portLoopBackTest
Augment the note on page 751 and in the corresponding man pag as followse:
This diagnostic cannot be run on an operational switch. You must disable the switch using the
chassisDisable command before you can run this test. After the test completes, re-enable the switch
using the chassisEnable command.
Do NOT use the switchDisable command followed by manually shutting down the ports before
running the test. This will not work, because executing switchEnable, after the test completes, will leave
the ports in the same state as before. The only way to bring the ports down before running the test and
back up after the test completes is by using the chassisDisable command followed by the
chassisEnable command
turboRamTest
:Augment the note section of the turboRamTest help pages as followse:
This diagnostic cannot be run on an operational switch. You must disable the switch using the
chassisDisable command before you can run this test. After the test completes, re-enable the switch
using the chassisEnable command.
portLedTest
:Augment the note section of the portLedtestTest help pages as followse:
This diagnostic cannot be run on an operational switch. You must disable the switch using the
chassisDisable command before you can run this test. After the test completes, re-enable the switch
using the chassisEnable command.
slotShow
In the Notes section, the following note to clarify the description of slot 5 in a DCX and in a DCX-4S.
In a DCX-4S, slot 5 is occupied by a control processor blade (Blade ID 50). On a DCX, slot 5 is occupied
by the core blade (Blade ID 52).
On page 927, the description for the -p operand should be clarified to avoid the impression that this
command displays real-time power consumption data. This is not the case. Real-time power
consumption data is displayed for 16G platforms only with the chassisShow command. The data
displayed in the "DC Power Consumption" column and in the summary field "Total DC Power
consumption" indicate the maximum allowed power consumption, not a real-time value.
-p
Fabric OS Documentation Updates
53-1002165-05
In addition to the basic slot status view, this command displays the following
information about power consumption:
The maximum allowed direct current (DC) power consumption for the chassis
and individual values for each blade (in Watts). Note that usage for other
components is included but not listed
portLoopBackTest
4
11