Summary of Contents for AccuEnergy Acuvim II Series
Page 1
Acuvim II Series Power Meter User's Manual 1.800.561.8187 information@itm.com www. .com...
Page 2
Please read this manual carefully before installation, operation and maintenance of the Acuvim II Series Power Meter. The following symbols in this manual are used to provide warning of danger or risk during the installation and operation of the equipment.
Table of Contents Chapter 1: Introduction ..................7 1.1 Meter Overview......................7 1.2 Areas of Application ..................... 8 1.3 Functionality ........................9 Chapter 2: Installation ..................14 2.1 Appearance and Dimensions ..................16 2.2 Installation Methods ....................18 2.3 Wiring ...........................22 2.3.1 Power Requirement ..................22 2.3.2 Voltage Input Wiring ..................23 2.3.3 Current Input Wiring ..................27 2.3.4 Typical Wiring ....................29...
Page 4
3.7.3 System Settings ....................54 3.7.4 I/O Module Settings ..................57 3.7.5 Communications Module Settings ..............59 3.7.6 Alarm Settings ....................63 3.8 Page Recovery Function .....................64 Chapter 4: Detailed Functions and Software ...........65 4.1 Acuview Software .......................65 4.1.1 Connect using RS485 ..................65 4.2 Basic Analog Measurements ..................68 4.2.1 High Speed Monitoring ...................69 4.3 Demand ........................70 4.4 Energy ..........................71...
Page 5
4.11.5 Weekend Settings ..................97 4.11.6 Holiday Settings .....................98 4.11.7 DST Settings ....................101 4.11.8 Reading the TOU data .................101 4.12 Power Quality Event Logging and Waveform Capture........104 4.12.1 Waveform Capture ..................105 4.12.2 Power Quality Event Logging ..............107 4.12.3 Waveform Retrieval ..................107 4.13 Dual Source Energy ....................110 4.13.1 Controlling the Energy Direction ...............111 4.13.2 Bi-Directional Energy Switching Record ...........112...
Page 6
5.2.9 Baud Rate .......................155 5.2.10 GSD Files .......................155 5.2.11 Information Exchange ................155 5.2.12 Format of Function code 01H ..............156 5.2.13 Format of function code 05H ..............157 5.2.14 Format of function code 02H ..............158 5.2.15 Format of function code 03H ..............159 5.2.16 Format of function code 10H ..............161 5.2.17 32 Word Output Interface ................162 5.3 RS485 Module (AXM-485) ..................163...
Page 7
6.3.16 SunSpec Registers ..................239 Chapter 6: Communication Part II ..............244 6.3.17 Over/Under Alarm Setting ................244 6.3.18 Data Logging ....................253 6.3.19 Time-of-Use ....................260 Appendix ......................289 Appendix A Technical Data and Specifications ..........289 Appendix B Ordering Information ................294 V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www.
Ideal for Electric Automation SCADA Systems The Acuvim II series meter is the ideal choice for replacing traditional analog meters. In addition to providing clear real-time readings on the meter display, it can also be used as a remote terminal unit (RTU) for monitoring and controlling a SCADA system.
Acuvim II Series Power Meter Data Logging The Acuvim IIR meter and Acuvim IIW meter contain 8MB (megabytes) of on-board memory for data logging and historical trending respectively. Since the meters contain real-time clocks, all events and logged data will include a timestamp of when data is recorded.
This meter can be installed into a standard ANSI C39.1 (4" round) or an IEC 92mm DIN (square) cutout. With the 51mm depth after mounting, the Acuvim II series meter can be installed in a small cabinet. Mounting clips are used for easy installation and removal.
Page 11
Acuvim II Series Power Meter Function Comparison of Acuvim II Series Meter Acuvim Acuvim Category Items Parameters • • Phase Voltage V1, V2, V3, Vlnavg • • Line Voltage V12, V23, V31, Vllavg • • Current I1, I2, I3, In, Iavg •...
Page 12
Chapter 1: Introduction Acuvim Acuvim Category Items Parameters Voltage • • Unbalance U_unbl Factor Current • • Unbalance I_unbl Factor • • Voltage THD THD_V1, THD_V2, THD_V3, THD_Vavg Power Quality • • Current THD THD_I1, THD_I2, THD_I3, THD_Iavg Harmonics 2nd to 63rd Individual •...
Page 13
Acuvim II Series Power Meter Acuvim Acuvim Category Items Parameters F, V1/2/3/lnavg, V12/23/13/lavg, I1/2/3/n/ avg, P1/2/3/sum, Q1/2/3/sum, S1/2/3/sum, PF1/2/3, PF, U_unbl, I_unbl, Load Type, Ep_imp, Ep_exp, Ep_total, Ep_net, Eq_imp, Eq_exp, Eq_total, Eq_net, Es, THD_V1/2/3/ Data Logging 1 avg, THD_I1/2/3/avg, Harmonics 2nd to 63rd,...
CTs. CT grounding is optional. • Accuenergy recommends using a dry cloth to wipe the meter. NOTE: IF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.
Page 15
Chapter 2: Installation DISCONNECT DEVICE: The following part is considered the equipment disconnect device: A SWITCH OR CIRCUIT-BREAKER SHALL BE INCLUDED IN THE INSTALLATION. THE SWITCH SHALL BE IN CLOSE PROXIMITY TO THE EQUIPMENT AND WITHIN EASY REACH OF THE OPERATOR.
There are two different types of Acuvim II meter design, either panel mount with an LCD display or DIN rail mount with no display. The following figures provide the front view, side view, and rear view of the two different Acuvim II series meters. Figure 2-1 Front view of the Meter Display and...
Page 17
Figure 2-6 Rear View of Acuvim II Meter Figure 2-7 Rear View of Remote Display Figure 2-8 Installation Clip Unit: mm (inches) The table below specifies the part name and description of the Acuvim II series meter. Table 2-1 Meter Part Name and Description Part Name Description 1) LCD Display Large bright white backlight LCD display.
The Acuvim II series meter should be installed in a dry and dust-free environment. Avoid exposing meter to excessive heat, radiation, or high electrical noise source. Installation Steps The Acuvim II series meter can be installed into a standard ANSI C39.1 (4-inch round) or an IEC 92mm DIN (square) form. Panel Mount Installation 1.
Page 19
Chapter 2: Installation 2. Remove the clips from the meter and insert the meter into the square hole from the front side. NOTE: Optional rubber gasket must be installed on the meter before inserting the meter into the cutout. Figure 2-10 - Insert meter into the opening 3.
Page 20
The DIN rail mount option meter is simply installed on a 35mm DIN rail. AXM-DIN Installation The AXM-DIN rail adapter provides an easy installation method for panel-mount Acuvim II series meters on DIN rail. Available for all models and I/O options.
Page 21
Chapter 2: Installation Figure 2-13 – Install the AXM-DIN rail adapter 2. The AXM-DIN rail adapter can be adjusted for horizontal or vertical DIN rail installations. Figure 2-14 - Horizontal DIN rail installation Figure 2-15 - Vertical DIN rail installation V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com...
Acuvim II Series Power Meter 2.3 Wiring There are four terminal strips at the back of the Acuvim II series meter, they are the voltage input terminal, current input terminal, power supply terminal and the communication port terminal. The three-phase voltage and current are represented by using 1, 2, and 3 respectively. These numbers have the same meaning as A, B, and C used in other literature.
Chapter 2: Installation terminal of the switch gear. An isolated transformer or EMC filter should be used in the power supply loop if there is a power quality issue with the power supply. Figure 2-17 - Power Supply Figure 2-18 - Power Supply with EMC Filter 2.3.2 Voltage Input Wiring Voltage Input Terminal The voltage input terminal strip consists of 4 input terminals: V1 (7), V2 (8), V3 (9), and VN (10).
Page 24
Acuvim II Series Power Meter The maximum voltage input for the Acuvim II series meter shall not exceed 400LN/690LL Vac RMS for three-phase or 400LN Vac RMS for single-phase. In high voltage systems a Potential Transformer (PT) must be used. The typical secondary output for PTs shall be over 100V or 120V.
Page 25
Chapter 2: Installation 3-Phase 3-Wire Delta Mode (3LL) 3-Phase 3-Wire Delta mode is commonly used in low voltage electric distribution systems. For voltages lower than 400LN/690LL, the voltage lines can be connected directly to the meters voltage input terminal as shown in Figure 2-20c. For high voltage systems (over 400LN/690LL), PTs (Potential Transformers) are required as shown in Figure 2-20d.
Page 26
Figure 2-20f - 1LN Direct Connection Vn Connection Vn is the reference point of the Acuvim II series meter voltage input. Low wire resistance helps improve the measurement accuracy. Different system wiring modes require Vn connection methods. Please refer to the wire diagram section for more details.
Chapter 2: Installation 2.3.3 Current Input Wiring Current Input Terminal Current Transformers (CTs) are required for most engineering applications. Typical current rating for the secondary side of the CT shall be 5A (standard) or 1A (optional); please refer to the ordering information appendix for further details.
Page 28
Acuvim II Series Power Meter The 3CT current wiring configuration can be used when either 3CTs are connected (as shown in Figure 2-22) or when 2 CTs are connected (as shown in Figure 2-23). In either case, there is current flowing through all three circuit terminals.
Chapter 2: Installation 1 CT Figure 2-25a - 1CT wiring for Figure 2-25b - 1CT wiring for Figure 2-25c - 1CT wiring for 5A/1A CTs in 1LN single phase 333mV/mA CTs in 1LN single Rogowski Coil (RCT) in 1LN systems phase systems single phase systems 2.3.4 Typical Wiring...
Acuvim II Series Power Meter 2.3.5 Frequently Used Wiring Methods In this section, the most common voltage and current wiring combinations are shown in different diagrams. In order to display measurement readings correctly, please select the appropriate wiring diagram for your setup and application.
Page 31
Chapter 2: Installation 3. 3LL-3CT Figure 2-28a 3LL-3CT Figure 2-28b 3LL-3CT Figure 2-28c 3LL-3CT configuration using 5A/1A CTs configuration using 333mV/mA configuration using Rogowski Coils 4. 2LL-3CT Figure 2-29a 2LL-3CT wiring Figure 2-29b 2LL-3CT wiring Figure 2-29c 2LL-3CT wiring with with PTs using 5A/1A CTs with PTs using 333mV/mA CTs PTs using Rogowski Coils...
333mV/mA configuration using Rogowski Coils 2.3.6 Communication The Acuvim II series meter uses RS485 serial communication and the Modbus RTU protocol. The terminals of communication are A, B, and S (14,15,16). • A is the positive differential signal •...
Page 33
Figure 2-33 RS485-USB connection to Acuvim II series meter The Acuvim II series meter is used as the slave device of masters such as a PC, PLC, Data Collector or RTU. If the master does not have a RS485 communication port, a converter (such as a RS232/ RS485 or a USB/RS485 converter) will be required.
3.1 Display Panel and Keys The front of the Acuvim II series meter consists of an LCD screen and four control keys. All the display segments are illustrated in Figure 3-1. Users should note that all the segments will not display in a single page under normal conditions.
