Figure 2 Low Volt Wiring Terminals - Liebert InteleCool 2 User Manual

Outdoor wall-mount air conditioner,1.5 - 5 tons, 50 & 60 hz
Hide thumbs Also See for InteleCool 2:

Advertisement

Figure 2
Low volt wiring terminals
Liebert Thermostat
See 2.5.2 - Control Connections for further information, refer to the detailed instructions that ship
with the thermostat.
NOTE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of is
useful life. If this control is replacing a control that contains mercury in a sealed tube, do not
place your old control in the trash. Contact your local waste management authority for
instructions regarding recycling and the proper disposal of this control, or of an old control
containing mercury in a sealed tube.
If you have questions, call the thermostat manufacturer, Honeywell, at 800-468-1502.
Dual Unit Control
®
The InteleCool
control contains an electronic timer for switching the operating sequence of two units on a one-, two-,
four-, or eight-day basis. It also contains a two-stage heat/two-stage cool thermostat with individual
heat and cool set points. Light emitting diodes (LEDs) indicate Lead Unit 1 or 2 and power from
Unit 1 or 2. The schedule for lead/lag switchover is adjustable by moving jumpers on the printed cir-
cuit board. A jumper is also used to change lead and lag unit before a scheduled changeover (if neces-
sary for servicing).
WARNING
!
The original Dual Unit Control (part # 153054G1, produced through March 2002), is phase
sensitive. The latest version Dual Unit Control (Part # 171170G1) is not. Please refer to
specific installation instructions supplied with each control. Failure to follow specific
instructions may damage the control and/or the unit and void the warranty.
NOTE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of
its useful life. If this control is replacing a control that contains mercury in a sealed tube, do
not place your old control in the trash. Contact your local waste management authority for
instructions regarding recycling and the proper disposal of this control, or of an old control
containing mercury in a sealed tube.
If you have questions, call the thermostat manufacturer, Honeywell, at 800-468-1502.
Tele2
Consult the Tele2 user manual for installation instructions.
Dual Unit Control is designed to control two InteleCools in a "lead/lag" fashion. The
7
Installation