Please read this manual carefully before installation, operation and maintenance of the Acuvim II series meter. The following symbols in this manual are used to provide warning of danger or risk during the installation and operation of the meters.
Acuvim II Series - AXM WEB PUSH Contents Chapter 1: Introduction to Ethernet ………………………………………6 Chapter 2: Functional Description of the Ethernet module …………6 Chapter 3: Appearance and Dimensions ………………………………7 Chapter 4: Installation Method ………………………………………… 8 Chapter 5: Definition of RJ45 …………………………………………… 9 Chapter 6: Initializing the Ethernet module …………………………...
Page 5
Acuvim II Series - AXM WEB PUSH Chapter 10 : Web Interface Readings and Parameter Settings …… 10.1 User Access Login …………………………………………………………………36 10.2 Dashboard ………………………………………………………………………37 10.3 Metering web page ……………………………………………………………38 10.3.1 Trend Log ………………………………………………………………39 10.3.2 Basic Metering ……………………………………………………………40 10.3.3 Power & Energy ………………………………………………………41...
Page 6
Acuvim II Series - AXM WEB PUSH Chapter 11 : Communications ………………………………………………… 11.1 WiFi Communication ………………………………………………………52 11.2 Network ………………………………………………………………………55 11.3 Emails …………………………………………………………………………56 11.4 Time & Date ………………………………………………………………………59 11.5 Datalog ……………………………………………………………………………61 11.5.1 Downloading the Data Logs ………………………………………64 11.6 HTTP/FTP Post ……………………………………………………………………64 11.6.1 HTTP Post …………………………………………………………………66...
Page 7
Acuvim II Series - AXM WEB PUSH Chapter 13 : Network Diagnostic ……………………………………………… 13.1 Network Status ………………………………………………………………83 13.2 Host Lookup …………………………………………………………………84 13.3 Connection Test …………………………………………………………………85 Chapter 14 : Firmware Update …………………………………………………… 14.1 Manual Firmware Update …………………………………………………86 14.2 Remote Firmware Update ………………………………………………...
The AXM-WEB-PUSH module supports the Modbus-TCP protocol. When connected to the Acuvim II series meter, it is a slave device that can only respond to queries. The default value for the Modbus Port is 502. The user defined range is 2000~5999.
1) Remove cover from the back of the Acuvim II series meter which will expose the socket. 2) Insert the installation clips to the grooves in the Acuvim II series meter and then press the AXM-WEB-PUSH module lightly to establish a linking between meter and module.
Acuvim II Series - AXM WEB PUSH 5. Definition of RJ45 The AXM-WEB-PUSH uses a standard RJ45 connector to access the Ethernet network. The me- chanical and electrical characteristics of the connector are consistent with the requirements of IEC 603-7.
Ethernet module settings from the display: • Press the H and V/A buttons simultaneously on the Acuvim II series for about a second and release. The screen will go blank and Meter will be flashing. V: 1.36 Revised: June. 2020...
Page 13
Acuvim II Series - AXM WEB PUSH • Press the P or E button to move the cursor to Setting and then press V/A to enter the parameter setting mode. The device address page is the first page of the 'Setting' mode. It will show the Modbus address of the meter for a second before prompting for the pass- word of the device.
Page 14
Acuvim II Series - AXM WEB PUSH • The first page of the NET Settings will be the N01 DHCP page. By default this is config- ured to Manual. Configuring this setting to Auto will allow the network to assign the meter an IP address, whiles Manual will allow the user to configure the IP address.
Page 15
Acuvim II Series - AXM WEB PUSH • Press P to move to the next screen which is N02 IP address, this is the IP address of the meter and will be the IP address to access the web interface of the module. Users can configured the IP address if the DHCP is configured to Manual.
Page 16
Acuvim II Series - AXM WEB PUSH Press P to move to the N04 Gateway page. This is the meters gateway setting, and will • need to be configured if the DHCP is set to Manual. To configure the gateway press V/A to enter edit mode, the cursor will begin to flash on •...