Page 35
Chapter 3: Meter Display & Parameter Settings Display Description Item Icons: U for voltage I for current P for active power Q for reactive power S for apparent power Three " " digits PF for power factor F for frequency for phase angles DMD for demand Mxx for expanded I/O module type and display setting page...
Acuvim II Series Power Meter Display Description No Icon: no pulse output Energy pulse output indicator With Icon: icon blinks when sending pulse output M1: one AXM-IO1 connected M1x2: two AXM-IO1 connected None: no AXM-IO1 connected M2: one AXM-IO2 connected...
Page 37
Chapter 3: Meter Display & Parameter Settings Figure 3-2 - Voltage and Current screen sequence NOTE: When the meter is set to 2LL or 3LL, there is no phase voltage or neutral current displayed. Therefore, only the third screen (line voltage & avg) and the fourth screen (three-phase current & avg) will be displayed.
Page 38
Acuvim II Series Power Meter Figure 3-3 shows an image of the three-phase voltage reading, where 1 represents phase A, 2 represents phase B, 3 represents phase C, and avg represents the average phase voltage. Similarly in Figure 3-4, the three-phase current and average can be seen in the same representation.
Chapter 3: Meter Display & Parameter Settings 3.2.2 Power, Power Factor, and Frequency To view all power related data, press P while in metering mode. The screen will roll to the next page when P is pressed again. It will go back to the first screen if you press P at the last screen.
Acuvim II Series Power Meter Figure 3-7 - Three-Phase Power Page Figure 3-8 - Total System Power Page 3.2.3 Phase Angles and Unbalance To view the phase angle and unbalance data, press H while in metering mode. The screen will roll to the next page when H is pressed again. It will go back to the first screen if you press H on the last screen.
E is pressed again. It will go back to the first screen if you press E at the last screen. The Acuvim II series meter can be set to record either primary or secondary energy. The unit of energy is kWh for active energy, kvarh for reactive energy, and kVAh for apparent energy. The running time has a resolution of 0.01h.
Page 42
Acuvim II Series Power Meter Figure 3-12 - Energy and Real Time Clock screen sequence There are different types of energy that the Acuvim II meter can measure, Figure 3-13 shows the Import Active Energy represented by the IMP icon and the kWh unit.
Chapter 3: Meter Display & Parameter Settings Table 3-2 Energy Parameter Table Parameter Unit Import Energy Export Energy Net Energy Total Total Energy Import Reactive Energy kvarh Export Reactive Energy kvarh Net Reactive Energy kvarh Total Total Reactive Energy kvarh Apparent Energy kVAh The meter’s time can also be found in the energy screen sequence.
Page 44
Acuvim II Series Power Meter Chapter 3: Meter Display & Parameter Settings Figure 3-15 - TOU screen sequence V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Chapter 3: Meter Display & Parameter Settings 3.3 Statistical Data In the statistical data mode, the meter displays the maximum and minimum values for voltage, current, power, power factor, unbalance, demand, THD, etc. To change the mode of the Acuvim II meter to view statistical data, press H and V/A simultaneously for about one second then release;...
Acuvim II Series Power Meter NOTE: The timestamp for the max/min parameters can be viewed only from the Acuview software or through Modbus communication. There are no commands associated with the H button in the Max/ Min display mode. Figure 3-17 Acuvim II Minimum Readings Figure 3-18 Acuvim II Maximum Readings 3.4 Demand Data...
Chapter 3: Meter Display & Parameter Settings Figure 3-19 Power Demand Screen 3.5 Harmonic Data In the Harmonic data mode, the meter displays the individual harmonic data for voltage and current, Total Harmonic Distortion, odd Harmonic Distortion, even Harmonic Distortion, Crest Factor, and K Factor.
Acuvim II Series Power Meter NOTE: When the meter is set to 1LN, only phase A is displayed for voltage THD, voltage odd harmonic distortion, voltage even harmonic distortion, THFF, voltage crest, current THD, current odd harmonic distortion, current even harmonic distortion, and current K factor. When the meter is set to 1LL phase C is not displayed.
Page 49
Chapter 3: Meter Display & Parameter Settings Figure 3-22 - Individual Harmonic data screen sequence NOTE: The figure shows the rolling sequence when pressing P. If the E button is pressed, the sequence will be reversed. When the meter is set to 1LN, only phase A is displayed for voltage and current harmonic magnitudes.
Acuvim II Series Power Meter 3.6 Expanded I/O Module Data To view the data from the expanded I/O modules, press H and V/A simultaneously for about one second then release; the screen will go blank, and the cursor will begin flashing. Press either P or E to move the cursor right or left until it is on Digital I/O, then press V/A to view the I/O data.
Page 51
Chapter 3: Meter Display & Parameter Settings Table 3-3 I/O Module Representation Code Module AXM-IO1-1 AXM-IO1-2 AXM-IO2-1 AXM-IO2-2 AXM-IO3-1 AXM-IO3-2 I/O Module Data Display In the I/O Module Data selection screen, press P to move the cursor downwards; the cursor will move to the top when it reaches the bottom.
Page 52
Acuvim II Series Power Meter Figure 3-26 - AXM-IO2 data display screen sequence Figure 3-27 - AXM-IO3 data display sequence V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Chapter 3: Meter Display & Parameter Settings 3.7 Meter Setting Mode In the settings mode, the system parameters, expanded I/O module parameters, alarm parameters, and communications module parameters can be read and modified. To access the settings mode, press H and V/A simultaneously for about one second then release; the screen will go blank, and the cursor will begin flashing.
Acuvim II Series Power Meter • I/O • NET (Depending on the type of communications module and protocol selected, this may say MESH or BACNET) • Alarm To navigate in the parameter selection mode, press P to move the cursor downwards; the cursor will move to the top when it reaches the bottom.
Page 55
Chapter 3: Meter Display & Parameter Settings Figure 3-30 - System Parameters page sequence V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Page 56
Acuvim II Series Power Meter V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Chapter 3: Meter Display & Parameter Settings 3.7.4 I/O Module Settings In the expanded I/O module parameter mode, users can choose to view the available modules that are attached to the meter and modify their parameters. If no expanded I/O modules are connected, the screen will display NO IO.
Page 58
Acuvim II Series Power Meter Figure 3-32 - Screen sequence for AXM-IO21/IO22 Figure 3-33 - Screen sequence for AXM-IO31/IO32 V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Chapter 3: Meter Display & Parameter Settings 3.7.5 Communications Module Settings When the second communication protocol is set to BACnet, there are certain pages that will be displayed related to BACnet. These pages will only be shown when the module is successfully connected to the meter;...
Page 60
Acuvim II Series Power Meter The following figures show the screen sequence for the supported communication protocols: Figure 3-34 - Ethernet module net settings screen sequence NOTE: This figure shows the rolling screen sequence using the P key. If using the E key for rolling to the next page the sequence will be reversed.
Page 61
Chapter 3: Meter Display & Parameter Settings Figure 3-35 - BACnet IP module rolling screen sequence V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Page 62
Acuvim II Series Power Meter Figure 3-36 - BACnet MS/TP settings Figure 3-37 - Mesh settings V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Chapter 3: Meter Display & Parameter Settings 3.7.6 Alarm Settings In the alarm parameter mode, the user can view and modify the parameters. Key functions for finding the alarm parameter: • Press H to return to parameter selection mode. • The screen will roll to the next page each time P is pressed and will return to the first page when P is pressed on the last page.
Acuvim II Series Power Meter 3.8 Page Recovery Function The Acuvim II series meter includes a page recovery function. This means that the meter stores the current display page in the non-volatile memory upon power loss and reloads the page when power is recovered.
Chapter 4: Detailed Functions and Software Chapter 4: Detailed Functions and Software The Acuvim II series meter contains advanced metering tools and is able to measure a multitude of power, energy and power quality parameters. Some advanced functions may not be accessible directly from the meter front;...
Page 66
Acuvim II Series Power Meter Once the physical wiring is connected between the converter cable and the Acuvim II meter, the meter’s communication settings need to be confirmed. The communication settings in this case are the meter’s Modbus device address (slave ID), the communication speed or baud rate, and the parity.
Page 67
Chapter 4: Detailed Functions and Software Open the Acuview software. The following New Connection screen will appear where users are required to provide the type of connection, COM port, baud rate, parity, and scan interval. Select the connection type as Serial Port and then select the COM port number assigned to the USB converter cable from the device manager.
Acuvim II Series Power Meter Figure 4-5 - Acuview Software interface once successfully connected to the meter NOTE: For methods on how to connect to the software using Modbus TCP via a communications module, please refer to the AXM-WEB2 or AXM-WEB-PUSH User Manual 4.2 Basic Analog Measurements...
Chapter 4: Detailed Functions and Software 4.2.1 High Speed Monitoring The Acuvim II V3 model supports High Speed Monitoring which includes either 100ms or 20ms sampling rates. The high speed parameters include most real time parameters for 100ms, however at 20ms sampling the meter only supports voltage, current, total active/reactive power and frequency.
Acuvim II Series Power Meter 4.3 Demand This meter can support demand measurements consisting of power and current demand readings. The demand can be found in the real-time section as outlined in Figure 4-7 below. The demand will be calculated using the demand calculation method configured in the meter. The calculation types include: •...
Chapter 4: Detailed Functions and Software 4.4 Energy The Acuvim II meter supports the writing of energy values which can be done via software or Modbus but not from the meter’s display. This is used to configure the meter to start accumulating from a certain energy value.
Acuvim II Series Power Meter 4.5 Max/Min Acuvim II series meter logs maximum and minimum value statistics for all real time, demand, THD parameters and also log the time that it occurred. All data is stored in non-volatile memory so that statistic information can be preserved even when the meter is loses power or gets shut off.
4.6 Harmonics and Power Quality Analysis 4.6.1 Harmonics & THD Acuvim II series meter can measure and analyze several power quality parameters which is useful for further analyzing the voltage and current signals measured by the meter. Total Harmonic Distortion: A ratio of the sum of powers in all harmonic components to power of the fundamental frequency.
Acuvim II Series Power Meter Figure 4-11 - Individual Harmonic Reading 4.6.2 Amplitude and Angle This section provides users with the amplitude and phase angle details of the harmonics being measured by the meter. For example if the voltage input to the meter is 120V, and a harmonic reading of 10% for the 2nd order, the amplitude in this case will show 12V.
Chapter 4: Detailed Functions and Software 4.6.3 Phase Angles Phase angle indicates the angle between phase A voltage and other voltage/current parameters in a range from 0 to 360 degrees. These readings allows the users to analyze the phase angle difference between each phase and also determine if current/voltage are incorrectly out of phase, which tend to be related to wiring/installation issues with the meter.
Acuvim II Series Power Meter 4.6.4 Sequence Component and Unbalance Analysis Acuvim II series meter is able to perform sequential analysis for the input signal. The sequence components allow users to represent three-phase systems as individual into three single phase networks, where these networks can be described as the positive sequence, negative sequence and zero sequence.
Page 77
Chapter 4: Detailed Functions and Software Zero Sequence: Combines a set of three phasors that are equal in magnitude and in-phase with each other. Unlike the positive and negative sequence, there is no rotation associated with the zero sequence. Figure 4-15 - Zero Sequence Phasor Diagram Unbalance Factor The unbalance factor allows users to understand the percentage in which the voltage and current are unbalanced.
