If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com. V01.00 | 2025/03 | 4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The delivery consists of the following: IP65/IP67 power supply Quick Start Guide Turck service Turck supports you in your projects — from the initial analysis right through to the commis- sioning of your application. The Turck product database at www.turck.com offers you several software tools for programming, configuring or commissioning, as well as data sheets and CAD files in many export formats.
The product is designed according to state of the art technology. Residual hazards, however, still exist. Observe the following safety instructions and warnings in order to prevent danger to persons and property. Turck accepts no liability for damage caused by failure to observe these safety instructions.
The unit's outputs are protected by internal electronic fuses (eFuse). V01.00 | 2025/03 | 8 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The DC voltage input is designed for a DC voltage range of 110…300 VDC (nominal range) for use with a battery or similar DC power source. V01.00 | 2025/03 | 9 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The outputs then start automatically one after the other at intervals of 150 ms in the sequence OUT1…OUT4. Turn Start-up delay 2 s 50 ms/DIV Fig. 5: Sequential start of outputs V01.00 | 2025/03 | 10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The RMS output current must be lower than the specified continuous output current. Continuous increased RMS current may cause thermal shutdown of the device. V01.00 | 2025/03 | 11 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
IO-Link during commissioning for example, are stored in the EEPROM of the device and are available even if the IO-Link communication fails. V01.00 | 2025/03 | 12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
TN, TT, IT delta mains systems or IT star mains systems without insulation monitoring: Use in zones of overvoltage category II up to 2000 m (6560 ft) V01.00 | 2025/03 | 13 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Malfunction or damage to the device Do not use a DC link of a frequency converter as a DC source. V01.00 | 2025/03 | 14 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Commissioning Commissioning After connecting the wires and by switching on the AC input voltage, the device automatically goes into operation. V01.00 | 2025/03 | 16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
In case of an error at the output: Press and hold the button on the output (OUT1…OUT4) for longer than 1 s to reset the output. V01.00 | 2025/03 | 17 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
All LEDs flash for 5 s to indicate that the key lock status has changed. The display returns to normal operation. V01.00 | 2025/03 | 18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Firmware revision of the device, e. g. V1.0.7.0 (23) 0x18 Application Specific Tag R/W Default "***" (24) Field for customer or application specific data V01.00 | 2025/03 | 19 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Data storage lock 0: not activated (default) 1: activated Local parameterization lock Not implemented Local user interface lock Not implemented V01.00 | 2025/03 | 20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Default values are shown in bold. Value Meaning PSU normal operation False True PSU standby Power supply in standby mode, all outputs are switched off V01.00 | 2025/03 | 21 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 22
Default values are shown in bold. Unit: V/bit Value range: 6144…7168 = 24…28 V Default value: 6272 = 24.5 V V01.00 | 2025/03 | 22 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 23
Bit order 15…8 7…0 15…8 7…0 15…8 7…0 15…8 7…0 Trip value Channel 1 Channel 2 Channel 3 Channel 4 V01.00 | 2025/03 | 23 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 24
15…8 7…0 Sub index Bit order 7…0 7…0 7…0 7…0 Trip value Channel 1 Channel 2 Channel 3 Channel 4 V01.00 | 2025/03 | 24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The power supply is not switched on: AC input voltage too low Orange flashing Output switched off and in Hiccup Plus mode (18 s) V01.00 | 2025/03 | 25 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 26
The device has switched off due to overtemperature. As soon as the tem- perature reaches the normal operating range, the output switches on again and the STATUS LED lights up permanently green. V01.00 | 2025/03 | 26 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 27
The deviations of the internal output current sensors exceed the permissible limits. Temperature sensor measurement out of range (-40 °C or +150 °C for more than 5 s). V01.00 | 2025/03 | 27 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 28
0: OK eFuse ch2, 1: tripped, short-circuit at output short-circuit state eFuse ch3, short-circuit state eFuse ch4, short-circuit state V01.00 | 2025/03 | 28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 30
15…12 3: Temperature trip 4: Power budget trip 5: Installation failure trip 6: Sensor fault trip 7: Fatal fault trip V01.00 | 2025/03 | 30 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 31
Ch1 eFuse number of 47… overcurrents Ch2 eFuse number of 31… overcurrents Ch3 eFuse number of 15…0 overcurrents Ch4 V01.00 | 2025/03 | 31 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The temperature in the device is too high. temperature exceeded 0x6320 Parameter error Error The parameter settings of the device are invalid. V01.00 | 2025/03 | 33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type. V01.00 | 2025/03 | 35 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Disposal The devices must be disposed of properly and do not belong in the domestic waste. V01.00 | 2025/03 | 36 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
100 VAC typ. 0.99, at 360 W typ. 0.99, at 360 W 120 VAC typ. 0.97, at 360 W 230 VAC V01.00 | 2025/03 | 37 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 38
120 Vac 0.90 230 Vac 0.85 0.80 0.75 0.70 Fig. 15: power factor vs. output power (at 24 VDC output voltage) V01.00 | 2025/03 | 38 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Do not connect outputs or devices in parallel. Back-feeding loads Max. 35 V/4 J For all outputs together, even when switched off V01.00 | 2025/03 | 39 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 40
Fig. 17: Derating, output power vs. ambient temperature *Atmospheric pressure T<45 °C T<55 °C 2000 5000 Altidue (m) AP* (kPa) Fig. 18: Derating, output power vs. altitude V01.00 | 2025/03 | 40 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
IO-Link version V1.1 Baud rate COM3 (230.4 kBaud) Cycle Time 2 ms SIO Mode Supported Process data length 23 byte V01.00 | 2025/03 | 41 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
30 g 6 ms, 20 g: 11 ms According to IEC 60068-2-27 3 bumps per direction, 18 bumps in total LABS compatibility V01.00 | 2025/03 | 42 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 43
Derating, standard mounting orientation Other mounting orientations: max. output power 300 W T/°C Fig. 21: Derating, standard mounting orientation V01.00 | 2025/03 | 43 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Via San Domenico 5, IT-20008 Bareggio (MI) www.turckbanner.it Japan TURCK Japan Corporation ISM Akihabara 1F, 1-24-2, Taito, Taito-ku, 110-0016 Tokyo www.turck.jp V01.00 | 2025/03 | 44 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 45
United Kingdom TURCK BANNER LIMITED Blenheim House, Hurricane Way, GB-SS11 8YT Wickford, Essex www.turckbanner.co.uk Turck Inc. 3000 Campus Drive, USA-MN 55441 Minneapolis www.turck.us V01.00 | 2025/03 | 45 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 46
Over 30 subsidiaries and 60 representations worldwide! 100049091 | 2025/03 100049091 www.turck.com...
Need help?
Do you have a question about the PSU67-1P-1M-2M4-24150-IOL-F and is the answer not in the manual?
Questions and answers