PSU67-1P-1S-2L-24150-IOL-F
Smart switching power
supply in IP65/IP67
Instructions for Use

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSU67-1P-1S-2L-24150-IOL-F and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for turck PSU67-1P-1S-2L-24150-IOL-F

  • Page 1 PSU67-1P-1S-2L-24150-IOL-F Smart switching power supply in IP65/IP67 Instructions for Use...
  • Page 2: Table Of Contents

    8.2.3 Index 0x02: System commands (according to IO-Link specification)...... 19 8.2.4 Index 0x0C: Device Access Locks.....................  19 8.2.5 Parameters............................ 20 V01.00 | 2023/06 | 2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 3 Efficiency and power losses .................. 37 13.5 IO-Link interface...................... 38 13.6 General technical data .................... 38 14 Turck branches — contact data .................... 42 V01.00 | 2023/06 | 3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 4: About These Instructions

    If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com. V01.00 | 2023/06 | 4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 5: Notes On The Product

    The delivery consists of the following: IP65/IP67 power supply Quick Start Guide Turck service Turck supports you in your projects – from the initial analysis right through to the commission- ing of your application. The Turck product database at www.turck.com offers you several soft- ware tools for programming, configuring or commissioning, as well as data sheets and CAD files in many export formats.
  • Page 6: For Your Safety

    The product is designed according to state of the art technology. Residual hazards, however, still exist. Observe the following safety instructions and warnings in order to prevent danger to persons and property. Turck accepts no liability for damage caused by failure to observe these safety instructions.
  • Page 7: Product Description

    Out 1 Out 2 Switchable Fuse Output Input Filter Out 3 Rectifier Inrush Current Out 4 Limiter Fig. 2: Block diagram V01.00 | 2023/06 | 7 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 8: Operating Elements

    The inrush current is usually lower than the permanent input current. V01.00 | 2023/06 | 8 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 9: Dc Voltage Input

    The lower output in each case remains switched on to prevent voltage dips and to output current continuously. V01.00 | 2023/06 | 9 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 10 Output load Hold-up time Typ. 75 ms 150 W Min. 56 ms Typ. 44 ms 300 W Min. 29 ms V01.00 | 2023/06 | 10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 11: Io-Link Interface

    Link during commissioning for example, are stored in the EEPROM of the device and are avail- able even if the IO-Link communication fails. V01.00 | 2023/06 | 11 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 12: Installing

    TN, TT, IT delta mains systems or IT star mains systems without insulation monitoring: Use in zones of overvoltage category II up to 2000 m (6560 ft) V01.00 | 2023/06 | 12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 13: Connecting

    Malfunction or damage to the device „ Do not use a DC link of a frequency converter as a DC source. V01.00 | 2023/06 | 13 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 14: Connecting The Dc Output Voltage Side

    1 = 24 VDC 2 = n.c. 3 = GND 4 = C/Q (IO-Link) 5 = n.c. Fig. 11: Pin assignment, IO-Link interface (X0) V01.00 | 2023/06 | 14 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 15: Commissioning

    Commissioning Commissioning After connecting the wires and by switching on the AC input voltage, the device automatically goes into operation. V01.00 | 2023/06 | 15 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 16: Setting

    In case of an error at the output: „ Press and hold the button on the output (OUT1…OUT4) for longer than 1 s to reset the output. V01.00 | 2023/06 | 16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 17: Activating And Deactivating The Button Lock

    All LEDs flash for 5 s to indicate that the key lock status has changed. The display returns to normal operation. V01.00 | 2023/06 | 17 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 18: Setting The Device Via Io-Link

    Firmware revision of the device, e. g. V1.0.7.0 (23) 0x18 Application Specific Tag Default "***" (24) Field for customer or application specific data V01.00 | 2023/06 | 18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 19: Index 0X02: System Commands (According To Io-Link Specification)

    Data storage lock 0: not activated (default) 1: activated Local parameterization lock Not implemented Local user interface lock Not implemented V01.00 | 2023/06 | 19 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 20: Parameters

    Default values are shown in bold. Value Meaning PSU normal operation False True PSU standby Power supply in standby mode, all outputs are switched off V01.00 | 2023/06 | 20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 21 Default values are shown in bold. Unit: V/bit Value range: 6144…7168 = 24…28 V Default value: 6272 = 24.5 V V01.00 | 2023/06 | 21 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 22 Bit order 15…8 7…0 15…8 7…0 15…8 7…0 15…8 7…0 Trip value Channel 1 Channel 2 Channel 3 Channel 4 V01.00 | 2023/06 | 22 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 23 15…8 7…0 Sub index Bit order 7…0 7…0 7…0 7…0 Trip value Channel 1 Channel 2 Channel 3 Channel 4 V01.00 | 2023/06 | 23 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 24: Operating