Acuvim II Series Power Meter 4.7 Alarm Acuvim II series meter supports an over/under limit alarming function. When the monitored parameter goes over or under the preset limit and stays at the level over the preset time delay, the alarm will be triggered. The alarm can be configured directly from the meter display, the Acuview software, or via Modbus communication.
Page 79
Chapter 4: Detailed Functions and Software Comparison Mode: Users can select three, different alarm conditions: 1. Greater than (>) 2. Equal to (=) 3. Smaller than (<) For example: If you choose the target parameter to be "Frequency," the condition to be "greater than"...
Page 80
Acuvim II Series Power Meter RO Code RO Channel IO Module AXM-IO1-2 AXM-IO1-2 AXM-IO3-1 AXM-IO3-1 AXM-IO3-2 AXM-IO3-2 NOTE: If RO is under alarming mode, it can only work in the “latch” mode. Table 4-3 - Alarming Parameter Code Table Alarming...
Power (AXM-IO3-1) 4.7.1 Alarm Log The Acuvim II series meter has built-in alarm logging capabilities where 16 entries in total can be recorded. The record sequence of these entries do not depend on the sequence of the 16 alarm channels.
Page 82
Acuvim II Series Power Meter Figure 4-18 - Alarming Records No.: There are 16 alarm entries in the alarm log and this number indicates the alarm number. For example, the newest alarm record number in Figure 4-18 is record entry 7.
Chapter 4: Detailed Functions and Software 4.8 Meter Settings The meter settings can be configured from the meter display (refer to chapter 3 for screen sequencing), through the Modbus registers (refer to chapter 6) and from the Acuview software. The meter settings need to be configured correctly in order for the Acuvim II meter to read data. After configuring any of the meter settings users will need to click on Update Device at the bottom of the settings page in order for the setting to take effect.
Acuvim II Series Power Meter 4.8.1 Communication • Communication Channel 1 - Refers to the meters RS485 communication port; the settings here are relative to Modbus RTU or DNP over serial communication. • Protocol - Can be set as Modbus or DNP, Modbus is default •...
Page 85
Chapter 4: Detailed Functions and Software • PT1 - If using Potential Transformers with the meter at the voltage input, this setting refers to the Primary side rating of the transformer. The range is from 50.0-1000000.0. If PTs are not being used with the meter, this setting can be left as the default which is 400.0.
Acuvim II Series Power Meter 4.8.3 Demand Settings • Demand Calculation Method - There are four types of demand that the Acuvim II meter supports: Fixed, Sliding Window, Thermal, and Rolling Window. See section 4.3 for a description for each calculation method.
Chapter 4: Detailed Functions and Software reactive currents. Active current is calculated as: And reactive current as: Active and reactive powers are as follows, where Ia and Ir represents RMS values of instantaneous active and reactive currents: 4.8.5 Load Percentage The rated load can be represented in terms of either current or power.
Acuvim II Series Power Meter Rogowski Coil (RCT), 333mV, or mA type Current Inputs, then 1A is used in this equation. For example, if the max primary power of your system is 576000W (or 576kW), your system is currently using 211kW and the meters current input type is 5A, then the load percentage would be calculated as follows: The load percentage can only be viewed on the front LCD display of the Acuvim II meter;...
Chapter 4: Detailed Functions and Software Figure 4-21 - Device Clock Configuration 4.10 Data Logging The Acuvim IIR/IIW models support data logging onto the meter internal memory, where these models include 8MB of memory. The base model Acuvim II does not have the internal memory and does not support data logging capabilities.
Page 90
Acuvim II Series Power Meter • DI Counter - If using an external I/O module, the user can log the DI counter value • Analog Output/Input Raw & Scaled values - Users have the option to log the AO/AI values—both the raw values as well as the scaled values. More information on scaling for AO/AI can be found in Chapter 5.
Page 91
Chapter 4: Detailed Functions and Software need to specify the start time by selecting the hour and minute. Once the data starts to log, it does not stop and, like the immediate logging mode, the data will start to overwrite the oldest data log entry once the memory is full.
Acuvim II Series Power Meter 4.10.2 Retrieving the Data Log The data logs can be retrieved directly from the Acuview software or by Modbus (refer to Chapter 6). In the Acuview software, under the readings tab, select Data Log. The top of the screen will...
Chapter 4: Detailed Functions and Software Figure 4-23 - Data Log Retrieval Page 4.11 Time-of-Use (TOU) Most utilities bill customers according to their Time-of-Use rates where customers are billed at certain rates depending on when the energy usage occurs. The Acuvim II meter supports a Time- of-Use functions that allows users to assign up to 4 different tariffs to different time periods within the day according to their billing requirements.
Page 94
Acuvim II Series Power Meter • Tariff Setting - The Acuvim II supports up to 4 tariffs in the TOU function. The range is 0-3 for this setting where 0 means 1 tariff and 3 means all 4 tariffs are used.
Chapter 4: Detailed Functions and Software Error Code (Hex) Error Code (Decimal) Meaning of Error Code Tariff of Schedule Setting Error Time of Schedule Setting Error 1024 Time sequence on schedule setting Error 2048 Weekend Schedule Number Setting Error 1000 4096 Weekend Setting Error Figure 4-24 - TOU General Settings...
Acuvim II Series Power Meter the date parameters are March 31 and November 4, and TOU schedule 01, 02 will be used respectively, the first TOU season table slot shall enter 03-31 01, and the second slot shall enter 11-04 02. With this configuration the first season would be form March 31st to November 4th, and the second season would be from November 4th to March 31st.
Chapter 4: Detailed Functions and Software Figure 4-27 - TOU Schedule Configuration 4.11.5 Weekend Settings Weekends (Alternative): In the case where a TOU schedule supports multiple schedules for a weekday or weekend within a season, the Weekends (Alternative) can be enabled to allow that day to run a specific schedule.
Acuvim II Series Power Meter NOTE: The days to fill in with the schedule number must correspond to the decimal representation set in the box to the left of this field. Figure 4-28 - Weekends Alternative Setting 4.11.6 Holiday Settings The Acuvim II supports holiday configuration within its TOU function, where a maximum of 30 holidays can be programmed to the TOU calendar.
Page 99
Chapter 4: Detailed Functions and Software codes are defined as follows: 0- Holiday only occurs once 1- Holiday occurs on the same date each year 2- Holiday occurs on the first Sunday on or after the date entered 3- Holiday occurs on the first Monday on or after the date entered 4- Holiday occurs on the first Thursday on or after the date entered 5- Holiday moved from Sunday to Monday 6- Holiday moved from Saturday to Friday or Sunday to Monday...
Page 100
Acuvim II Series Power Meter Figure 4-31 - TOU Holiday Code Definition V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Chapter 4: Detailed Functions and Software 4.11.7 DST Settings The Acuvim II series meter can adjust for the Daylight Savings Time and this function can be enabled from the Acuview software. DST can be configured to follow one of two formats: 1.
Page 102
Acuvim II Series Power Meter The Current Month TOU is divided into two sections: Accumulated and Incremental. Current Month TOU (Accumulated): Refers to the TOU energy accumulated in the current month. Current Month TOU (Incremental): Refers to the TOU energy accumulated in this month minus the TOU energy accumulated in the prior month.
Page 103
Chapter 4: Detailed Functions and Software The TOU function displays the prior month TOU readings from the Acuview software. This allows users to compare the current month and previous month’s readings for billing and analytical purposes. These readings can be viewed in the software by clicking on the Prior Month TOU option under the Readings tab.
Acuvim II Series Power Meter When setup appropriately and when TOU is enabled, energy will be accumulated on a month- to-month basis. The current energy usage will be stored under Current Month TOU (or Current Accumulation Month TOU) and is divided up into different tariffs. When the next month (or counting period) starts, all Current Month TOU values will be moved to the Prior Month TOU (or Prior Accumulation Month TOU).
100 groupings in the meters dedicated internal memory. The Acuvim IIW is the only model of the Acuvim II series that has 16MB of internal memory; 8MB is dedicated for the data logging function and another 8MB is dedicated for capturing power quality events.
Page 106
Acuvim II Series Power Meter • Threshold - Enter in the percentage of the voltage sag to be captured. The range is from 20- 100%. For example, if the rated voltage is 277V, and the voltage sag threshold is set for 50%, the sag event would be captured when the voltage drops 50% below 277V, which is roughly 138V.
Chapter 4: Detailed Functions and Software 4.12.2 Power Quality Event Logging When a power quality event happens, such as voltage sag and swell, Acuvim IIW will record the event timestamp and the triggering condition. It can save up to 50,000 events. The events can be viewed from Acuview software in the Events Log located under the Readings tab.
Page 108
Acuvim II Series Power Meter Figure 4-35 - Waveform Log Users have the option to also manually capture a waveform on the Acuvim II meter, on the Acuview software click on Capture Waveform. This may take 1-2 minutes to capture the waveform, and the waveform will show up in the Waveform Log with Reason description as Manual (refer to record number 8 in Figure 4-35 above).
Page 109
Chapter 4: Detailed Functions and Software Figure 4-36 - Manual Capture Waveform Reading the Voltage and Current waveform When the waveforms are displayed on the Acuview software, the voltage and current are displayed as peak-to-peak values. In order to view the RMS values, users must convert the peak-to-peak values into RMS.
Figure 4-37 - Waveform Capture Retrieval Screen 4.13 Dual Source Energy The Acuvim II series meters have bi-directional energy capability that allows users to control the direction (Grid/Generator) of the energy accumulation. The user can control the direction either by the Digital Input and through communication. There are two directions in which the energy can be changed to, "Grid"...
Chapter 4: Detailed Functions and Software The bi-directional energy function can be enabled in the General Settings on the Acuview software. Users can select the enabled option and configure the settings accordingly. Switching Mode: Select the method in which the user wants to change the direction of the energy.
Acuvim II Series Power Meter 4.13.2 Bi-Directional Energy Switching Record Whenever there is a change in direction for the energy, the Acuvim II meter will keep the historical changes in the Switching Record. The record supports 20 event records, and will overwrite from the earliest entry once the records reach the max amount.
Page 113
Chapter 4: Detailed Functions and Software When the meter is in sealed status, the parameters listed in the tables below will be blocked. Table 4-9 System Parameters Settings blocked in Sealed Status Meter Display Modbus Parameters Keys Communication Voltage Input Wiring Mode √...
Acuvim II Series Power Meter Meter Display Modbus Parameters Keys Communication Reactive energy NET √ Apparent energy √ Phase A Energy IMP √ Phase A Energy EXP √ Phase B Energy IMP √ Phase B Energy EXP √ Phase C Energy IMP √...
Page 115
Chapter 4: Detailed Functions and Software Figure 4-40 - Sealed Nonstandard Parameter Configuration There are five categories that can be optionally sealed: • Device Run Time • DI Counters • Device Clock & TOU • Communication Channel 1 • Communication Channel 2 The following tables explain what functions are blocked if any of these are selected to be sealed.
Page 116
Acuvim II Series Power Meter Meter Display Modbus Parameters Keys Communication DI pulse constant √ √ DI7-10 type √ √ DI pulse constant √ √ DI11-14 type √ √ DI pulse constant √ √ DI15-20 type √ √ DI pulse constant √...
