Generator Ac Connection System; Grounding The Generator - GE 20 kW Home Installation And Start-Up Manual

Home generator systems
Table of Contents

Advertisement

Generator ac connection system

A single-phase, three-wire AC connection system is used in
33
Neutral
the home generator. The stator assembly consists of a pair
22
of stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as a wiring diagram. A
complete schematic and wiring diagram can be found later
in this manual.
120V
NOTICE Neutral is not bonded to ground at generator.
NOTICE Generator must be used with only an UL approved
transfer switch that is compatible with the generator.
120V
Circuit
Breaker
11
240V
44
From Alternator Power Windings
0
22
44
11
Circuit
Breaker
Ground
Neutral
Line 2
Line 1
To Transfer Switch

Grounding the Generator

The home generator must be installed as part of a system
that includes a listed transfer switch, with neutral to
ground bonding at the transfer switch in accordance
with installation instructions. Unless mandated by local
code, additional grounding to earth at the generator is
not required. Any grounding at generator must use metal
piercing lock washers (or equal), UL listed terminals installed
per terminal supplier's instructions, and comply with national
electrical codes and local requirements.