Figure 2
Upflow (BU) cabinet dimensions
A
STD 3 & 5T
11-3/4 (299mm)
Hi Static 3T
8 5/8 (219mm)
Hi Static 5T
11-3/4 (299mm)
7-1/2"
(191mm)
29-3/4"
(756mm)
29"
(737mm)
REAR VIEW
(rear return configuration)
10-1/4"
(260mm)
Standard Piping Location
Projection of Display
Bezel 5/8" (16mm)
Filter Access
Through Top
1" (25mm)
FRONT &
SIDES
3/4" (19mm)
REAR
94"
(2388mm)
2-1/2"
(67mm)
(1930mm)
1-3/4 "
(44mm)
Shaded area indicates a recommended
clearance of 34" (864mm) for component
access. Right side access suggested for
GLYCOOL units.
32-1/2"
(826mm)
30-1/2"
(775mm)
A
8-1/2"
(216mm)
5-1/2" (140mm)
32-1/2"
32-1/2"
(826mm)
(826mm)
Overall
Overall
Dimension
Dimension
18"
(457mm)
76"
FRONT VIEW
(front return configuration)
7
Installation (Applicable to all Models)
UNIT
TOP VIEW
9-5/8"
(244mm)
1-5/8"
13"
(41mm)
(330mm)
30-1/2"
(775mm)
12-1/2"
1-7/8"
(318mm)
(48mm)
Standard Electrical Outlet
Location Through Unit
6-7/8" (175mm)
Standard Electrical Outlet
Location Through Plenum
Air Discharge Grille
Plenum available with:
-2, 3 or 4 grilles.
-Solid sides with a 7/8" (22mm)
duct flange on top.
Blower Outlet with
1" (25.4mm) Flange
7/8" (22.2mm) Flange for
Duct or Plenum Connection
Return Air Louvers
DPN000350
Rev. 01
32-1/2"
(826mm)