Page 117
Chapter 4: Detailed Functions and Software Table 4-16 Communication Channel 2 Sealed Parameters Meter Display Modbus Parameters Keys Communication Baud rate 2 √ √ Parity setting 2 √ √ Communication address 2 √ √ Ethernet Module DHCP setting √ √ IP address 1st byte (high) √...
Page 118
Acuvim II Series Power Meter Meter Display Modbus Parameters Keys Communication Gateway 1st byte (high) √ √ Gateway 2nd byte (low) √ √ Gateway 3rd byte (high) √ √ Gateway 4th byte (low) √ √ DNS1 1st byte (high) √...
The Acuvim II series supports three types of I/O modules: the AXM-IO1, AXM-IO2 and AXM-IO3. There is a maximum of three external modules that can be attached to the Acuvim II meter, and this includes communication modules.
Acuvim II Series Power Meter Table 5-1 I/O Module Description Table Number Description Enclosure Wiring Terminals Linking Pins Linking Socket Installation Screw Counterpart of Clip Installation Clip 5.1.2 I/O Functionality The AXM-IO1 module is composed of: Figure 5-2 AXM-IO1 Module •...
Page 121
Chapter 5: Extended Modules for RO1 and RO2 circuits. • 24Vdc Power Supply • Used as an auxiliary power supply for the digital input pulse circuits. • The voltage of the DI auxiliary power supply is 24V(1W). • Terminals V+ and V- are the terminals for the 24Vdc power supply. The AXM-IO2 module is composed of: Figure 5-3 AXM-IO2 Module •...
Page 122
Acuvim II Series Power Meter measured by the Acuvim II meter. In alarm mode, the DO will output a digital pulse when an alarm is triggered. • Terminals DO1 to DOC are the Digital Output terminals, where DOC is the common terminals for DO1 and DO2.
Chapter 5: Extended Modules NOTE: The AXM-IO3 can only read input from one type of analog signal. Table 5-2 I/O Module Functionality Table Functions AXM-IO1 AXM-IO2 AXM-IO3 • • • Detection of remote signals • • • SOE Recording • •...
Page 124
Acuvim II Series Power Meter Figure 5-5 External Port Cover NOTE: Use a small, flat, thin screwdriver to remove the external port cover from the back of the meter. 1. Insert the counterpart clips of the module into the Acuvim II meter and then press the module down lightly to establish the linking.
Chapter 5: Extended Modules 5.1.4 I/O Module Wiring Digital Input Wiring of Digital Input Circuit: There are six DI channels in the AXM-IO1 and four DI channels in the AXM-IO2 and AXM-IO3 modules. The Digital Input circuits within each of the modules are the same for both pulse counter and digital status modes.
Acuvim II Series Power Meter Figure 5-9 Multiple channel Digital Input wiring using 24Vdc on AXM-IO1 module Figure 5-10 Digital Input Wiring Using AXM-IO2 and AXM-IO3 Modules NOTE: The wire gauge to use with the DI should be between AWG22~16.
Chapter 5: Extended Modules Relay Output ratings: • Switching Voltage (Max): 250Vac, 30Vdc • Load Current: 5A (R), 2A (L) • Set Time: 10ms (Max) • Contact Resistance: 30mΩ (Max) • Isolation Voltage: 2500Vac • Mechanical Life: 1.5e7 Typical Relay Output Wiring Figure 5-11 Relay Output Diagram NOTE: The wire gauge to use with the relay output should be between AWG22~16.
Page 128
Acuvim II Series Power Meter Wiring of Digital Output Circuit When the internal signal J is in the low state, OUT is also in a low state and, therefore, there is no pulse output. When J is in a high state, OUT is in the high state which will then output a pulse.
Page 129
Chapter 5: Extended Modules Figure 5-14 Digital Output to a pulse counter NOTE: The power supply can be 0-250Vac/dc. NOTE: The wire gauge to use for the DO should be between AWG22-16. Analog Output There are two Analog Output channels on the AXM-IO2 module. The AO circuit can convert metering parameters into an AO signal as either a voltage or current signal.
Page 130
Acuvim II Series Power Meter Analog Output Ratings: • For the current output (0-20mA/4-20mA): The max load resistance is 500Ohms. • For the voltage output (0-5V/1-5V): The max load current is 20mA. • Accuracy: 0.5% • Temperature Drift: 50ppm/°C Typical •...
Chapter 5: Extended Modules 5.1.5 IO Module Readings 5.1.6 Detection of Remote Signals By default, the Digital Input on all I/O modules are configured in State mode, where the meter provides a digital signal status (ON/OFF). When the DI circuit detects a sufficient voltage input, it will show a 1 on the screen and ON from the Acuview software.
Page 132
Acuvim II Series Power Meter The DI settings must be set to State to monitor the Digital Status. If any changes are made to the I/O settings, click on Update Device at the bottom of the Settings page in order to save the configurations.
Page 133
Chapter 5: Extended Modules Sequence of Events Record (SOE) When the Digital Input is configured to detect remote signals, users have the option to monitor the digital status change using the sequence of events log on the Acuvim II meter. Users can select which I/O module to log from the General page under the Settings tab on the software.
Acuvim II Series Power Meter When the Acuvim II series meter is powered, the SOE will begin to record immediately. The data in the SOE Log is saved when the meter is powered down. When a new I/O module is selected to be recorded from, the records will be overwritten immediately.
Page 135
Chapter 5: Extended Modules Figure 5-22 Digital Input Pulse Count from meters display NOTE: The counter value is read from top to bottom on the meter display. For example, if the count value is 123456789, it will be displayed on the meter as 1 on the top line, 2345 on the second line, and 6789 on the bottom line.
Page 136
Acuvim II Series Power Meter Fig 5-24 Pulse Counter Readings from the Acuview software Scaling Pulse Count Values The pulse count can be scaled from the Acuview software. This allows users to scale or multiply the raw pulse count values and can be useful when converting pulse counts from a water or gas meter.
Chapter 5: Extended Modules Figure 5-26 Pulse Category/Unit configuration To view the scaled pulse input readings, go to Real-Time under Energy in the Readings tab. The multiplied pulse count values will be displayed in the Pulse Input table. Figure 5-27 Scaled Pulse Input Readings NOTE: These scaled readings will only be displayed on the Acuview software.
Acuvim II Series Power Meter 5.1.8 Relay Output The relay output is supported on the AXM-IO1 and AXM-IO3 modules. Users can read the relay output status from either the meter’s display, Acuview software, or through Modbus registers. Reading Relay Output from Meter Display: •...
Page 139
Chapter 5: Extended Modules • Latch: When the control mode is set for Latch, the relay will only be switched ON/OFF manually by the user. • Momentary: When the control mode is set for Momentary, the relay will only switch ON for certain time period which can be configured by user.
Acuvim II Series Power Meter Figure 5-32 Relay Output Readings from Acuview Software 5.1.9 Digital Output The AXM-IO2 module supports the Digital Output and has two digital output channels that can be configured for either Alarm mode or Energy Pulse mode. The DO can be configured from the meter’s display (refer to Chapter 3), from the Acuview software, or from the Modbus registers (refer...
Page 141
Chapter 5: Extended Modules Whenever the meter sends a pulse signal, a pulse icon can be seen on the meter’s display. This icon will flash whenever a pulse signal is sent out from the digital output. Figure 5-33 shows where and how the pulse signal indicator is displayed.
Page 142
Acuvim II Series Power Meter • This means 1 pulse = (1/22000) kWh; therefore 22000 pulses = 1 kWh • Since we get 22000 pulse/kWh, 22000 is the pulse constant. Once the pulse constant value has been calculated, users can configure the pulse constant setting from the setting menu in the meter display (refer to Chapter 3), via Modbus registers (refer to Chapter 6), or Acuview software.
Page 143
Chapter 5: Extended Modules NOTE: If this is a 333mV current input meter, consider CT2 as 1A. If this is a Rope CT meter, consider CT2 as 1A. • Enter the value of the Primary Maximum Power by performing the following calculation: 3*(PT1*CT1)/1000 •...
Acuvim II Series Power Meter 5.1.10 Analog Output The analog output is supported in the AXM-IO2 module where users can convert measured electrical parameters into an analog voltage (0-5V/1-5V) or current (4-20mA/0-20mA). Viewing the Digital status from the Meters Display: •...
Page 145
Chapter 5: Extended Modules How to view and configure the Analog Output from the Acuview software: The Analog Output settings can be configured from the Acuview software on the I/O Modules *1 or I/ O Modules *2 page under the Settings tab depending on the logic number of the I/O module being used.
Page 146
Acuvim II Series Power Meter Setting Parameter Value Phase C Power Factor Total Power Factor Figure 5-39 Analog Output settings In the AO Input/Output Transfer Curve section, users can configure the scaling of the Analog Output signal relative to the parameter selected.
Page 147
Chapter 5: Extended Modules Figure 5-40 Relationship between analog output and electrical parameters Certain parameters have a range that can be configured for the AO. • Frequency: 45Hz-65Hz • Phase Voltage: V1, V2, V3, and Vavg: 0-480V • Line Voltage: V12, V23, V31, and Vavg: 0-831V •...
Acuvim II Series Power Meter Figure 5-41 Analog Output readings on the Acuview software 5.1.11 Analog Input The analog input is supported in the AXM-IO3 module where users can read either 0-20mA/4-20mA or 0-5V/1-5V. Analog input can measure into an analog voltage (0-5V) or current (4-20mA).
Page 149
Chapter 5: Extended Modules The analog input value can be viewed on the meter’s display as a hex number. The AI value ranges from 0-4095. The figure below shows the relationship between the AI value and the input analog value. Similar to the analog output, the analog input can be converted.
Page 150
Acuvim II Series Power Meter Figure 5-45 Analog Input Type Setting Reading the analog input value from the Acuview software: Similar to the display, the analog input value is read as a hex number and needs to be converted to the correct mA or V signal. In the figure below, AI1 reads 9 which converts to 0.01V or 0.044mA and AI2 reads 3420 which converts to 4.17V or 16.7mA.
Chapter 5: Extended Modules 5.2 Profibus Module AXM-PROFI 5.2.1 Introduction of PROFIBUS Technology Profibus (Process Field Bus) is an international field bus standard that is widely used in the automation technology of manufactures and the flow industry. It is a widely used, open digital communication system which is suitable for high speed, time-critical and high-reliability communications.
Figure 5-48 AXM-PROFI Installation to Acuvim II meter The AXM-PROFI module is linked to the Acuvim II series meter by a communication plug. Other extended modules, such as the I/O modules, can be linked to the Acuvim II series meter through the AXM-PROFI.
Chapter 5: Extended Modules 1. Insert the installation clips to the counterpart of the Acuvim II meter and then press the AXM-PROFI module lightly to establish the linking. 2. Tighten the installation screws. NOTE: Do not install any modules when power is applied to the meter. 5.2.5 Definition of DP Interface The AXM-PROFI module uses a standard 9-pin, D-type connector to access the PROFIBUS network.
Acuvim II Series Power Meter Figure 5-49 DP station Connection Diagram The bus terminal is composed of three resistors and a connection wire, where Vp is the supply positive voltage and DGND is the Digital Ground. When the bus is idle, the bus terminal makes the data P level higher than data N so the bus's idle signal is always 1.