Page 17
Acuvim II Series - AXM WEB PUSH • Press P to move to the N05 DNS Primary Server page. This is the primary DNS setting of the meter. To configure the DNS press V/A to enter edit mode, the cursor of the first digit will begin to •...
Page 18
Acuvim II Series - AXM WEB PUSH • Press P to move to N07 Modbus Port page. This is the Modbus port setting of the meter, the default is 502 and the range is from 2000-5999. • To configure the Modbus port press V/A to enter edit mode, the cursor of the first digit will begin to flash.
Page 19
Acuvim II Series - AXM WEB PUSH • Press P to move to the N08 HTTP Port page. This is the meters HTTP port setting screen, the default is 80 and the range is from 6000-9999. To configure the HTTP port press V/A to enter edit mode, the cursor of the first digit will •...
Page 20
Acuvim II Series - AXM WEB PUSH After configuring the AXM-WEB-PUSH module, press the H and V/A buttons simultaneously, the screen will go blank and Setting will be flashing. From here users can press either the P or E buttons to navigate to Meter and then press V/A to navigate back to the main metering page.
Acuvim II Series - AXM WEB PUSH 7. Cable An RJ45 cable is needed to connect the meter to the network. A shielded twisted pair cable(standard 568A or standard 568B) is recommended as reference to the EIA/TIA standard. 8. Connection Method There are two ways that users can access the meters web interface, either using a direct Ether- net connection or by connecting to a router/switch.
Page 22
Acuvim II Series - AXM WEB PUSH To connect meter directly to the computer, the following can be done using a computer run- ning the Windows OS: • Manually connect the meter via Ethernet cable to the computer • Right click on the connection icon •...
Page 23
Acuvim II Series - AXM WEB PUSH • Once there, right click on the Ethernet icon and select Properties . Select the icon Internet Protocol Version 4 TCP/IP. • V: 1.36 Revised: June. 2020 www.accuenergy.com...
Page 24
Acuvim II Series - AXM WEB PUSH • The Internet Protocol Version 4(TCP/IP) Properties box will pop up. Click on Use the following IP address and enter in an IP number so that meter and computer are in the same local network range. For example, if the meter has IP address of 192.168.1.254, then the computer must be assigned with a IP 192.168.1.xxx, where xxx can be any number but...
Page 25
Acuvim II Series - AXM WEB PUSH • Once you have entered in the IP address, press the Tab key on your keyboard to automati-cally populate the sub mask setting for the computer. • Before selecting the OK button make note of the IP address you have assigned to the me- ter and then press OK.
Acuvim II Series - AXM WEB PUSH 8.2 Connection to Router/Switch The AXM-WEB-PUSH can be connected to a router or switch using a patch cable. If users have the DHCP set for AUTO, once connected to a router/switch the IP address will automatically be assigned to the meter by the network.
Acuvim II Series - AXM WEB PUSH 9. Description of Modbus-TCP Protocol The Modbus-TCP protocol is used as one of the communication protocols in the AXM-WEB- PUSH. The protocol establishes a master and slave connection in Ethernet. The master device (client) first sets up a TCP-IP link with slave device (server).
Acuvim II Series - AXM WEB PUSH 9.1.1 Modbus Application Header (MBA Header) Field Modbus application header field is the start of the data frame, and consists of seven bytes. Field Length Description Identification of a Modbus Request/Response Transaction Identifier...
Acuvim II Series - AXM WEB PUSH 9.1.3 Data Field The data field is constructed using sets of two hexadecimal digits, in the range of 00 to FF. The data field of messages sent from a master to slave contains additional information which the slave must use to take the action defined by the function code.
Page 30
Acuvim II Series - AXM WEB PUSH The meaning of each abbreviated field above is: Transaction identifier hi: High byte of transaction identifier Transaction identifier lo: Low byte of transaction identifier Protocol identifier hi: High byte of protocol identifier Protocol identifier low: Low byte of protocol identifier...
