Page 4
Protection may be impaired if the instrument is used in a manner not specified by the manufacturer. Service and warranty In the event of malfunction, fault, requests for information or to purchase accessory modules, contact the CARLO GAVAZZI branch or distributor in your country.
96 single-phase loads or any combination of single and three-phase loads or two and single-phase loads for a maximum of 96 channels. The system can be set up, measurements viewed and up to 16 alarms managed from WM50 and UCS. Main unit functions can be expanded with a maximum of two of the following available modules: digital input/output module, analog input module and communication module.
M C ETH TCD12 12-channel current sensor. Measures main electrical variables on the single channels and loads and transmits them to WM50. A maximum of eight TCD12s can be connected in series on two TCD buses to each WM50 via TCD12WS cables.
UCS (Universal Configuration Software) UCS is available in desktop and mobile versions. It can connect to WM50 via accessory communication modules (Modbus TCP/IP or Modbus RTU protocol) or via OptoProg (via USB or Bluetooth). The following is possible with UCS: •...
WM50 calculates and displays both main line and single channel and load measurements. All measurements are displayed by UCS or via Modbus communications (Carlo Gavazzi VMU-C monitoring system or other data acquisition system). Main line measurements are also available on screen.
Essential information Measurement management Measurement error If a measurement is not available or out of range, it is displayed as "EEEE" on WM50 display and as "--" on UCS. See “Troubleshooting” on page 38. Average value calculation (dmd) The system calculates the average value of electrical variables in a set integration interval (15 min by default). The average value will not be available if the variable measurement is out of range.
Accessory modules Enabling accessory modules Accessory modules are automatically recognized by WM50. They only need to be manually set if configuring the system from UCS in offline mode. Note: by default, the M C 485 232 communication module is always enabled even if not actually connected.
Pulse transmission output on active or reactive, imported or exported energy consumption. • Energy type • Pulse weight Only from WM50, a pulse transmission test can be run, see “Running a pulse transmission • Enable of transmission test test” on page 34.
Essential information Disabling tariff management Set tariff management as disabled or enter 6 in the 143Fh register. From WM50: See “Settings menu” on page 19, sub-menu Tariff and Dig in x. Database Introduction Database can be exported to .xls file and databases and single variables, events and values to be saved can be enabled/disabled from UCS.
TCD12 TCD12 identification TCD12 configured and connected to WM50 is identified by the system via the combination of its three features: • serial number (on the top of the sensor) • physical position on the TCD bus (i.e.: A1 for TCD A bus TCD12 closest to WM50) •...
To learn more about settings pages, see “Settings from WM50” on page 31. Configuring WM50 via PC or smartphone Note: communication parameters may need to be set via touch keypad to communicate with WM50. 1. Meet all the requirements indicated in “Configuration requirements via UCS” before.
OptoProg skip to the next step 3. Start UCS and connect to WM50 via automatic scan or by manually setting correct communication parameters. 4. Open the settings section, set parameters and save changes.
4. Select the layout that represents the physical TCD12 positions. 5. Select TCD12s connected to port A (TCD A bus) and those connected to port B (TCD B bus) in the order they are connected to WM50 (i.e.: A1 for TCD A bus TCD12 closest to WM50).
• check/assign the correct phase to each channel. • optional. Create load groups. 8. Save changes. 9. If necessary, download the configuration on WM50 and check settings, see “TCD12 LED status” on page 9 and “Troubleshooting” on page 38. Moving a TCD12 If TCD12 position on the TCD bus changes, the system recognizes it: from UCS, view the warning on the involved TCD12.
Reset energy meters and totalizers Energy meters for the main line and totalizers can be reset from both WM50 and UCS. TCD12 energy meters can only be reset from UCS. From WM50: See “Settings from WM50” on page 31, sub-menu Meters.
2. Set network parameters via WM50 keypad or from USC mobile connected with OptoProg. 3. Connect WM50 to the master via Ethernet cable to the LAN or directly (point to point connection). 4. Create communications via mater (PC, VMU-C, PLC, etc.) connected to the same LAN or connected point to point.
Maintenance and disposal Troubleshooting Note: in the event of malfunction or fault, contact the CARLO GAVAZZI branch or distributor in your country. Measurement problems Problem Cause Possible solution 'EEEE' (on WM50) or "--" (on UCS) appears The current transformer settings are not correct...