The basic communication method of the Acuvim II series meter is RS-485, which uses the Modbus-RTU protocol. In order to use the same addresses as Modbus, the communication format of PROFIBUS-DP is 16-bit word input/output.
Acuvim II Series Power Meter 5.2.12 Format of Function code 01H Function code 01H is used to the read relay status. The format of this function code is defined as follows: Query: Table 5-5 Function Code 01H Query Format Frame Bytes...
Chapter 5: Extended Modules Example: reading Relay1 and Relay2 status (start register address is 0000H). Use 4 channels. Query: Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7~32 Response: Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7~32 Coil Status: (Relay 1 = OFF, Relay 2=ON) 5.2.13 Format of function code 05H The message with function code (05H) in MODBUS-RTU forces a single relay to either the on or off position.
Acuvim II Series Power Meter Table 5-8 Function Code 05H Response Format Frame Bytes Caption Byte 1 Byte 2 Byte 3 outputs address high byte Byte 4 outputs address low byte Byte 5 outputs value high byte Byte 6 outputs value low byte Byte 7~32 Example: setting Relay2 on.
Chapter 5: Extended Modules Frame Bytes Caption Byte 4 inputs status1 Byte 5 inputs status2 (or 0) Byte 6 inputs status3 (or 0) Byte 7 inputs status4 (or 0) Byte 8~32 The digital inputs in the response message are packed as one input per bit of the data field. Status is indicated as 1=ON;...
Page 160
Acuvim II Series Power Meter Frame Bytes Caption Byte 4 starting address low byte Byte 5 quantity of registers high byte Byte 6 quantity of registers low byte Byte 7~32 “Quantity of registers” identifies how many words will be read.
Chapter 5: Extended Modules (F=42480000H(50.00Hz), V1=42C7CCCDH(99.9v), V2=42C83333H(100.1v)). NOTE: The relationship between the numerical value in the register of the meter and the actual physical value is described in Chapter 6. 5.2.16 Format of function code 10H This function code is used in MODBUS-RTU to write a block of continuous registers in the Acuvim II meter, such as system parameters setting and so on.
Acuvim II Series Power Meter Response: The normal Response returns the function code, starting address, and quantity of registers written. Table 5-14 Function Code 10H Response Format Frame Bytes Caption Byte 1 Byte 2 Byte 3 starting address high byte...
AXM-RS485 module uses RS485 serial communication and the Modbus-RTU protocol, just like the on-board RS485 port of the Acuvim II series meter. It provides a second RS485 port for serial communication and it can work with the on-board RS485 serial communication simultaneously.
Acuvim II Series Power Meter 5.3.3 Appearance and Dimensions Figure 5-51 AXM-RS485 Dimensions 5.3.4 Installation Method Figure 5-52 AXM-RS485 installation to Acuvim II meter The RS485 module is linked to the meter by a communication plug. It also can be linked to other extended modules.
The default baud rate of the RS485 module is 38400 bps. Users can change the baud rate in system settings S03 of the Acuvim II series meter. Figure 5-53 Baud Rate setting for the AXM-RS485 module The data format is start bit + 8n data bit + parity + stop bit.
Acuvim II Series Power Meter Figure 5-54 Parity setting for the AXM-RS485 module NOTE: If AXM-WEB/AXM-WEB2 is used, the RS-485 module’s parity (PAR2) must be set as None1 so that the meter will recognize the communications module. 5.3.6 Communication Address The communication address used for the AXM-RS485 module is located on page S36.
Modbus would also be helpful. 6.1 Modbus Protocol Introduction Modbus RTU is the communication protocol used in Acuvim II series meters. Data format and error check methods are defined in the Modbus protocol. The half duplex query and respond mode is adopted in the Modbus protocol. There is only one master device in the communication network.
Acuvim II Series Power Meter Function Field The function code field of a message frame contains eight bits. Valid codes are in the range of 1~255 decimal. When a message is sent from a master to a slave device the function code field tells the slave what kind of action to perform.
CRC 16 HI CRC 16 LO register HI register LO registers HI registers LO Response: The Acuvim II series meter response includes the meter address, function code, quantity of data V: 3.0 Revised: November 2022 1.800.561.8187 information@itm.com www. .com...
Page 170
2. Read Status of DI Function Code 02 1=ON, 0=OFF DI’s address is 0000H, D12’s address is 0001H, and so on. The following query is to read the status of 4 DI’s of Acuvim II series meter with communication address 17. Query:...
Page 171
3. Read Data (Function Code 03) Query: This function allows the master to obtain the measurement results from the Acuvim II series meter. Table 6-8 is an example of reading the measured data (F, V1 and V2) from slave device number 17, the data address of F is 4000H, 4001H;...
Page 172
0000H will turn it off; all other values are invalid and will not affect that relay. The example below is a request to the Acuvim II Series meter with the address of 17 to turn on Relay1.
Chapter 6: Communication Part I Table 6-13 Preset Multi-Register Response Message Number of Number of Data start Data start data start Address Function data start CRC 16 HI CRC 16 LO register HI register LO registers registers HI 6.3 Data Address Table and Application Details There are several rules to follow in using the meter: 6.3.1 Data Type •...
Page 174
Acuvim II Series Power Meter Table 6-14 Relationship of Parameters Format Parameters Relationship Unit Code Numerical value equals to communication System parameters No unit value Run-time T=Rx/100 Hour Numerical value equals to communication Clock Unit of time value Energy (primary)
Chapter 6: Communication Part I Modification of the contents in both of two or more regions above cannot be accomplished in a single communication. 2. When function code 03H is used, the rules and limitations described above will not be applied. 6.3.3 System Parameter Setting System parameters determine how the meter works.
Page 176
Acuvim II Series Power Meter System Status 03H Read, 10H Write Access Address(H) Address(D) Parameter Range Default Data Type Property 1007H 4103 50.0~400.0 Word CT1 = 5 , for 5A CT1 = 1 , for 333mV 1008H 4104 1~50000 Word...
Page 177
Chapter 6: Communication Part I System Status 03H Read, 10H Write Access Address(H) Address(D) Parameter Range Default Data Type Property 0: Real Reactive Power 1018H 4120 Word Measurement Mode 1: General 0: Primary 1019H 4121 Energy Display Mode Word 1: Secondary 0: None 101AH 4122...
Acuvim II Series Power Meter 6.3.4 System Status Parameters The “System status” indicates the events that have occurred in the meter, what kinds of flags are read by the user, and the index of the storage events. Flags should be cleared after being read by the controller;...
Page 179
Chapter 6: Communication Part I System Status 03H Read, 10H Write Access Address(H) Address(D) Parameter Range Default Data Type Property Bit0: AXM-IO11 Bit1: AXM-IO12 Bit2: AXM-IO21 Bit3: AXM-IO22 Expansion IO Modules 1036H 4150 Word Status Bit4: AXM-IO31 Bit5: AXM-IO32 0: Disconnected 1: Connected 1037H 4151...
Acuvim II Series Power Meter Chapter 6: Communication Part I 6.3.5 Date and Time Registers Function code: 03H for reading, 10H for presetting. Table 6-17 Clock Settings: 03H Read, 10H Write Access Address(H) Address(D) Parameter Range Data Type Property 103FH...
Page 181
Chapter 6: Communication Part I Basic Measurements: 03H Read Parameter Mode Data Access Address(H) Address(D) Symbol Parameter Property Primary Type Property Secondary Mode Mode 3012H- 12306- Total Phase A I=Rx I=Rx*(CT1/CT2) Float 3013H 12307 Current 3014H- 12308- Total Phase B I=Rx I=Rx*(CT1/CT2) Float...
(Rx is the numerical value in the register of the Acuvim II Series meter). NOTE: The parameter mode Primary or Secondary corresponds to the Basic Parameter Mode (at address 101DH) in the system parameter settings.
Page 183
Chapter 6: Communication Part I Energy Measurements: 03H Read, 10H Write Data Access Parameter Mode Address(H) Address(D) Symbol Parameter Property Type Property Primary Mode Secondary Mode 400AH- 16394- Line Voltage 1-2 U=Rx U=Rx*(PT1/PT2) Float 400BH 16395 400CH- 16396- Line Voltage 2-3 U=Rx U=Rx*(PT1/PT2) Float...
Page 184
Acuvim II Series Power Meter Energy Measurements: 03H Read, 10H Write Data Access Parameter Mode Address(H) Address(D) Symbol Parameter Property Type Property Primary Mode Secondary Mode Phase A S=[Rx*(PT1/ 402CH- 16428- Apparent S=Rx/1000 PT2)*(CT1/ Float 402DH 16429 Power CT2)]/1000 Phase B...
Chapter 6: Communication Part I 6.3.8 Energy Parameters NOTE: The Energy Display option of either Primary Mode or Secondary Mode corresponds to the Energy Display Mode (at address 1019H) in the system parameter settings. You can also configure the energy display mode from the 'S24 E SEL' in the system settings through the meters display.
Page 186
Acuvim II Series Power Meter Energy Measurements: 03H Read, 10H Write Parameter Mode Data Access Address(H) Address(D) Symbol Parameter Property Primary Type Property Secondary Mode Mode Phase C 4628H- 17960- Epc_ Epc_ Epc_Imp Consumed 0~999999999 4629H 17961 Imp=Rx/10 Imp=Rx/1000 Energy...
Chapter 6: Communication Part I 6.3.9 TOU (Time-of-Use) Registers Current Month Accumulation TOU Energy Table 6-21 Current month accumulation TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Range Property Data Type Property Sharp 29184- Consumed 7200H-7201H Ep_Imp 0-999999999 Dword 29185...
Page 188
Acuvim II Series Power Meter Current month accumulation TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Range Property Data Type Property 29216- Generated 7220H-7221H Ep_Exp 0-999999999 Dword 29217 Energy 29218- Consumed 7222H-7223H Eq_Imp 0-999999999 kvarh Dword 29219...
Page 189
Chapter 6: Communication Part I Prior Month Accumulation TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Range Property Data Type Property 29246- Generated 723EH-723FH Ep_Exp 0-999999999 Dword 29247 Energy 29248- Consumed 7240H-7241H Eq_Imp 0-999999999 kvarh Dword 29249 Reactive Energy 29250- Generated...
Page 190
Acuvim II Series Power Meter Current Month Incremental TOU Energy Table 6-23 Current Month Incremental TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Range Property Data Type Property Sharp 29440- Consumed 7300H-7301H Ep_Imp 0-999999999 Dword 29441 Energy...
Page 191
Chapter 6: Communication Part I Current Month Incremental TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Range Property Data Type Property 29472- Generated 7320H-7321H Ep_Exp 0-999999999 Dword 29473 Energy 29474- Consumed 7322H-7323H Eq_Imp 0-999999999 kvarh Dword 29475 Reactive Energy 29476- Generated...
Page 192
Acuvim II Series Power Meter Prior Month Incremental TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Range Property Data Type Property 29502- Generated 733EH-733FH Ep_Exp 0-999999999 Dword 29503 Energy 29504- Consumed 7340H-7341H Eq_Imp 0-999999999 kvarh Dword 29505...
