Field Controls 46001000 Installation Instruction

Draft regulators (3"-10")

Advertisement

Quick Links

LISTED UNDER RE-EXAMINATION SERVICE OF UNDERWRITERS LABORATORIES INC. LISTED UNDER LABEL SERVICE OF CANADIAN STANDARDS ASSOCIATION.
The regulator contained in this package is manufactured with careful precision.
regulate chimney draft with a high degree of accuracy and fuel efficiency.
marked B-34 or DR. The basic draft adjustments are similar, but where variations apply, the
following paragraphs will explain the procedure.
Proper operation of the regulator depends upon proper installation and adjustment.
indicator, stack thermometer and draft gauge to adjust oil or solid fuel burners.
burners work best with the draft over fire of .01 to .02-inches W.C.
Solid fuel burners work best with over-fire draft of .04 to .08.
over the fire create smokey fires and pulsation.
Step 1
Weight assembly must be attached to
damper prior to its installation in flue
pipe, refer to appropriate illustration
below.
Step 2
LOCATION OF DRAFT CONTROL (See Figs.
3-8)
Locate the draft control as near to the
furnace or boiler as possible.
installation has a smoke pipe stack control,
locate the regulator at least 18" away from
the stack control.
Step 3
BALANCING WEIGHT ASSEMBLY AND DRAFT ADJUSTMENT
as shown in Fig. 1.
TYPE B-34 (See Fig. 1)
Assemble the "counter balance weight assembly" to the
draft control as shown in Fig. 1.Thread "counter balance
weight" through "threaded nut" attached to the vane.
Assemble"hex nut" and "knurled nut" on front of vane.
Turn "knurled nut" counter clockwise for less draft, clockwise for
When adjustment is made for desired draft, lock the "counter balance weight assembly" in place
by tightening the "hex nut"" located under the "knurled nut" against the vane.
INSTALLATION INSTRUCTION
THE FIELD CONTROLS COMPANY
DRAFT REGULATORS (3"-10")
TYPES B34, AND DR
READ CAREFULLY
NOT CSA CERTIFIED FOR SOLID FUELS.
If the
BEST LOCATIONS FOR
OIL OR SOLID FUELS
*Selected sizes CSA and UL
approved.Not
CSA certified for
solid fuels.
It is designed to
The control may be
Use a CO
Domestic oil
Excessively high draft settings
NOTE:
Damper must be mounted
with the hinge pins horizontal
and the face of the damper
plumb for correct operation.
This is done by rotating the
damper section within the
collar for any pipe position.
Tighten screws to hold firmly
in place.
more draft.
2

Advertisement

loading

Summary of Contents for Field Controls 46001000

  • Page 1 INSTALLATION INSTRUCTION THE FIELD CONTROLS COMPANY DRAFT REGULATORS (3"-10") TYPES B34, AND DR READ CAREFULLY LISTED UNDER RE-EXAMINATION SERVICE OF UNDERWRITERS LABORATORIES INC. LISTED UNDER LABEL SERVICE OF CANADIAN STANDARDS ASSOCIATION. NOT CSA CERTIFIED FOR SOLID FUELS. The regulator contained in this package is manufactured with careful precision.
  • Page 2 TYPE DR (See Fig. 2) Assemble the "carriage bolt" through the "weight support bracket" attached to vane. Thread tapered "counter balance weight" on "carriage bolt" (tapered portion of weight must point toward bottom of draft control). For less draft, slide "counter balance weight assembly" toward "Low"...
  • Page 3 .Figures 8 and 9 show method of checking Damper for "plumb" and hinge pins for "horizontal" after Damper is installed.This is important for proper draft control operation. THE FIELD CONTROLS COMPANY 2308 AIRPORT ROAD KINSTON, NORTH CAROLINA 28501-8947 (919) 522-3031 P/N 46001000 REV. A...