Figure 14 Air-Cooled Condensers; Table 4 Air-Cooled Condenser Statistics - Emerson Liebert Challenger 3000 Installation Manual

Environmental control systems
Hide thumbs Also See for Liebert Challenger 3000:
Table of Contents

Advertisement

Figure 14 Air-cooled condensers

FAN SPEED AND VFD CONDENSER
Liquid line
Secure each leg to condenser frame at all
points shown using hardware provided.
51-7/16"
(1306.5mm)
37-7/8"
(962mm)
43-3/16"
(1097mm)
1"
1-3/4"
(25.4mm)
(44.5mm)
1-3/4"
(44.5mm)
4-1/4"
(108mm)
TYPICAL FOOTPRINT
Table 4
Air-cooled condenser statistics
Number
Model
of Fans
083
1
104
1
165
2
Liebert Lee-Temp heater
pad connection box
Electric service
supplied by
others
* B
Hot gas line
43-9/16"
(1106mm)
1-3/4"
44"
(44.5mm)
(1118mm)
37-11/16"
(957.3mm)
4-1/4"
(108mm)
1-3/4"
(44.5mm)
1"
(25.4mm)
Connection Sizes
(OD Copper)
Hot Gas (in.)
Liquid (in.)
7/8
5/8
1-1/8
5/8
1-1/8
7/8
Air-Cooled Models—Self-Contained Compressor
*B - Inverted traps are to be field-supplied and installed
(typ). When installing traps, provide clearance for swing
end of access door. Traps are to extend above base of
coil by a minimum of 7-1/2" (190 mm)
SINGLE FAN AIR-COOLED CONDENSERS
18" (457.2mm)
CONDENSER MOUNTING
9/16" (14.3mm)
diameter holes
8 places for
1/2" (12.7mm)
diameter bolts
Common to all models. See Table 4
below for key to "A" dimension.
Net Weight
"A" Dimension
lb (kg)
295 (133.8)
42 (1067)
315 (142.8)
42 (1067)
425 (193)
82 (2083)
24
LIEBERT LEE-TEMP CONDENSER
* B
Electric
service
supplied by
Liquid line
others
1" typ.
(25.4mm)
A
in (mm)
Hot gas
line
1" typ.
(25.4mm)
1-3/4"
(44.5mm)

Hide quick links:

Advertisement

Table of Contents
loading