Acuvim II Series - AXM WEB PUSH 9.2.2 Read Status of Relay (Function code 01) Function Code 1 This function code is used to read the relay output status in the Acuvim II series meter. 1=On 0=Off There are 8 relay outputs in the Acuvim II series meter and they start at address 0000H.
Page 32
Acuvim II Series - AXM WEB PUSH Response The Acuvim II series meter responds back with the MBAP header, function code, quantity of data bytes and the data. An example of response to read the status of the first 2 relay outputs starting at 0000H is shown below.
9.2.3 Read Status of DI(Function Code 02) 1=On 0=Off There are 28 DIs in the Acuvim II series meter starting at address 0000H. The following query is to read 4 DI statuses of AXM-IO1 module with logic address of 1 in the Acuvim II series meter.
9.2.4 Read Data(Function Code 03) Query This function allows the user to obtain the measurement results of the Acuvim II series meter. Below is an example to read 6 registers corresponding to the device clock of the meter, starting at 1040H.
Page 35
Acuvim II Series - AXM WEB PUSH An example response is provided to read the time (2006-12-18 14:15:20). Transaction Transaction Protocol Protocol Unit Length hi Length lo identifier hi identifier lo identifier hi identifier lo identifier Byte Data1 Data1 Data2...
This function code enables the control of a single relay output in the Acuvim II series meter. Any relay output in the Acuvim II series meter can be controlled on or off starting at 0000H. Sending the data 'FF00H' will set they relay output on and sending '0000H' will turn it off; all other values are illegal and will not affect they relay output status.
This function code allows the user to modify the contents of a register. The example below is a request to an Acuvim II series meter with device address 1 to preset the CT1(500) and CT2(5) registers. The CT1 data address is 1008H and CT2 is at 1009H.
Acuvim II Series - AXM WEB PUSH 10. Web Interface Readings and Parameter Settings The AXM-WEB-PUSH module supports the HTTPS protocol to allow for the use of a web inter- face. The user will need to access the AXM-WEB-PUSH web interface to configure the module and to further use its functions.
Acuvim II Series - AXM WEB PUSH The two different access levels are summarised below: Access Level Default Password Read Parameter/Status Configure Settings User view Admin admin 10.2 Dashboard In the dashboard, the user will find the menu tabs to access different pages in the web inter- face such as Metering, Status, and Settings.
Trendlog , Basic Metering , Power & Energy , Min/Max , THD , Harmonics , Phase Angles , Sequence , and Data Log . Each web page shows data from the Acuvim II series meter. V: 1.36 Revised: June. 2020...
Acuvim II Series - AXM WEB PUSH 10.3.1 Trend Log The Trend Log web page includes the real-time and energy trend diagram. The real-time trend log diagram can be selected to show the phase voltage, line voltage, current, active power, reactive power, apparent power and power factor for each phase.
Acuvim II Series - AXM WEB PUSH 10.3.2 Basic Metering The Basic Metering web page includes the data of real-time parameters for the Acuvim II series meter. This includes the Line Voltages, Phase Voltages, Current, Neutral Current, Active, Reac- tive and Apparent Power, Power Factor, Frequency and Load type.
Acuvim II Series - AXM WEB PUSH 10.3.3 Power & Energy The Power & Energy web page shows the energy data for the Acuvim II series meter such as the Active and Reactive energy that is consumed and delivered as well as the Apparent energy per phase.
Acuvim II Series - AXM WEB PUSH 10.3.4 Min/Max The Min/Max page shows the maximum and minimum statistics that the meter has records since the lifetime of the meter or from the last reset of the min/max statistics as well as the timestamps they were recorded at.
Acuvim II Series - AXM WEB PUSH 10.3.5 THD The THD web page shows the power quality data such as the Total Harmonic Distortion, THFF, Crest Factor and K Factor for both the voltage and current. The parameters in this web page are updated every 15 seconds.
Acuvim II Series - AXM WEB PUSH 10.3.6 Harmonics The Harmonics web page will show the harmonics of the voltage and the current waveform being measured. It will display the harmonics of each phase in a graphical and tabular format.
Acuvim II Series - AXM WEB PUSH 10.3.7 Phase Angle The Phase Angles web page will show the phase angles of the voltage and current waveform being measured which can be used for remote troubleshooting. This page provide a visual dia- gram of the phase angles with respect to the voltage connected to the Phase A voltage input.
Acuvim II Series - AXM WEB PUSH 10.3.8 Sequence The Sequence web page will show the positive, negative and zero components of the voltage and current waveform being measured. The parameters in this web page are updated every 15 seconds.
Acuvim II Series - AXM WEB PUSH 10.3.9 Data log The data log web page includes all the data files from the meter. The log file for the meter can be downloaded by clicking on the file name where the file is downloaded as a csv file.
The Device Information web page shows information about the Acuvim II series meter and AXM-WEB-PUSH module. It will contain the model of the Acuvim II series meter serial number, firmware version and meter addresses. It also contains the serial number, hardware and firm- ware version as well as the MAC address of the AXM-WEB-PUSH module.
Acuvim II Series - AXM WEB PUSH 10.4.2 Alarm Status The alarm status web page shows the alarm log of the meter. It will show the status of up to 16 alarm events indicating the alarm ID, status, parameter, value and timestamp of the alarm event.
10.4.4 SOE The SOE web page will display the Sequence of Event log for the enabled I/O module that is attached to the Acuvim II series meter with timestamps. It will display the DI status for up to 20 events.
Acuvim II Series - AXM WEB PUSH 10.5.1 Meter Setting The meter setting web page will allow user to configure basic meter settings in order for the meter to correctly read the voltage and current correctly. Voltage Wiring: Select how the meter's voltage input terminal is wired by selecting a configu- ration from the drop down list.
Acuvim II Series - AXM WEB PUSH Click Save after changing any settings. 11. Communications The communication setting web page will allow the user to configure settings related to the Ethernet network. The functions that the AXM-WEB-PUSH support can be configured from this...
Page 55
Acuvim II Series - AXM WEB PUSH The following settings need to configured for using the WIFI: WiFi Enabled: Select the Enable or Disable communication through WIFI. WiFi Mode: The WIFI can be configured to work in two modes just like any other WIFI device.
Page 56
Acuvim II Series - AXM WEB PUSH In station Mode the DHCP can configured as either manual or auto. • If manual, users can configure the IP, Subnet Mask and Gateway and DNS Servers. • If auto, users can check the meter's display to get the IP address and all other network configurations assigned by the wireless network.
Acuvim II Series - AXM WEB PUSH 11.2 Network Under the network tab users can configure all network related settings for the module. DHCP: Select Manual to manually configure the IP address to access the meter. If set to Manual, user will also need to manually configure the Subnet Mask and Gate- way.
Acuvim II Series - AXM WEB PUSH 11.3 Emails The AXM-WEB-PUSH supports the SMTP protocol so users can send emails based on a time in- terval or when there is an alarm or SOE event or a combination of both. Users must know their SMTP server provider and details regarding their SMTP server, which can be provided by users' IT personnel.
Page 59
Acuvim II Series - AXM WEB PUSH After configuring the above settings, the next step is to select the content for the emails. To enable emails to be sent based on a new Alarm or SOE Event, select Yes under SMTP Trig- gered Sending Alarm Event or SMTP Triggered Sending SOE Event .
Page 60
Acuvim II Series - AXM WEB PUSH To receive email reports at timed intervals, configure the following settings: SMTP Timed Sending Interval: Configure this setting with a value between 5-1440 min. This represents how often the emails will be sent.
Acuvim II Series - AXM WEB PUSH 11.4 Time & Date The device clock of the Acuvim II series meter can be set through the web interface of the AXM- WEB-PUSH module. The AXM-WEB-PUSH module also supports the SNTP (Simple Network Time Protocol) protocol so that the module can update the meter's device clock by synchroniz- ing with a time server.
Page 62
Acuvim II Series - AXM WEB PUSH Examples of North American SNTP servers are: 0.us.pool.ntp.org 1.us.pool.ntp.org 2.us.pool.ntp.org 3.us.pool.ntp.org For more NTP servers based on region, visit the following site: http://www.pool.ntp.org/en/ Click Save after changing any settings, users will be prompted to reboot the AXM-WEB-PUSH immediately or later.
Acuvim II Series - AXM WEB PUSH 11.5 Datalog The AXM-WEB-PUSH module supports logging data onto its memory which has 4GB of internal memory for storage. Once enabled users can configure the meter to log data daily or monthly. The data can be downloaded as a .csv file using a sFTP client or simply from the meters web interface from the Metering>Datalog page.
Page 64
Acuvim II Series - AXM WEB PUSH Next, configure the following data log details: Log Start Time: Select a valid time for the meter to start logging the data. Set this to the cur- rent date and time. Log Interval: Select how frequently the module will log data to the file from the drop down list.
Page 65
Acuvim II Series - AXM WEB PUSH By default the password for retrieving the backup log files is accuenergy . The user can config- ure any password or can reset to the default password by clicking on Reset SFTP Password.
Acuvim II Series - AXM WEB PUSH 11.5.1 Downloading the Data Logs The data logs can be downloaded directly from the AXM-WEB-PUSH interface. To download the CSV files, click on the Metering header at the top right of the page, then click on the Datalog tab.
Page 67
Acuvim II Series - AXM WEB PUSH The following settings must be configured in order to use the HTTP/FTP post function: Data Upload: To use the HTTP/FTP post function to send data to the appropriate server, select the Enable option to view and configure the settings that are applicable.
Acuvim II Series - AXM WEB PUSH 11.6.1 HTTP Post With the above settings configured the following settings need to be configured depending on which protocol will be used: HTTP Push Channel 1 Enable: Select Yes to enable and to further configure the HTTP Push 1 settings.
Page 69
Acuvim II Series - AXM WEB PUSH NOTE: The "TEST HTTP Push1" button should only be utilized after clicking the 'Save' button otherwise a fail response will be observed. If a fail response occurs after clicking 'Save', double check the post settings, time settings and the network settings.
Acuvim II Series - AXM WEB PUSH 11.6.2 FTP Post FTP Push Enable: Select 'Yes' to enable and further configure the FTP Push settings. FTP Push Meter Upload Url: Enter the Url of the FTP server that will receive the data from the meter.
Page 71
Acuvim II Series - AXM WEB PUSH Click Save after changing any settings. Users will be prompted to reboot the AXM-WEB-PUSH immediately or later. If later is chosen the AXM-WEB-PUSH will need to be rebooted from the Management page in order for the settings to take effect.
NOTE: Users will need an AcuCloud account before they can configure the module to post data to the cloud. Please contact Accuenergy Technical Support in order to get account setup. AcuCloud Reporting: Select Enable to enable the function and to further configure the settings related to AcuCloud.
Acuvim II Series - AXM WEB PUSH 11.8 SNMP The AXM-WEB-PUSH module supports the Simple Network Management Protocol (SNMP) pro- tocol for reporting the metering data to the management station. The AXM-WEB-PUSH uses a public community string for read-only access. By default the module will communicate using SNMP port 161.
Page 74
Acuvim II Series - AXM WEB PUSH Trap Enable: Select Enable so that the meter will send a message to the management station when an event is triggered. The event could be triggered by a change in Digital Input Status and alarm status. The notification can then be sent to up to 4 stations.
Acuvim II Series - AXM WEB PUSH 11.9 DNP The AXM-WEB-PUSH supports the DNP communications protocol. The Distributed Network Protocol (DNP) is an open protocol used in the electric utility industry for communication and interoperability among substation computers, Remote Terminal Units(RTUs), Intelligent Elec- tronic Devices(e.g.
Page 76
Acuvim II Series - AXM WEB PUSH Number of Unsolicited Retries: Number of retries can be selected as 0, 10 and infinite. Unsolicited response trigger Condition(Num of class # events): Enter the number of events for each class to setup the trigger point. The unsolicited response will be triggered once the number the class events reaches the configured triggering number.
