CARLO GAVAZZI MDI 40 TF - CONFIGURATION SOFTWARE Instruction Manual page 19

Multi-range mp-based panel meter and controller

Advertisement

Where:
d = diameter of the circumference
n = number of pulses per revolution
32
dSY : display parameter programming
menu
d.P
: decimal point position selection.
Lo
: minimum value of the display
scale, programmable value: -1999 < Lo
< 9999
Hi
: maximum value of the display
scale, programmable value: -1999 < Hi
< 9999
These values are referred only to the
output limits of the analogue output and
to the "OFF" alarm function.
For instance: if Lo=100.0 and hi=800.0
and the alarm type "TYP" is "OFF", the
display will blink and activate the rel-
evant output when the measured
variable goes out of the "100.0 to 800.0"
limits. If the analogue output is avail-
able, the output signals will start from
"100.0" and will arrive to "800.0".
• Cnd : auxiliary command selection
menu
r1 : display HOLD.
r2 : key-pad disabling.
t.in
: activation time of the auxiliary
input, programmable value: 20 < t.in <
255 msec.
• SP.1 / SP.2 : set-point programming
menu
tYP
: working type:
oFF : abnormal condition notifying. The
output will be activated either when
the measurement is out of the measur-
ing range or when it cannot be displayed
(blank display or "EEE" / "-"
cation on the display).
Note: if the above mentioned function
will be selected, the Lo.S, Hi.S, SP1,
HYS parameters will not be consid-
ered.
do : down alarm.
uP : up alarm.
d.do : down alarm with disabling at
power-on.
• •
• •
uP.L : up alarm with latch ( the alarm
i n d i -
33

Advertisement

loading