Installation (Applicable To All Models ); Room Preparation; Equipment Inspection; Location Considerations - Emerson Liebert Challenger 3000 Installation Manual

Environmental control systems
Hide thumbs Also See for Liebert Challenger 3000:
Table of Contents

Advertisement

2.0
I
NSTALLATION
2.1

Room Preparation

The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the
ceiling can be a polyethylene film type. Use a rubber or plastic base paint on concrete walls and floors.
Doors should not be undercut or have grilles in them.
Outside (or fresh) air should be kept to an absolute minimum. Outside air adds to the heating, cool-
ing, humidifying and dehumidifying loads of the site. It is recommended that outside air be kept
below 5% of the total air circulated in the room and be preconditioned.
2.2

Equipment Inspection

Upon arrival of the unit, inspect all items for visible and concealed damage. Damage should be imme-
diately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales
representative.
2.3

Location Considerations

The unit can sit on top of an accessible elevated flooring system. It may be necessary to furnish addi-
tional pedestal support below the unit to ensure maximum structural support (see Table 1). A sepa-
rate floor stand for the unit may be used as support, independent of the elevated floor and installed
prior to the flooring system.
Provide approximately 34" (864 mm) service clearance on the front of the unit.
NOTE
GLYCOOL units require 34" (864 mm) service clearance on the right side of the unit in
addition to front service clearance.
Avoid placing units in an alcove or at the extreme end of a room that has a high aspect ratio (long,
narrow room). Ducted units can be placed in room corners or ends as long as front access is main-
tained. Placing units too close together will reduce the effectiveness of the air distribution.
NOTE
Locate and remove shipping screw on fan motor base.
2.4

Equipment Handling

WARNING
!
Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or
death.
Read all of the following instructions before attempting to move, lift, remove packaging from
or preparing unit for installation.
The instructions below are to be adhered to when handling this unit with or without the skid.
There is the potential for this unit to tip over if it is handled improperly.
(A
PPLICABLE TO ALL
Installation (Applicable to all Models)
M
)
ODELS
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents