AccuEnergy Acuvim II Series User Manual

AccuEnergy Acuvim II Series User Manual

Power meter
Hide thumbs Also See for Acuvim II Series:

Advertisement

Quick Links

Acuvim II Series Power Meter
AXM-WEB-PUSH
User's Manual

Advertisement

Table of Contents
loading

Summary of Contents for AccuEnergy Acuvim II Series

  • Page 1 Acuvim II Series Power Meter AXM-WEB-PUSH User's Manual...
  • Page 2 Copyright © 2018 V2.00 This manual may not be altered or reproduced in whole or in part by any means without the ex- pressed written consent of Accuenergy.
  • Page 3 The information contained in this document is believed to be accurate at the time of publica- tion, however, Accuenergy assumes no responsibility for any errors which may appear here and reserves the right to make changes without notice. Please ask the local representative for latest product specifications before ordering.
  • Page 4: Table Of Contents

    Acuvim II Series - AXM WEB PUSH Contents 1. Introduction to Ethernet ............4 2. Functional Description of the Ethernet module ......4 3. Appearance and Dimensions ............4 4. Installation Method ..............5 5. Definition of RJ45 ..............6 6. Initializing the Ethernet module ..........7 7.
  • Page 5 Acuvim II Series - AXM WEB PUSH 10. Web Interface Readings and Parameter Settings ....26 10.1 User Access Login ..............26 10.2 Dashboard ................27 10.3 Metering web page ..............28 Basic Metering: ..................29 Power & Energy: ..................30 Min/Max: ....................30 THD: ......................31 Harmonics: ....................32 Phase Angles: ....................33...
  • Page 6: Introduction To Ethernet

    The AXM-WEB-PUSH module supports the Modbus-TCP protocol. When connected to the Acuvim II series meter, it is a slave device that can only respond to queries. The default value for the Modbus Port is 502. The user defined range is 2000~5999.
  • Page 7: Installation Method

    22mm Chapter 4: Installation Method (Side View) 90mm (Top View) (Bottom View) 4. Installation Method V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 8: Definition Of Rj45

    1. Remove cover from the back of the Acuvim II series meter which will expose the socket. 2. Insert the installation clips to the grooves in the Acuvim II series meter and then press the AXM-WEB-PUSH module lightly to establish a linking between meter and module.
  • Page 9: Initializing The Ethernet Module

    Ethernet module settings from the display: • Press the 'H' and 'V/A' buttons simultaneously on the Acuvim II series. Release the buttons and the meter will enter the meter selecting mode, as indicated by the flashing 'Meter' cursor.
  • Page 10 Acuvim II Series - AXM WEB PUSH • Press the 'P' or 'E' button to move the cursor to 'Setting'. Press 'V/A' button to enter the parameter setting mode. The device address page is the first page of the 'Setting' mode. It will show the Modbus address of the meter for a second before prompting for the pass- word og the device.
  • Page 11 'V/A' button to enter edit mode. Press 'P' or 'E' to change the setting and press 'V/A' to confirm. Note: If the DHCP is selected as Auto, the Ethernet module needs to be rebooted before it can be assigned with the new IP address. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 12 Acuvim II Series - AXM WEB PUSH • Press 'P' to get to "N02 IP address" This is the IP address of the meter and will be the IP address to access the web interface of the module. Users can configured the IP address if the DHCP is configured to Manual.
  • Page 13 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to confirm. The DNS parameters must be set correctly to use the SMTP, FTP/HTTP Post and AcuCloud functions. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 14 Acuvim II Series - AXM WEB PUSH • Press 'P' to get to "N06 DNS Secondary Server". Press 'V/A' to configure the DNS address. The cursor of the first digit will begin to flash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the flashing cursor and press 'V/A' to con- firm.
  • Page 15: Cable

    7. Cable An RJ45 cable is needed to connect the meter to the network. A shielded twisted pair cable(- standard 568A or standard 568B) is recommended as reference to the EIA/TIA standard. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 16: Connection Method

    Acuvim II Series - AXM WEB PUSH 8. Connection method 8.1 Direct Connect to a Computer The AXM-WEB-PUSH can be connected to a computer using a crossover cable(standard 568A). The AXM-WEB-PUSH module supports Modbus-TCP and HTTPS Functions for this method of connection.
  • Page 17 Chapter 8: Connection Method • Once there right click on the local area connection icon and click properties • Select the icon that says Internet Protocol Version 4 TCP/IP V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 18 Acuvim II Series - AXM WEB PUSH • The Internet Protocol Version 4(TCP/IP) Properties box will pop up • Click on “Use the following IP address” and enter in an IP number so that meter and computer are in the same local network range. For example, if the meter has IP address of 192.168.1.254, then the computer must be assigned with a IP 192.168.1.xxx, where xxx can...
  • Page 19: Direct Connect To Router/Switch

    Auto to have the router assign the meter with an IP address or the DHCP can be configured to Manual to set an IP address using the information in Chapter 5. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 20: Description Of Modbus-Tcp Protocol

    Acuvim II Series - AXM WEB PUSH 9. Description of Modbus-TCP Protocol The Modbus-TCP protocol is used as one of the communication protocols in the AXM-WEB- PUSH. The protocol establishes a master and slave connection in Ethernet. The master device (client) first sets up a TCP-IP link with slave device (server).
  • Page 21: Function Field

    If the master needs to perform a write to a group of registers in the slave(function code 10 hexadecimal), the data field specifies the starting register, how many registers to write, the count of data bytes to follow in the data field and the data to be written into the registers. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 22: Format Of Communication

    Acuvim II Series - AXM WEB PUSH 9.2 Format of communication Explanation of frame Transaction Transaction Protocol Protocol Unit Length hi Length lo identifier hi identifier lo identifier hi identifier lo identifier Data start reg hi Data start reg lo...
  • Page 23: Read Status Of Relay (Function Code 01)

    Chapter 9: Description of Modbus-TCP Protocol 9.2.1 Read Status of Relay (Function code 01) This function code is used to read the relay output status in the Acuvim II series meter. 1=On 0=Off There are 8 relay outputs in the Acuvim II series meter and they start at address 0000H.
  • Page 24: Read Status Of Di(Function Code 02)

    9.2.2 Read Status of DI(Function Code 02) 1=On 0=Off There are 28 DIs in the Acuvim II series meter starting at address 0000H. The following query is to read 4 DI statuses of AXM-IO1 module with logic address of 1 in the Acuvim II series meter.
  • Page 25: Read Data (Function Code 03)

    9.2.3 Read Data (Function Code 03) Query This function allows the user to obtain the measurement results of the Acuvim II series meter. Below is an example to read 6 registers corresponding to the device clock of the meter, starting at 1040H.
  • Page 26: Control Relay(Function Code05)

    This function code enables the control of a single relay output in the Acuvim II series meter. Any relay output in the Acuvim II series meter can be controlled on or off starting at 0000H. Sending the data 'FF00H' will set they relay output on and sending '0000H' will turn it off; all other values are illegal and will not affect they relay output status.
  • Page 27: Preset/Reset Multi-Register(Function Code 16)

    This function code allows the user to modify the contents of a register. The example below is a request to an Acuvim II series meter with device address 1 to preset the CT1(500) and CT2(5) registers. The CT1 data address is 1008H and CT2 is at 1009H.
  • Page 28: Web Interface Readings And Parameter Settings

    Acuvim II Series - AXM WEB PUSH 10. Web Interface Readings and Parameter Settings The AXM-WEB-PUSH module supports the HTTPS protocol to allow for the use of a web interface. The user will need to visit access the AXM-WEB-PUSH web interface to configure the module and use its functions.
  • Page 29: Dashboard

    The parameters on this page are updated every 5 sec. NOTE: If user is logged in with 'User' access, clicking on 'Settings' will automatically log the V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 30: Metering Web Page

    Acuvim II Series - AXM WEB PUSH user out from the web interface. 10.3 Metering web page Click on the 'Metering' tab to visit the metering data web pages. There are seven kinds of me- tering parameter web pages. They are "Basic Metering", "Power & Energy", "Min/Max", 'THD', 'Harmonics', "Phase Angles"...
  • Page 31: Basic Metering

    Chapter 10: Web Interface Readings and Parameter Settings Basic Metering: The Basic Metering webpage includes the data of real-time parameters for the Acuvim II series meter. This includes the Line Voltages, Phase Voltages, Current, Neutral Current, Active, Reac- tive and Apparent Power, Power Factor, Frequency and Load type.
  • Page 32: Power & Energy

    Acuvim II Series - AXM WEB PUSH Power & Energy: The Power & Energy webpage shows the energy data for the Acuvim II series meter such as the Active and Reactive energy that is consumed and delivered as well as the Apparent energy per phase and total.
  • Page 33: Thd

    THD: The THD webpage shows the power quality data such as the THD, THFF, Crest and K Factor for both the voltage and current. The parameters in this webpage are updated every 15 sec. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 34: Harmonics

    Acuvim II Series - AXM WEB PUSH Harmonics: The Harmonics webpage will show the harmonics of the voltage and the current waveform being measured. It will display the harmonics of each phase in graphical and tabular format. Select between voltage and current to view their respective harmonics as well as between the 2nd-31st harmonics or 32nd-63rd from the drop down list.
  • Page 35: Phase Angles

    The parameters in this webpage are updated every 5 sec. Sequence: The Sequence webpage will show the positive, negative and zero components of the voltage and current waveform being measured. The parameters in this webpage are updated every 15 sec. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 36: Status Web Page

    Click on the 'Status' tab to visit the status parameter web pages. There are four kinds of status web pages. They are "Device Information", "Alarm Status", 'I/O' and 'SOE' statuses. Each web- page shows different statuses or information about the Acuvim II series meter. V: 2.0 Revised: Sept. 2018...
  • Page 37: Device Information

    The Device Information webpage shows information about the Acuvim II series meter and AXM- WEB-PUSH module. It will contain the model of the Acuvim II series meter, serial number, firm- ware version and meter addresses. It also contains the serial number, hardware and firmware version as well as the MAC address of the AXM-WEB-PUSH module.
  • Page 38: I/O

    Acuvim II Series - AXM WEB PUSH I/O: The I/O webpage will display the status of the I/O modules that are connected and their values depending on the model of the module that is connected to the meter. I.E. The AXM-IO11 mod- ule will display the Relay Output status(on/off), DI status/counter.
  • Page 39: Soe

    SOE: The SOE webpage will display the Sequence of Event log for the enabled I/O module that is attached to the Acuvim II series meter with timestamps. It will display the DI status for up to 20 events. The parameters in this webpage are updated every 10 sec.
  • Page 40: Meter Setting

    Acuvim II Series - AXM WEB PUSH NOTE: The Settings webpage will only be accessible at Admin level. Meter Setting: The meter setting webpage will allow user to configure basic meter settings in order for the meter to measure the voltage and current and display it correctly.
  • Page 41 I C Direction: Represents the flow of direction for the Phase C current being measured, con- figure this setting to troubleshoot issues related to incorrect polarity of readings such as real power, Power Factor and etc. Click 'Save' after changing any settings. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 42: Communication

    Acuvim II Series - AXM WEB PUSH Communication: The communication setting webpage will allow the user to configure settings related to the Ethernet network. The functions that the AXM-WEB-PUSH support can be configured from this webpage by selecting the corresponding tab such as Emails, Time/Date , Datalog, HTTP/FTP Post, AcuCloud Post for communicating with the AcuCloud software, SNMP and DNP3.
  • Page 43: Network

    Click 'Save' after changing any settings. Users will be prompted to reboot the AXM-WEB-PUSH immediately or later. If later is chosen the AXM-WEB-PUSH will need to be rebooted from the 'Management' page. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 44: Emails

    Acuvim II Series - AXM WEB PUSH Emails: The AXM-WEB-PUSH supports the SMTP protocol so users can setup the email function on the AXM-WEB-PUSH to enable the meter to send emails based on a time interval or when there is an alarm or SOE event or a combination of both.
  • Page 45 SMTP Enabled: Select 'Yes' to enable and to further configure the settings related to the SMTP function. SMTP Server: Enter the URL of a valid SMTP server. I.E. mail.accuenergy.com or smtp.gmail. SMTP Port: Enter the port number associated with the SMTP server.
  • Page 46 Acuvim II Series - AXM WEB PUSH Where xxx can be for receiving emails on: • Metering: Report on Real-time voltage, current, power and etc. • Energy: Report on energy parameters. • Harmonics: Report on the voltage and current harmonics from 2nd to 63rd.
  • Page 47: Time/Date

