Page 1
CONTROL KIT Model: CK-50 Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas Lochinvar appliances. TEMS INCLUDED IN 1 - Junction box with mounted pressure switch and relays 1 - Fan control gas pressure switch 1 - 2 ft.
Page 2
INSTALLATION AND ADJUSTMENTS OUNTING UNCTION The junction box can be mounted at the venter or remotely mounted away from the venter. (See Fig. 1 & Fig. 2) 1. Remove one of the knockouts from the side of the junction box where the pressure switch is mounted. Install the flexible conduit connector onto the CK-50 junction box Figure 1 and secure with fastening nut.
Page 3
WIRING INSTRUCTIONS CAUTION: DISCONNECT ELECTRICAL POWER WHEN WIRING POWER VENTER Wire the venter motor and controls in accordance with the National Electrical Code, manufacturer's recommendations and/or applicable local codes. UNITS MUST BE GROUNDED. Check ground circuit to make certain that the unit has been properly grounded. The wiring should be protected by an overcurrent circuit device rated at 15 amperes.
Page 4
Check system draft. b. Check for negative pressure in building. DO NOT DESTROY HESE NSTRUCTIONS EMAIN QUIPMENT Installation Information Model No.: ________________________________________ Installer’s Name: ___________________________________ Installer’s Company: ________________________________ Phone No.: _______________________________________ Date of Installation: _________________________________ Page 4 P/N 46382500 05/00...