Page 193
Chapter 6: Communication Part I Current Month Maximum Demand TOU Table 6-25 Current Month Maximum Demand TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property Sharp 7500H 29952 Ep_Imp Max Demand Rx/10 32768~32767 YY/MM;...
Page 194
Acuvim II Series Power Meter Current Month Maximum Demand TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property YY/MM; 29981- 751DH-751FH Timestamp DD/HH; 29983 Min/Sec Peak 7520H 29984 Ep_Imp Max Demand Rx/10 32768~32767 YY/MM;...
Page 195
Chapter 6: Communication Part I Current Month Maximum Demand TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property YY/MM; 30013- 753DH-753FH Timestamp DD/HH; 30015 Min/Sec Valley 7540H 30016 Ep_Imp Max Demand Rx/10 32768~32767 YY/MM;...
Page 196
Acuvim II Series Power Meter Current Month Maximum Demand TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property YY/MM; 30045- 755DH-755FH Timestamp DD/HH; 30047 Min/Sec Normal 7560H 30048 Ep_Imp Max Demand Rx/10 32768~32767 YY/MM;...
Page 197
Chapter 6: Communication Part I Current Month Maximum Demand TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property YY/MM; 30077- 757DH-757FH Timestamp DD/HH; 30079 Min/Sec Total 7580H 30080 Ep_Imp Max Demand Rx/10 32768~32767 YY/MM;...
Page 198
Acuvim II Series Power Meter Current Month Maximum Demand TOU Energy: 03H Read, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property YY/MM; 30109- 759DH-759FH Timestamp DD/HH; 30111 Min/Sec Prior Month Maximum Demand Table 6-26 Previous Month Maximum Demand TOU Energy: 03H, 10H Write...
Page 199
Chapter 6: Communication Part I Previous Month Maximum Demand TOU Energy: 03H, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property Rx*(CT1/ 7618H 30232 Max Demand 32768~32767 CT2)/1000 YY/MM; 30233- 7619H-761BH Timestamp DD/HH; 30235 Min/Sec Rx*(CT1/ 761CH 30236 Max Demand 32768~32767...
Page 200
Acuvim II Series Power Meter Previous Month Maximum Demand TOU Energy: 03H, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property Rx*(CT1/ 7638H 30264 Max Demand 32768~32767 CT2)/1000 YY/MM; 30265- 7639H-763BH Timestamp DD/HH; 30267 Min/Sec Rx*(CT1/ 763CH...
Page 201
Chapter 6: Communication Part I Previous Month Maximum Demand TOU Energy: 03H, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property Rx*(CT1/ 7658H 30296 Max Demand 32768~32767 CT2)/1000 YY/MM; 30297- 7659H-765BH Timestamp DD/HH; 30299 Min/Sec Rx*(CT1/ 765CH 30300 Max Demand 32768~32767...
Page 202
Acuvim II Series Power Meter Previous Month Maximum Demand TOU Energy: 03H, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property Rx*(CT1/ 7678H 30328 Max Demand 32768~32767 CT2)/1000 YY/MM; 30329- 7679H-767BH Timestamp DD/HH; 30331 Min/Sec Rx*(CT1/ 767CH...
Chapter 6: Communication Part I Previous Month Maximum Demand TOU Energy: 03H, 10H Write Access Address(H) Address(D) Symbol Parameter Relationship Range Data Type Property Rx*(CT1/ 7698H 30360 Max Demand 32768~32767 CT2)/1000 YY/MM; 30361- 7699H-769BH Timestamp DD/HH; 30363 Min/Sec Rx*(CT1/ 769CH 30364 Max Demand 32768~32767...
Page 204
Acuvim II Series Power Meter Voltage V1 (V12) Harmonics Table 6-28 Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V1(V12) 2nd 4062H 16482 THD=Rx/100 ≥0 Word Harmonic V1(V12) 3rd...
Page 205
Chapter 6: Communication Part I Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V1(V12) 22nd 4076H 16502 THD=Rx/100 ≥0 Word Harmonic V1(V12) 23rd 4077H 16503 THD=Rx/100 ≥0 Word Harmonic V1(V12) 24th 4078H...
Page 206
Acuvim II Series Power Meter Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V1(V12) 44th 450CH 17676 THD=Rx/100 ≥0 Word Harmonic V1(V12) 45th 450DH 17677 THD=Rx/100 ≥0 Word...
Page 207
Chapter 6: Communication Part I Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 4082H 16514 Crest Factor V1(V12) CF=Rx/100 0~65535 Word 4083H 16515 THFF_V1(V12) THFF=Rx/100 ≥0 Word Voltage V2(V31) Harmonics Table 6-29 Voltage Harmonics, Even &...
Page 208
Acuvim II Series Power Meter Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V2(V31) 18th 4094H 16532 THD=Rx/100 ≥0 Word Harmonic V2(V31) 19th 4095H 16533 THD=Rx/100 ≥0 Word...
Page 209
Chapter 6: Communication Part I Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V2(V31) 40th 4528H 17704 THD=Rx/100 ≥0 Word Harmonic V2(V31) 41st 4529H 17705 THD=Rx/100 ≥0 Word Harmonic V2(V31) 42nd 452AH...
Page 210
Acuvim II Series Power Meter Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V2(V31) 62nd 453EH 17726 THD=Rx/100 ≥0 Word Harmonic V2(V31) 63rd 453FH 17727 THD=Rx/100 ≥0 Word...
Page 211
Chapter 6: Communication Part I Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V3(V23) 15th 40B3H 16563 THD=Rx/100 ≥0 Word Harmonic V3(V23) 16th 40B4H 16564 THD=Rx/100 ≥0 Word Harmonic V3(V23) 17th 40B5H 16565...
Page 212
Acuvim II Series Power Meter Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V3(V23) 37th 4545H 17733 THD=Rx/100 ≥0 Word Harmonic V3(V23) 38th 4546H 17734 THD=Rx/100 ≥0 Word Harmonic...
Chapter 6: Communication Part I Voltage Harmonics, Even & Odd Harmonics, Crest Factor: 03H Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property V3(V23) 59th 455BH 17755 THD=Rx/100 ≥0 Word Harmonic V3(V23) 60th 455CH 17756 THD=Rx/100 ≥0 Word Harmonic V3(V23) 61st 455DH 17757...
Page 214
Acuvim II Series Power Meter Current Harmonics, Even & Odd Harmonics, K Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 40D5H 16597 I1 15th Harmonic THD=Rx/100 ≥0 Word 40D6H 16598 I1 16th Harmonic THD=Rx/100 ≥0...
Chapter 6: Communication Part I Current Harmonics, Even & Odd Harmonics, K Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 456DH 17773 I1 45th Harmonic THD=Rx/100 ≥0 Word 456EH 17774 I1 46th Harmonic THD=Rx/100 ≥0 Word 456FH 17775...
Page 216
Acuvim II Series Power Meter Current Harmonics, Even & Odd Harmonics, K Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 40EBH 16619 I2 4th Harmonic THD=Rx/100 ≥0 Word 40ECH 16620 I2 5th Harmonic THD=Rx/100 ≥0...
Page 217
Chapter 6: Communication Part I Current Harmonics, Even & Odd Harmonics, K Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 4582H 17794 I2 34th Harmonic THD=Rx/100 ≥0 Word 4583H 17795 I2 35th Harmonic THD=Rx/100 ≥0 Word 4584H 17796...
Acuvim II Series Power Meter Current Harmonics, Even & Odd Harmonics, K Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 4107H 16647 Odd THD_I2 THD=Rx/100 ≥0 Word 4108H 16648 Even THD_I2 THD=Rx/100 ≥0 Word 4109H...
Page 219
Chapter 6: Communication Part I Current Harmonics, Even & Odd Harmonics, K Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 411FH 16671 I3 23rd Harmonic THD=Rx/100 ≥0 Word 4120H 16672 I3 24th Harmonic THD=Rx/100 ≥0 Word 4121H 16673...
Acuvim II Series Power Meter Current Harmonics, Even & Odd Harmonics, K Factor: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 45B5H 17845 I3 53rd Harmonic THD=Rx/100 ≥0 Word 45B6H 17846 I3 54th Harmonic THD=Rx/100 ≥0...
Page 221
Chapter 6: Communication Part I MAX: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 4145H- 16709- Timestamp YYYY:MM:DD:hh:mm:ss 414AH 16714 32768~ 414BH 16715 Max of V12 (Rx*(PT1/PT2))/10 32767 414CH- 16716- Timestamp YYYY:MM:DD:hh:mm:ss 4151H 16721 32768~ 4152H 16722 Max of V23 (Rx*(PT1/PT2))/10...
Page 222
Acuvim II Series Power Meter MAX: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property Max of 32768~ 4191H 16785 Rx/1000 Frequency 32767 4192H- 16786- Timestamp YYYY:MM:DD:hh:mm:ss 4197H 16791 Max of Power (Rx*(CT1/CT2)*(PT1/ 32768~ 4198H 16792 Demand...
Page 223
Chapter 6: Communication Part I MAX: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property Max of THD_ 32768~ 41C2H 16834 Rx/100 V2(V31) 32767 41C3H- 16835- Timestamp YYYY:MM:DD:hh:mm:ss 41C8H 16840 Max of THD_ 32768 41C9H 16841 Rx/100 V3(V23) ~32767 41CAH-...
Page 224
Acuvim II Series Power Meter MIN: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 32768~ 4201H 16897 Min of V23 (Rx*(PT1/PT2))/10 32767 4202H- 16898- Timestamp YYYY:MM:DD:hh:mm:ss 4207H 16903 32768~ 4208H 16904 Min of V31 (Rx*(PT1/PT2))/10 32767...
Page 225
Chapter 6: Communication Part I MIN: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property 4248H- 16968- Timestamp YYYY:MM:DD:hh:mm:ss 424DH 16973 Max of Reactive (Rx*(CT1/CT2)*(PT1/ 32768~ 424EH 16974 kvar Power Demand PT2))/1000 32767 424FH- 16975- Timestamp YYYY:MM:DD:hh:mm:ss 4254H 16980 Max of...
Acuvim II Series Power Meter 6.3.12 Phase Angles All voltage and current phase angles corresponding to V1 (V120) are stored here. You can find out the phase sequence according to them. Data type is "Word". Table 6-36 Phase Angles: 03H Read...
Chapter 6: Communication Part I Sequence Component: 03H Read Data Access Address(H) Address(D) Parameter Relationship Property Range Type Property Negative Sequence 429DH 17053 THD=Rx/100 -32768~32768 Word complex part of I1 Zero Sequence real 429EH 17054 THD=Rx/100 -32768~32768 Word part of I1 Zero Sequence 29FH 17055...
Page 228
Acuvim II Series Power Meter AXM-IO2-1 Settings, 10H Write Data Address Parameters Default Range Property Type Working mode of 10A5H 0: Pulse output, 1: Alarming output Word relay 3 and 4 Output mode of 10A6H 20~1000ms Word relay 3 and 4...
Page 229
Chapter 6: Communication Part I AXM-IO12 Table 6-41 AXM-IO1-2 Settings: 03H Read, 10H Write Data Address Parameters Default Range Property Type 10B0H DI15~20 type Bit0: DI15, Bit1: DI16 Word DI pulse constant 10B1H 1~65535 Word (high) Working mode of 10B2H 0: Control output, 1: Alarming output Word relay 5 and 6...
Page 230
Acuvim II Series Power Meter AXM-IO32 Table 6-43 AXM-IO3-2 Settings: 03H Read, 10H Write Data Address Parameters Default Range Property Type Bit0: DI25, Bit1: DI26, Bit2: DI27, Bit3: DI28 10BCH DI25~28 type Word 0: DI, 1: Pulse constant 10BDH DI pulse constant...
Page 231
Chapter 6: Communication Part I AO Parameter Selection Setting Transforming Setting Setting Transforming Transforming Object Value Object Value Value Object Power of phase B Power of phase C Power of all Reactive power of Reactive power of Reactive power of phase B phase C Reactive power of Apparent power of...
Page 232
Acuvim II Series Power Meter NOTE: 1. AO Gradient Number Selection of input/output transfer curve When the number is 1, only the AO following value range setting start point, AO following value range setting end point, AO1 output range setting start point, and AO1 output range setting endpoint should be set.
Chapter 6: Communication Part I AO output range setting: The AO output value range setting start point, AO1 output value range setting point 2, AO1 output value range setting point 3, and AO output value range setting end point are increasing value, while they should be within range of the AO output value.
Page 234
Acuvim II Series Power Meter DI Counter: 03H Read Access Address(H) Address(D) Symbol Parameter Range Data Type Property 17235- DI6 Pulse Counter 4353H-4354H DI_116 0~4294967295 Dword 17236 Number AXM-IO2-1 17237- DI7 Pulse Counter 4355H-4356H DI_211 0~4294967295 Dword 17238 Number 17239-...
Page 235
Chapter 6: Communication Part I DI Counter: 03H Read Access Address(H) Address(D) Symbol Parameter Range Data Type Property AXM-IO3-2 17265- DI21 Pulse Counter 4371H-4372H DI_221 0~4294967295 Dword 17266 Number 17267- DI22 Pulse Counter 4373H-4374H DI_222 0~4294967295 Dword 17268 Number 17269- DI23 Pulse Counter 4375H-4376H DI_223...
Page 236
Acuvim II Series Power Meter DI Status: 02H Read Access Address(H) Address(D) Symbol Parameter Range Data Type Property AXM-IO3-1 0: OFF 000AH DI_311 DI11 Status 1: ON 0: OFF 000BH DI_312 DI12 Status 1: ON 0: OFF 000CH DI_313 DI13 Status...
Page 237
Chapter 6: Communication Part I DI Status: 02H Read Access Address(H) Address(D) Symbol Parameter Range Data Type Property 0: OFF 001AH DI_323 DI27 Status 1: ON 0: OFF 001BH DI_324 DI28 Status 1: ON Analog Input The output of AI is mapped to the range of 0~4095 according to its sampling value using an algorithm.
Page 238
Acuvim II Series Power Meter Relay Output Table 6-51 DI Status: 02H Read Access Address(H) Address(D) Symbol Parameters Range Data Type Property AXM-101-1 0:OFF 0000H RO_111 1:ON 0:OFF 0001H RO_112 1:ON AXM-IO3-1 0: OFF 0002H RO_311 1: ON 0: OFF...
Page 240
Acuvim II Series Power Meter SunSpec: 03H Read, 10H Write Number Data Access Address(H) Address(D) Parameters Range Default Type Property Registers Meter Configuration: Single Phase (AN or AB): Split Single C395H 50069 Uint16 Phase (ABN): WYE-Three Phase (ABCN): Delta Three...
Page 241
Chapter 6: Communication Part I SunSpec: 03H Read, 10H Write Number Data Access Address(H) Address(D) Parameters Range Default Type Property Registers 2(used as an C3A6H 50086 Frequency Scale Factor exponent of a sunssf power of10) C3A7H 50087 Total Real Power 32768~32767 W int16 Real Power: Phase A...
Page 242
Acuvim II Series Power Meter SunSpec: 03H Read, 10H Write Number Data Access Address(H) Address(D) Parameters Range Default Type Property Registers 3(used an Power Factor Scale C3BAH 50106 exponent of a sunssf Factor power of 10) C3BBH- 50107- 0~999999999 Total Real Energy: Export...
Page 243
Chapter 6: Communication Part I SunSpec: 03H Read, 10H Write Number Data Access Address(H) Address(D) Parameters Range Default Type Property Registers C3DDH- 50141- Total Reactive Energy: 0~999999999 int32 C3DEH 50142 Import varh C3DFH- 50143- Import Reactive Energy: 0~999999999 int32 C3E0H 50144 Phase A varh...
Acuvim II Series Power Meter Chapter 6: Communication Part II 6.3.17 Over/Under Alarm Setting This setting consists of alarm settings and single channel alarm settings. Alarm settings contain settings for all variables. There are 16 groups of records with the same format.
Page 245
Chapter 6: Communication Part II Alarm Settings: 03H Read, 10H Write Access Address(H) Address(D) Parameters Range Data Type Property 0~65535 Bit0: Channel 1 output Alarming output to DO3 104CH 4172 Word 1: Enable, 0: Disable setting Bit1: Channel 2 output .. Bit15: Channel 16 output 0~65535 Bit0: Channel 1 output...
Page 246
Acuvim II Series Power Meter Single Channel Alarm Settings: 03H Read, 10H Write Access Address(H) Address(D) Parameters Range Data Type Property 3rd group: parameter 1058H 4184 0~79 Word code 1: Greater than 3rd group: comparison 1059H 4185 2: Equal to...
Page 247
Chapter 6: Communication Part II Single Channel Alarm Settings: 03H Read, 10H Write Access Address(H) Address(D) Parameters Range Data Type Property 0:none 6th group: output to 106BH 4203 Word relay 1~8: related relay 7th group: parameter 106CH 4203 0~79 Word code 1: Greater than 7th group: comparison...
Page 248
Acuvim II Series Power Meter Single Channel Alarm Settings: 03H Read, 10H Write Access Address(H) Address(D) Parameters Range Data Type Property 107FH 4221 10th group: delay 0~3000 (*10ms) Word 0:none 10th group: output to 1080H 4222 Word relay 1~8: related relay...
Page 249
Chapter 6: Communication Part II Single Channel Alarm Settings: 03H Read, 10H Write Access Address(H) Address(D) Parameters Range Data Type Property 14th group: setpoint 1091H 4240 Related with parameters Word value 1092H 4241 14th group: delay 0~3000 (*10ms) Word 0:none 14th group: output to 1093H 4242...
Page 250
Acuvim II Series Power Meter Alarming Parameter Code Table Setting Setting Setting Alarming Object Alarming Object Alarming Object Value Value Value Power of phase B Power of phase C Power of all Reactive power of phase A Reactive power of phase B...
Page 251
Chapter 6: Communication Part II Alarming Group Records: 03H Read Access Address(H) Address(D) Parameters Range Data Type Property 1st group: over/under limit or reset Related to parameter 42ABH 17067 Word value chosen 17068- 1st group: Timestamp: 42ACH~42B2H Word 17074 yyyy:mm:dd:hh:ss:ms 42B3H 17075 2nd group: alarming status...
Page 252
Acuvim II Series Power Meter Alarming Group Records: 03H Read Access Address(H) Address(D) Parameters Range Data Type Property 17128- 7th group: Timestamp: 42E8H-42EEH Word 17134 yyyy:mm:dd:hh:ss:ms 42EFH 17135 8th group: alarming status 0-65535 Word 42F0H 17136 8th group: alarming parameter code...
Page 253
Chapter 6: Communication Part II Alarming Group Records: 03H Read Access Address(H) Address(D) Parameters Range Data Type Property 17188- 13th group: Timestamp: 4324H-432AH Word 17194 yyyy:mm:dd:hh:ss:ms 432BH 17195 14th group: alarming status 0-65535 Word 14th group: alarming parameter 432CH 17196 0-79 Word code...
Page 254
Acuvim II Series Power Meter log works in an identical fashion; therefore, only historical log 1 is described here. All register addresses in this section are shown within the address range of historical log 1. 1100H-11DFH (Historical Data Log 1)
Page 255
Chapter 6: Communication Part II • Valid register address ranges that can be recorded in the historical log registers are 4000H-412BH, 4294H-42A8H, 4349H-4398H, 4500H-461BH, 4620H-463DH. Item Descriptor List Registers: 1177H-11B1H Size: 1 byte per item, 117 bytes (59 registers) While the register list describes what to log, the item descriptor list describes how to interpret that information.
Page 256
Acuvim II Series Power Meter Log Status Block The Log Status Block describes the current status of the log in question. Table 6-59 Address(H) Address(D) Parameters Range Data Type Property 6100H~6101H 24832~24833 Max records 0~468104 Dword 6102H~6103H 24834~24835 Used records...
Page 257
Chapter 6: Communication Part II Address(H) Address(D) Parameters Format Property 24577 Record number Nnnnnnnn 6001H Status wwwwwwww 6002H~6003H 24578~24579 Offset 6004H~607EH 24580~24702 Window Log type: The log to be retrieved. Write this value to set which log is being retrieved. 0 - Historical Log 1 1 - Historical Log 2 2 - Historical Log 3...
Page 258
Acuvim II Series Power Meter in the data window. When the log is retrieved, the first (oldest) record is “latched.” This means that offset 0 will always point to the oldest record at the time of latching. Window: The actual data of the records, arranged according to the above settings.
Page 259
Chapter 6: Communication Part II 0x4002,0x4003,0x4004,0x4005,0x4006 and 0x4007 to 0x1102, 0x1103, 0x1104, 0x1105, 0x1106 and 0x1107. And the descriptor is 2, so set the 0x0202 and 0x0200 to 0x1177 and 0x1178. 2. The register is 6 and sector is 10, so we set 0x060A to 0x1100. 3.
Page 260
Acuvim II Series Power Meter 6.3.19 Time-of-Use Data Address of TOU Energy The data address saves the parameter of energy, which includes Data address of last month TOU energy, Data address of current month TOU energy, Data address of TOU parameter setting and Data address of TOU default parameter.
Page 261
Chapter 6: Communication Part II Data Type of Address(H) Address(D) Parameters Range Type Access 7210H~7211H 29200~29201 Eq_exp (peak) 0~999999999 Dword 7212H~7213H 29202~29203 Es (peak) 0~999999999 Dword 7214H~7215H 29204~29205 Ep_imp (valley) 0~999999999 Dword 7216H~7217H 29206~29207 Ep_exp (valley) 0~999999999 Dword 7218H~7219H 29208~29209 Eq_imp (valley) 0~999999999 Dword...
Page 262
Acuvim II Series Power Meter Data Type of Address(H) Address(D) Parameters Range Type Access 724CH~724DH 29260~29261 Eq_exp (valley) 0~999999999 Dword 724EH~724FH 29262~29263 Es (valley) 0~999999999 Dword 7250H~7251H 29264~29265 Ep_imp (normal) 0~999999999 Dword 7252H~7253H 29266~29267 Ep_exp (normal) 0~999999999 Dword 7254H~7255H 29268~29269...
