The scope of delivery includes: IP65/IP67 power supply Quick Start Guide Turck service Turck supports you with your projects, from initial analysis to the commissioning of your applic- ation. The Turck product database under www.turck.com contains software tools for program- ming, configuration or commissioning, data sheets and CAD files in numerous export formats.
The product is designed according to state-of-the-art technology. However, residual risks still exist. Observe the following warnings and safety notices to prevent damage to persons and property. Turck accepts no liability for damage caused by failure to observe these warning and safety notices.
Operator interface (LEDs and buttons) Functional principle The device converts an AC input voltage of 320…550 VAC into a 24 VDC output voltage. V01.00 | 2023/01 | 8 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If an external fuse is used, type B or C circuit breakers of at least 6 A have to be used to prevent unwanted tripping of the circuit breaker. V01.00 | 2023/01 | 9 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 10
Such use is not included in the approval according to UL 61010 and IEC 62368. PSU67 open Fig. 4: 2-phase operation /VAC Fig. 5: Performance in 2-phase operation V01.00 | 2023/01 | 10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Fig. 6: Hold-up time vs. input voltage L1 L2 L3 Input Voltage -5 % Output Voltage Hold-up Time Fig. 7: Shutdown behavior V01.00 | 2023/01 | 11 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Link during commissioning for example, are stored in the EEPROM of the device and are avail- able even if the IO-Link communication fails. V01.00 | 2023/01 | 12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
TN, TT, IT delta mains systems or IT star mains systems without insulation monitoring: Use in zones of overvoltage category II up to 2000 m (6560 ft) V01.00 | 2023/01 | 13 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Commissioning Commissioning After connecting the wires and by switching on the AC input voltage, the device automatically goes into operation. V01.00 | 2023/01 | 15 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
All LEDs flash for 5 s to indicate that the key lock status has changed. The display returns to normal operation. V01.00 | 2023/01 | 16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Firmware revision of the device, e. g. V1.0.7.0 (23) 0x18 Application Specific Tag Default "***" (24) Field for customer or application specific data V01.00 | 2023/01 | 17 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Actual output total current A/bit UINT16 Total output current (actual value) Actual output voltage 1 V/bit UINT16 Actual Output Voltage V01.00 | 2023/01 | 21 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 23
Uptime since last 0x53 Parameter access via sub index 0 only turn-on (83) Hours UINT32 39…8 Hours UINT8 7…0 Value range: 0…59 V01.00 | 2023/01 | 23 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 24
The temperature in the device is too high. perature exceeded 0x6320 Parameter error Error The parameter settings of the device are invalid. V01.00 | 2023/01 | 24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Observe our return acceptance conditions when returning the device to Turck. 11.1 Returning devices Returns to Turck can only be accepted if the device has been equipped with a Decontamination declaration enclosed. The decontamination declaration can be downloaded from https://www.turck.de/en/retoure-service-6079.php and must be completely filled in, and affixed securely and weather-proof to the outside of the packaging.
3 AC, 480 V typ. 0.95, at 500 W AC Input Range /VAC Fig. 11: Voltage range – input voltage AC V01.00 | 2023/01 | 27 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 28
0.90 0.85 3 × 480 Vac 0.80 0.75 0.70 Fig. 14: Power factor vs. output power (at 24 VDC output voltage) V01.00 | 2023/01 | 28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
IO-Link version V1.1 Baud rate COM3 (230.4 kBaud) Cycle Time 2 ms SIO Mode Supported Process data length 23 byte V01.00 | 2023/01 | 31 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
S. fig.: Output power vs. ambi- ent temperature [} 29] Altitude Max. 5000 m (16 400 ft) S. fig.: Output power vs. alti- tude [} 29] V01.00 | 2023/01 | 32 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 33
Max. 32.5 VDC redundant circuit limits the maximum output voltage. The output shuts down and auto- matically attempts to restart. V01.00 | 2023/01 | 33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 34
350 W at max. 60 °C - 25 + 45 + 55 + 70 T/°C Fig. 21: Derating – standard mounting orientation V01.00 | 2023/01 | 34 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...