    ] buttons until OUT1 or OUT4 is skipped. When all channel LEDs are off, the unit is back in normal mode for monitoring the total output power. V01.00 | 2023/06 | 24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 25: Led Displays

    The eFuse at the output has tripped. The output has switched off. „ Press pushbutton at the output(OUT1…OUT4) to restart the channel. V01.00 | 2023/06 | 25 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 26 The deviations of the internal output current sensors exceed the per- missible limits. Temperature sensor measurement out of range (-40 °C or +150 °C for more than 5 s). V01.00 | 2023/06 | 26 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 27: Process Data (Cyclic Io-Link Data)

    1: tripped, short-circuit at output circuit state eFuse ch3, short- circuit state eFuse ch4, short- circuit state V01.00 | 2023/06 | 27 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 28: Diagnostic And Status Messages (Acyclic Io-Link Data)

    0x42 (66) 0 UINT8 0…7 Current load: 0: < 5 % 1: > 5 % 2: > 25 % 3: > 50 % 4: > 75 % V01.00 | 2023/06 | 28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 29 15…12 3: Temperature trip 4: Power budget trip 5: Installation failure trip 6: Sensor fault trip 7: Fatal fault trip V01.00 | 2023/06 | 29 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 30 Ch1 eFuse number of 47…32 overcurrents Ch2 eFuse number of 31…16 overcurrents Ch3 eFuse number of 15…0 overcurrents Ch4 V01.00 | 2023/06 | 30 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 31 The eFuse for the channel has tripped due to overcur- rent. 0x1841 eFuse tripped ch 2 Warning 0x1842 eFuse tripped ch 3 Warning 0x1843 eFuse tripped ch 4 Warning V01.00 | 2023/06 | 31 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 32: Io-Link Error Codes

    0x8041 Inconsistent parameter set Parameters inconsistent, device plausibility check failed 0x8082 Application not ready Device not ready, access denied V01.00 | 2023/06 | 32 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 33: Maintenance

    Disposal The devices must be disposed of properly and do not belong in the domestic waste. V01.00 | 2023/06 | 33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 34: Technical Data

    100 VAC Typ. 0.99, at 360 W Typ. 0.99, at 360 W 120 VAC Typ. 0.97, at 360 W 230 VAC V01.00 | 2023/06 | 34 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 35 120 Vac 0.90 230 Vac 0.85 0.80 0.75 0.70 Fig. 15: Power factor vs. output power (at 24 VDC output voltage) V01.00 | 2023/06 | 35 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 36: Dc Input

    Do not connect outputs or devices in parallel. Back-feeding loads Max. 35 V/4 J For all outputs together, even when switched off V01.00 | 2023/06 | 36 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 37: Efficiency And Power Losses

    Typ. 10.0 W Typ. 8.3 W At 24 VDC, 150 W (no load) Typ. 20.5 W Typ. 18.2 W Typ. 16.2 W At 24 VDC, 300 W (full load) V01.00 | 2023/06 | 37 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 38: Io-Link Interface

    MTBF SN 29300, IEC 61709 100 VAC 120 VAC 230 VAC At 24 V, 300 W, 40 °C 270000 h 305000 h 384000 h V01.00 | 2023/06 | 38 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 39 For TN, TT, IT Delta mains sys- tems or IT star mains systems without insulation monitoring for altitudes up to 2000 m V01.00 | 2023/06 | 39 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 40 Derating, standard mounting orientation Other mounting orientations: max. output power 300 W V01.00 | 2023/06 | 40 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 41 Technical data General technical data T/°C Fig. 21: Derating, standard mounting orientation V01.00 | 2023/06 | 41 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 42: Turck Branches - Contact Data

    Via San Domenico 5, IT-20008 Bareggio (MI) www.turckbanner.it Japan TURCK Japan Corporation ISM Akihabara 1F, 1-24-2, Taito, Taito-ku, 110-0016 Tokyo www.turck.jp V01.00 | 2023/06 | 42 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 43 United Kingdom TURCK BANNER LIMITED Blenheim House, Hurricane Way, GB-SS11 8YT Wickford, Essex www.turckbanner.co.uk Turck Inc. 3000 Campus Drive, USA-MN 55441 Minneapolis www.turck.us V01.00 | 2023/06 | 43 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 44 Over 30 subsidiaries and 60 representations worldwide! 100045318 | 2023/06 100045318 www.turck.com...