Page 77
Acuvim II Series - AXM WEB PUSH V: 1.36 Revised: June. 2020 www.accuenergy.com...
Page 78
Acuvim II Series - AXM WEB PUSH DNP3 Point Configuration Users can assign certain parameters to either class 1, class 2 or class 3. The scale factor is a multiplier that can be applied to a certain parameter when viewing the readings.
Acuvim II Series - AXM WEB PUSH 11.10 Remote Access The AXM-WEB-PUSH has a remote access function. This will allows users to provide other users with remote access to the meters web interface. Users will have full functionality and access to all meter readings and settings with this function.
Page 80
Acuvim II Series - AXM WEB PUSH NOTE: The module must be rebooted in order for the remote access connection to work prop- erly. Registration Status: Displays the status as Registered or Unregistered. Remote Access Information: Lets users know if the remote access status is online or offline.
Acuvim II Series - AXM WEB PUSH 11.11 Import/Export Configuration Users can import and export settings from a Acuvim II meter by using Import/Export function. This page can be accessed by clicking on the Setting menu tab and selecting Import/Export.
Acuvim II Series - AXM WEB PUSH 11.11.1 Export Configuration The configuration file can be downloaded and saved in the computer by clicking on Export button. The exported file has the .conf.am format. 11.11.2 Import Configuration The configuration can be imported by using a .conf.am...
Acuvim II Series - AXM WEB PUSH 12. Management 12.1 Parameter Reset The Management web page allows the user to clear and reset certain parameters in the meter. The following parameters can be reset from the Management page: The web interface allows for remote initial setup of the Acuvim II meter. The AXM-WEB-PUSH web interface allows for different user access levels.
There is a diagnostic file on the AXM-WEB-PUSH module that users can download which can be used to analyze the modules diagnostics. The download diagnostic button is located at the bottom of the Management page. NOTE: Please send the log file to Accuenergy's Technical Support(support@accuenergy.com) for analysis. V: 1.36 Revised: June. 2020...
Acuvim II Series - AXM WEB PUSH 13. Network Diagnostic The network diagnostic page can be used to check the Ethernet Status, host lookup and test the connection. On the Ethernet status page, it shows the Ethernet network status, routing table, DNS server and Network stat.
Acuvim II Series - AXM WEB PUSH 13.2 Host Lookup If users have issue of AcuCloud, email or HTTP/FTP post, it may related to the internet connec- tion. To verify the connection is working, we can use the connection test here.
When using the remote server users can check to see if their firmware is running the latest firmware and update if necessary. Alternatively users can contact Accuenergy Technical Support who will then be able to provide the the latest firmware for the update, if using this method users should provide the current firmware version of the AXM-WEB-PUSH module which can be found from the Device Information page.
Page 89
Acuvim II Series - AXM WEB PUSH Once the upload was successfully uploaded users will see the following page confirming that the file was uploaded. Click Process to begin the update. The update will begin and you will see the following message: Firmware update in progress.
Acuvim II Series - AXM WEB PUSH Once the update is complete, you will see the following page. NOTE: The module is currently rebooting. This may take 1-2 minutes to complete. When com- plete, refresh the page to reconnect to the meter. You will be required to log in again.
Page 91
Acuvim II Series - AXM WEB PUSH Once the firmware has been downloaded, the updating process will begin. After the firmware update the module will reboot, this will take approximately 1-2 minutes to complete. V: 1.36 Revised: June. 2020 www.accuenergy.com...
Page 92
2 Lansing Square, Suite 700 FAX: +1-416-497-4130 Toronto, ON M2J 4P8, Canada E: marketing@accuenergy.com TF: +27 (0) 87 802 6136 ACCUENERGY SOUTH AFRICA (PTY) LTD. Castle Walk Corporate Park, Block B, Cnr. Nossob & Swakop Street Erasmuskloof, Pretoria, 0181 South Africa...
Need help?
Do you have a question about the Acuvim II Series and is the answer not in the manual?
Questions and answers