    Chapter 10: Web Interface Readings and Parameter Settings Time/Date: The device clock of the Acuvim II series meter can be set through the web interface of the AXM- WEB-PUSH module. The AXM-WEB-PUSH module also supports the SNTP (Simple Network Time Protocol) protocol so that the module can update the meter's device clock by synchro- nizing with a time server.
  • Page 48: Datalog

    Acuvim II Series - AXM WEB PUSH Examples of North American SNTP servers are: 0.us.pool.ntp.org 1.us.pool.ntp.org 2.us.pool.ntp.org 3.us.pool.ntp.org For more NTP servers based on region, visit the following site: http://www.pool.ntp.org/en/ Click 'Save' after changing any settings. Users will be prompted to reboot the AXM-WEB-PUSH immediately or later.
  • Page 49 SFTP Enable: To download the logged data from the module using a FTP client, select Enable. The log file will then be available to be downloaded using a FTP client using the following credentials: V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 50 Username: sftpuser SFTP Password: accuenergy Port: 22 By default the password for retrieving the backup log files is 'accuenergy'. The user can configure any password or can reset to the default of accuenergy by clicking on the "Reset SFTP Password".
  • Page 51 The log file length can be from 15 sec to 1 month. With the above settings configured the following settings need to be configured depending on which protocol will be used: V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 52 Acuvim II Series - AXM WEB PUSH HTTP Push Channel 1 Enable: Select 'Yes' to enable and to further configure the HTTP Push 1 settings. HTTP Push 1 Meter Upload Url: Enter the Url of the HTTP server that will receive the data from the meter.
  • Page 53 Click 'Save' after changing any settings. Users will be prompted to reboot the AXM-WEB- PUSH immediately or later. If later is chosen the AXM-WEB-PUSH will need to be reboot- ed from the 'Management' page. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 54: Acucloud Post

    Acuvim II Series - AXM WEB PUSH AcuCloud Post: The AXM-WEB-PUSH module can directly interface with the Accuenergy Cloud software Acu- Cloud. The AXM-WEB-PUSH will post data to the cloud software every five minutes. AcuCloud will require the serial number of the AXM-WEB-PUSH module which will then provide a token that will be used to configure the AXM-WEB-PUSH so it can send its data to AcuCloud.
  • Page 55: Snmp

    SNMP Enable: Select 'Enable' to enable the function and to further configure the settings relat- ed to the SNMP protocol. Read Only Community: By default the community string is Public, this configuration is similar to a password which allows only authorized users to access the meters data. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 56 Acuvim II Series - AXM WEB PUSH SNMP Port: By default the SNMP Port is configured to 161. The SNMP Port can be any value from 16100 to 16199. Trap Enable: Select 'Enable' so that the meter will send a message to the management station when an event is triggered.
  • Page 57: Management

    The user can also download the network log file for the module from this page which can be used for diagnostics of the module. Note: Please send the log file to Accuenergy's Technical Support(support@accuenergy.com) for analysis.
  • Page 58 Acuvim II Series - AXM WEB PUSH To update the module using the Select Firmware File option: • Click on "Choose File" and select the firmware file to update from your computer. Then click on 'Upload'. Once the upload was successfully uploaded you will see the following page confirming that the file was uploaded.
  • Page 59 Once the update is complete, you will see the following page. Note: The module is currently rebooting. This may take 1-2 minutes to complete. When com - plete, refresh the page to reconnect to the meter. You will be required to log in again. V: 2.0 Revised: Sept. 2018 www.accuenergy.com...
  • Page 60 MAKE ENERGY USAGE SMARTER ACCUENERGY (CANADA) INC. TF: 1-877-721-8908 INT: +1-416-497-4100 2 Lansing Square, Suite 700 FAX: +1-416-497-4130 Toronto, ON M2J 4P8, Canada E: marketing@accuenergy.com...

This manual is also suitable for:

Axm-web-push

Table of Contents