Operation
1S kW Generator
Tile generator
is equipped
with
an external
15 amp,
120
volt,
GFCI
convenience
outlet
that
is located
in
tile
right
rear
of the
generator
enclosure.
_rhen
tile
generator
is running,
in the absence
of utility
power,
this
outlet
may
be
used
to power
items
outside
a
home
such
as lights
or power
tools.
This
outlet
may
also
be
used
when
utility
power
is present
by
run-
ning
the generator
in manual
mode.
This
outlet
does
not
provide
power
if the
generator
is not
running.
This
outlet
is protected
by a 15 amp
circuit
breaker
located
in the generator
control
panel
{Figure
3.1 ).
3.4
SEQUENCEOF AUTOMATIC
OPERATION
The
generator's
control
panel
houses
a control
logie
circuit
board.
This
board
constantly
monitors
util-
ity power
source
voltage.
Should
that
voltage
drop
below
a preset
level,
circuit
board
action
will
signal
the engine
to crank
and
start.
After
the engine
starts,
the
circuit
board
signals
the
transfer
switch
to acti-
vate
and
connect
load
circuits
to the standby
power
supply
(load
terminal
lugs
T l/T2
connect
to terminal
lugs
E l/E2).
Upon
restoration
of utility
source
voltage
above
a
preset
level,
generator
circuit
board
action
signals
the
transter
switch
to transfer
loads
back
to that
power
supply.
After
retranster,
the engine
is signalled
to shut
down.
The
actual
sequence
of operation
is
controlled
by
sensors
anti
timers
on a control
logic
circuit
board,
as follows:
A. Utility
Voltage
Dropout
Sensor
. This
sensor
monitors
utility
source
voltage.
* If utility
source
voltage
drops
below
about
70
percent
of the nominal
supply
voltage,
the sensor
energizes
a 15-second
timer.
° Once
the timer
has expired,
the engine
will crank
and
start.
B. Engine
Warm-up
Time
Delay
° This
mechanism
lets
the
engine
warm
tip
for
about
10 seconds
before
the
load
is transferred
to a standby
source.
C. Standby
Voltage
Sensor
* This
sensor
monitors
generator
AC output
volt-
age.
When
the voltage
has
reached
50 percent
of
the
nominal
rated
voltage,
transfer
to
standby
ear
occur.
D. Utility
Voltage
Pickup
Sensor
* This
sensor
monitors
utility
power
supply
volt-
age.
When
that
voltage
is restored
to above
70
percent
of the nominal
source
voltage,
a retrans-
ter time
delay
starts
timing.
14
E.Retransfer
Time
Delay
. This
timer
runs
for about
15 seconds.
° At end
of a 15-second
delay,
circuit
board
action
de-energizes
the
transfer
relay
in
the
transfer
switch.
° Retransfer
to utility
power
source
then
occurs.
E Engine
Cool-down
Timer
° When
the load
is transferred
back
to utility
power
source,
the
engine
cool-down
timer
starts
tin>
ing.
° The
timer
will run
for about
one minute,
and
the
generator
will then
shut
down.
3.5
MANUAt. TRANSFEROPERATION
@ 3.5.1
TRANSFERTO GENERATORPOWER
To start
the generator
and
activate
the transfer
switch
manually,
proceed
as lbllows:
1.
Set the generator's
AUTO/OFF/1VLA_NUAL
switch
to
OFE
2.
Set
the
generator's
main
circuit
breaker
to
its
OFF
(or OPEN)
position.
3.
%lrn
OFF the utility
power
supply
to the transfer
switch
using
the means
provided
{such
as a utility
main
line
circuit
breaker).
A
4_
Do not attempt
to activate
the transfer
switch
manually
unti[ all power
voltage supplies to the
switch have been positively
turned
off. FaiJure
to turn off all power
vottage supplies may result
in extremely
hazardous
and possibly fataJ etec-
tricaJ shock.
Use
the manual
transfer
handle
inside
the trans-
fer
switch
to
move
the
main
contacts
to
their
"Standby"position,
i.e.,
loads
connected
to
the
standby
power
source
(Figure
3.2).
Figure
3.2 - ManuM
Transfer
Switch
Operation
i
LOADCONNECTEDTO UTiLiTY POWERSOURCE
LOAD CONNECTEDTO STANDBYPOWERSOURCE
i
MANUAL TRANSFER
HANDLE
TRANSFER SWITCH
OPERATING LEVER