Refrigerant charge requirements: Total refrigerant charge will be required only if units are evacuated
during installation or maintenance. Total refrigerant charge = evaporator + lines + condensing unit.
NOTE
All condensing units and 3-ton evaporator units are fully charged with refrigerant. All 5 ton
evaporator units include a nitrogen holding charge only. See Table 21 for field charge
required. If field-supplied refrigerant piping is installed, refrigerant must be added to the
system.
Once all piping is complete, check for leaks and dehydrate the field piping as follows:
1. Pressurize the field piping to 150 PSIG (1034 kPa) using dry nitrogen with a trace of refrigerant.
Check system for leaks with a suitable leak detector.
2. After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum
on the field piping with a suitable pump.
3. After 15 minutes, check the pressure readings and, if they have not changed, break vacuum with
dry nitrogen. Pull a second vacuum to 250 microns or less. Recheck the pressure after 15 minutes.
Table 21
Unit refrigerant charge
R407C Charge
Model
BF/BU 036E
0.5 (0.2)
BF/BU 035E
0.5 (0.2)
BF/BU 060E
0.8 (0.4)
BF/BU 059E
0.8 (0.4)
MC_40/39A
12.9 (5.8)
MC_65/64A
26.1 (11.8)
PF_042A-_L
12.9 (5.8)
PF_041A-_L
12.9 (5.8)
PF_Z42A-_L
25.8 (11.7)
PF_Z41A-_L
25.8 (11.7)
Table 22
Line charges - refrigerant per 100 ft. (30 m) of Type "L" copper tube
R407C
Liquid Line
Suction Line
O.D.
lb (kg)
1/2"
7.3 (3.3)
5/8"
11.7 (5.3)
7/8"
24.4 (11.1)
1-1/8"
41.6 (18.9)
1-3/8"
63.3 (28.7)
Table 23
Recommended refrigerant lines (R407C) sizes OD copper
Equivalent Feet (m)
0-50 (0-15)
51-100 (16-30)
101-150 (31-45)
lb (kg)
Model
PF_042A-_H
PF_041A-_H
PF_067A-_L
PF_066A-_L
PF_Z67A-_L
PF_Z66A-_L
PF_067A-_H
PF_066A-_H
MC_44/43W
MC_69/68W
lb (kg)
-
0.4 (0.2)
1.0 (0.4)
1.7 (0.7)
2.7 (1.1)
3.5-Ton
036E (035E)
Suction
Liquid
7/8"
1/2"
1-1/8"
1/2"
1-1/8"
5/8"
58
R407C Charge
lb (kg)
25.8 (11.7)
25.8 (11.7)
25.8 (11.7)
25.8 (11.7)
50.1 (22.7)
50.1 (22.7)
50.1 (22.7)
50.1 (22.7)
3.4 (1.5)
5.9 (2.7)
5-Ton
060E (059E)
Suction
Liquid
1-1/8"
1/2"
1-1/8"
5/8"
1-3/8"
5/8"
Split System Models