Generator ac connection system
A single-phase, three-wire AC connection system is used in
the home generator. The stator assembly consists of a pair
of stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as a wiring diagram. A
complete schematic and wiring diagram can be found later
in this manual.
Neutral is not bonded to ground at generator.
Grounding the Generator
Ground the generator per applicable codes, standards, and
regulations. The generator GND lug is located inside the
control panel door under the circuit breaker cover.
16
33
22
Circuit
Breaker
11
44
44
Circuit
0
Breaker
Ground
Line 2
To Transfer Switch
Neutral
120V
120V
240V
11
22
Line 1
Neutral