Page 263
Chapter 6: Communication Part II Data Type of Address(H) Address(D) Parameters Range Type Access 731CH~731DH 29468~29469 Es (valley) 0~999999999 Dword 731EH~731FH 29470~29471 Ep_imp (normal) 0~999999999 Dword 7320H~7321H 29472~29473 Ep_exp (normal) 0~999999999 Dword 7322H~7323H 29474~29475 Eq_imp (normal) 0~999999999 Dword 7324H~7325H 29476~29477 Eq_exp (normal) 0~999999999 Dword...
Page 264
Acuvim II Series Power Meter Data Type of Address(H) Address(D) Parameters Range Type Access 7358H~7359H 29228~292291 Es (sharp) 0~999999999 Dword 735AH~735BH 29230~29231 Ep_imp (sharp) 0~999999999 Dword 735CH~735DH 29232~29233 Ep_exp (sharp) 0~999999999 Dword 735EH~735FH 29234~29235 Eq_imp (sharp) 0~999999999 Dword 7360H~7361H 29236~29237...
Page 265
Chapter 6: Communication Part II Data Type of Address(H) Address(D) Parameters Range Type Access Max of Es (peak) demand and 7530H~7533H 30000~30003 timestamp 32768~32767 Max of Ia (peak) demand and 7534H~7537H 30004~30007 timestamp 32768~32767 Max of Ib (peak) demand and 7538H~753BH 30008~30011 timestamp...
Page 266
Acuvim II Series Power Meter Data Type of Address(H) Address(D) Parameters Range Type Access Max of Ep_exp (all) demand and 7584H~7587H 30084~30087 timestamp 32768~32767 Max of Eq_imp (all) demand and 7588H~758BH 30088~30091 timestamp 32768~32767 Max of Eq_exp (all) demand and...
Page 267
Chapter 6: Communication Part II Data Type of Address(H) Address(D) Parameters Range Type Access 0: Sunday 770DH 30477 DST start Week Word 1~6, Monday to Saturday 770EH 30478 DST start first few Weeks Word 770FH 30479 DST start Hour 0~23 Word 7710H 30480...
Page 268
Acuvim II Series Power Meter Data Type of Address(H) Address(D) Parameters Range Type Access 7807H 30727 TOU factory setting 1: Enable Word Choice of calculation auto 7808H 30728 1: Enable Word reset (0: End of Month) TOU auto reset fixed date:...
Page 269
Chapter 6: Communication Part II Data Type of Address(H) Address(D) Parameters Range Type Access Data and season table of the 7823H~7825H 30755~30757 Word 2nd season Data and season table of the 7826H~7828H 30758~30760 Word 3rd season Data and season table of the 7829H~782BH 30761~30763 Word...
Page 270
Acuvim II Series Power Meter Data Type of Address(H) Address(D) Parameters Range Type Access 10th segment and tariff 785FH~7861H 30815~30817 Word number of the 1st schedule 11th segment and tariff 7862H~7864H 30818~30820 Word number of the 1st schedule 12th segment and tariff...
Page 271
Chapter 6: Communication Part II Data Type of Address(H) Address(D) Parameters Range Type Access From 1st to 14th segment The same as the 1st 7A3CH~7A65H 31292~31333 and tariff number of the 13th Word schedule schedule From 1st to 14th segment The same as the 1st 7A66H~7A8FH 31334~31375...
Page 272
Acuvim II Series Power Meter Data Type of Address(H) Address(D) Parameters Range Type Access Data and the schedule of the 7AC0H~7AC2H 31424~31426 Word 17th holiday Data and the schedule of the 7AC3H~7AC5H 31427~31429 Word 18th holiday Data and the schedule of the...
Page 273
Chapter 6: Communication Part II The 1st Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access The 1st holiday and schedule 7B00H~7B02H 31488~31490 Word (format: month/day/schedule) 7B03H~7B05H 31491~31493 The 2nd holiday and schedule Word 7B06H~7B08H 31494~31496...
Page 274
Acuvim II Series Power Meter The 1st Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7B5AH 31578 The 1st setting year Word 7b5BH 31579 Holiday number of the 1st year Word Table 6-67...
Page 275
Chapter 6: Communication Part II The 2nd Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7BA1H~7BA3H 31649~31651 The 24th holiday and schedule Word 7BA4H~7BA6H 31652~31654 The 25th holiday and schedule Word 7BA7H~7BA9H 31655~31657 The 26th holiday and schedule Word...
Page 276
Acuvim II Series Power Meter The 3rd Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7BE8H~7BEAH 31720~31722 The 17th holiday and schedule Word 7BEBH~7BEDH 31723~31725 The 18th holiday and schedule Word 7BEEH~7BF0H...
Page 277
Chapter 6: Communication Part II The 4th Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7C2FH~7C31H 31791~31793 The 10th holiday and schedule Word 7C32H~7C34H 31794~31796 The 11th holiday and schedule Word 7C35H~7C37H 31797~31799 The 12th holiday and schedule Word...
Page 278
Acuvim II Series Power Meter The 5th Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7C76H~7C78H 31862~31864 The 3rd holiday and schedule Word 7C79H~7C7BH 31865~31867 The 4th holiday and schedule Word 7C7CH~7C7EH...
Page 279
Chapter 6: Communication Part II Table 6-71 The 6th Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access The 1st holiday and schedule 7CCCH~7CCEH 31948~31950 Word (format: month/day/schedule) 7CCFH~7CD1H 31951~31953 The 2nd holiday and schedule Word 7CD2H~7CD4H 31954~31956...
Page 280
Acuvim II Series Power Meter The 6th Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7D23H~7D25H 32035~32037 The 30th holiday and schedule Word 7D26H 32038 The 6th setting year Word 7D27H 32039...
Page 281
Chapter 6: Communication Part II The 7th Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7D6AH~7D6CH 32106~32108 The 23rd holiday and schedule Word 7D6DH~7D6FH 32109~32111 The 24th holiday and schedule Word 7D70H~7D72H 32112~32117 The 25th holiday and schedule Word...
Page 282
Acuvim II Series Power Meter The 8th Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7DB1H~7DB3H 32177~32179 The 16th holiday and schedule Word 7DB4H~7DB6H 32180~32182 The 17th holiday and schedule Word 7DB7H~7DB9H...
Page 283
Chapter 6: Communication Part II The 9th Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7DF8H~7DFAH 32248~32250 The 9th holiday and schedule Word 7DFBH~7DFDH 32251~32253 The 10th holiday and schedule Word 7DFEH~7E00H 32254~32256 The 11th holiday and schedule Word...
Page 284
Acuvim II Series Power Meter The 10th Year Holiday Address Function: 03H Read 10H Preset Data Type of Address(H) Address(D) Parameters Type Access 7E42H~7E44H 32322~32324 The 3rd holiday and schedule Word 7E45H~7E47H 32325~32327 The 4th holiday and schedule Word 7E48H~7E4AH...
Page 285
Chapter 6: Communication Part II Table 6-76 Data Factory Address(H) Address(H) Parameters Property Range Default Type Setting Manual triggering 0xAA: Enable 8000H 32768 Word waveform 0: Disable bit1bit0: DI1, bit3bit2: DI2, bit5bit4: DI3, bit7bit6: DI4, bit9bit8: DI5, bit11bit10: D1 triggering – AXM- 8001H 32769 Word...
Page 286
Acuvim II Series Power Meter the same data format. Only one group of waveforms is saved in the registers. When retrieving the waveform, first write 1-8 group number into 0X801FH, then read the registers after it to acquire the waveform corresponding to the written group number.
Page 287
Chapter 6: Communication Part II Power Quality Event Retrieve Address Power quality event includes timestamp, triggering condition, and related settings. Every group uses the same data format. Only 10 groups of data are saved in the registers. When retrieving the event data, its parameters must be correctly set in order to get correct information.
Page 288
Acuvim II Series Power Meter Data Factory Address(H) Address(H) Parameters Property Range Default Type Setting 8D20H~ 36128~ No. 5 Event Word 8D27H 36135 8D28H~ 36136~ No. 6 Event Word 8D2FH 36143 8D30H~ 36144~ No. 7 Event Word 8D37H 36151 8D38H~ 36152~ No.
Chapter 6: Communication Part II Appendix Appendix A Technical Data and Specification Input Ratings CURRENT INPUTS (EACH CHANNEL) 1A (333mV) Nominal Current Options 1A (100mV Rope CT) 1A (80mA/100mA/200mA) 0-10A, 0-2A, 0-1.2A, Metering Range 0-1.2A, 0-1.2A Pickup Current 5mA, 1mA, 5mA, 5mA, 20Arms Continuous, 0.1% of Nominal...
Acuvim II Series Power Meter Metering PARAMETERS ACCURACY RESOLUTION RANGE 0.1V 10V~1000kV Voltage 0.1% 0.1mA 5mA~50000A Current 0.1% -9999MW~9999MW Power 0.1% 1var -9999Mvar~9999Mvar Reactive Power 0.1% 0~9999MVA Apparent Power 0.1% -9999MW~9999MW Power Demand 0.1% 1var -9999Mvar~9999Mvar Reactive Power Demand 0.1%...
Page 291
Appendix I/O Options DIGITAL INPUT Input Type Input Resistance 100kΩ Input Voltage Range 20~160 Vac/dc Input Current (Max) Start Voltage Stop Voltage Pulse Frequency (Max) 100Hz, 50% Duty Ratio (5ms ON and 5ms OFF) SOE Resolution DIGITAL OUTPUT (DO) (PHOTO-MOS) Voltage Range 0~250Vac/dc Load Current...
Page 292
Acuvim II Series Power Meter Standard Compliance & Certifications IEC 62053-22; Measurement Standard ANSI C12.20; IEC61557-12 Environmental Standard IEC 60068-2, CE, RoHS Safety Standard IEC 61010-1, UL 61010-1 IEC 61000-4/-2-3-4-5-6-8-11, CISPR 22, EMC Standard IEC 61000-3-2, IEC 61000-6-2/4 Outlines Standard DIN 43700, ANSI C39.1...
Appendix Control Power Universal AC or DC AC/DC CONTROL POWER Operating Range 100~415Vac, 50/60Hz; 100~300Vdc Burden Frequency 50/60Hz Withstand 3250Vac, 50/60Hz for 1 minute Installation Category III (Distribution) LOW VOLTAGE DC CONTROL POWER (OPTIONAL) Operating Range 20~60Vdc Burden Operating Environment -25°C to 70°C Operating Temperature -13°F to 158°F...
Ordering Example: Acuvim IIR-D-5A-P1V3 Note: Accuenergy suggests using USB-RS485 converter for configuration, and 3 CTs per three phase circuits. All fields must be completed to create a part number. Add “-S” after power supply for anti-tampering seal option. Contact for 400Hz frequency option; Acuvim IIW doesn't support this type.
Page 295
Appendix I/O Module (Optional) Logic Module Input/Output Type AXM-IO1 Ordering Example: AXM-IO1-1 AXM-IO2 A: 4~20mA AXM-IO3 B: 0~20mA C: 1~5V D: 0~5V Ordering Example: AXM-IO3-1B Accessories (Optional) Remote Display REM-DS2: (Only for Acuvim II DIN-Rail Mount "M" option) AXM-DIN: DIN Rail Adapter IP66/NEMA4X: Environmental Protection Cover USB-RS485:...
Need help?
Do you have a question about the Acuvim II Series and is the answer not in the manual?
Questions and answers