Installation Procedure
This chapter describes the installation requirements and installation procedure.
2-2-1 Installation requirements
Before installing the XG700, read " For Safe Use of the XG700 (P.2)" and comply with the
installation requirements described below.
Space requirements
When installing the XG700, a certain amount of installation space is necessary.
When installing the rack, the indicated space (800mm of both the front and rear of the rack)
should be reserved as a service area.
The following figures indicate examples of a 540mm (W) X 850mm (D) 19-inch rack and a
700mm (W) X 950mm (D) 19 inch rack.
When installing in any other 19-inch rack, refer to the user guide provided with the rack.
[540mm (W) 850mm (D) 19-inch rack]
(Unit: mm)
Front
Service area
(Front)
800
[700mm (W) 950mm (D) 19-inch rack]
(Unit: mm)
Front
Service area
(Front)
800
CAUTION
The XG700 may be installed in any rack with an internal depth of between 630mm
and 750mm.
Rack
Service area
(Top)
(Rear)
800
850
Rack
Service area
(Top)
(Rear)
800
950