Step 2 Password setting/change menu for ModBus. Real-time control will be available
when the ModBus password is the same to the UPS password.
Step 3 Com. port setting:
The default ID for nominated com. port is 0;
Selectable baud rates are 1200, 2400, 4800, 9600, and 19200. The default
setting is 4800;
Selectable data bit is 7 and 8. The default setting is 8;
Selectable stop bit is 1 and 2. The default setting is 1;
Supported parity is ODD parity, event parity and NONE. The default setting is
NONE.
NOTE: This function is only available for the UPS with ModBus communication port.
4.1.9. Certificates management
If using Exchange Server for mailbox system, it's required to configure ExChange
server domain name in this screen.