Page 1
VARIABLE CAPACITY COMMERCIAL 72 - 96kW Indoor (R-410A Series) Installation and Commissioning Guide Model Numbers EVA720T EVA850T EVA960T IMPORTANT NOTE: Please read this manual carefully before installing or operating your air conditioning unit.
Check your air conditioning unit and all items against the invoice upon receiving your shipment. Inspect the unit, components and accessories for any sign of damage. If there is any damage to the unit, contact ActronAir Customer Care Department immediately on: 1300 522 722 to obtain a Goods Return Number.
Variable Capacity Installation and Commissioning Guide Safety Instructions • Only licensed HVAC technicians* should install and service air conditioning equipment. Improper service or alteration by an unqualified technician could result in significant and major damage to the product or property which may render your warranty null and void.
Installation and Commissioning Guide Components Overview Indoor Unit Components Overview NOTES: Drawing is subject to change without notice. Drawing for illustration purposes only (may vary depending on capacity) EVA720T has a single fan configuration TOP PANEL HEAT EXCHANGER INTERNAL ACCESS PANEL...
Variable Capacity Installation and Commissioning Guide Unit Dimensions and Clearance EVA720T 8012-665-01 Unit Dim 72kW ID Catalogue 20230120 2440 O/A STG1 LIQ Ø15.9(5/8") SWAGED STG1 GAS Ø28.6(1-1/8") SWAGED STG1 LIQ Ø15.9(5/8") SWAGED 1123 STG1 GAS Ø28.6(1-1/8") SWAGED 1982 DETAIL P...
1000 mm between the units or between the unit and the outside perimeter is available. 3. Minimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
Compliance and consultation with the authorities having jurisdiction with the installation of this equipment is the responsibility of the installer. ActronAir will not be held liable for any damages or costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit Installation and Commissioning Guide for further information and details.
Page 10
NOTE This indoor unit is designed to match only with an ActronAir Series outdoor unit as specified in the Technical Selection Catalogue. The unit is supplied with factory charged dry air. Be aware of the pressurised air charge when purging. Remove the caps from the connection points and purge the system only when the field pipe connections are ready to be completed.
Variable Capacity Installation and Commissioning Guide WH&S regulations must be observed and will take Unit Lifting Instructions precedent during lifting process. Connect the loop ends NOTE RUBBER PADS: of slings into shackle All drawings are for illustration purposes only. Actual Provide rubber pads to prevent unit may vary depending on the model.
FLAT PATTERN 0.5 / m TUBE ENDS MUST BE ROUND AND OF FULL DIAMETER. FOLD 0.5 / m ActronAir Pty Ltd This drawing always remains the See Notes See Notes ANGLES & SQUARENESS TUBE MUST BE CLEAN AND FREE FROM...
Variable Capacity Installation and Commissioning Guide Suggested Drain Trap Details The top of the Vent must be The top of the Trap must be 125mm Evaporator 50mm higher than the top of below the top of the Evaporator Condensate Tray the Evaporator Condensate Tray Drain Connection 50mm...
Variable Capacity Installation and Commissioning Guide Electrical Installation All electrical work must be carried out by a qualified technician. Make sure all wiring is in accordance with local wiring rules. Wiring connections should be made in accordance with the wiring diagram provided in accordance with the latest edition of the AS/NZS 3000 “Australian / New Zealand Wiring Rules”.
Variable Capacity Installation and Commissioning Guide Electrical Connection NOTES • To minimise noise interference, Data and Power cable clearance should be maintained as much as possible. • All drawings are for illustration purposes only. Actual unit may vary depending on the model. •...
Variable Capacity Installation and Commissioning Guide Data Cable Shielding Instructions 2 Core Twisted (ActronAir Part Number: AEDC2) NOTES • Maintain the twist of the core wires up to the Green Terminal Plug. • Maximum strip length of outer insulation to the Green Terminal Plug is 50mm.
Variable Capacity Installation and Commissioning Guide Wall Controller Options Wall Controller Options A maximum of three (3) wall controllers in the below combinations is allowed per unit. See below table. Wall Controllers Options 1st Option 2nd Option 3rd Option LC7-2 4th Option LC7-2 5th Option...
Variable Capacity Installation and Commissioning Guide Wiring Configuration : Recommended NOTES • Diagram shown below is a general representation only. Refer to individual unit wiring diagram for complete wiring connection details. • Long runs beside Mains cables or TV antenna cables should be avoided. •...
Variable Capacity Installation and Commissioning Guide Wiring Configuration : Alternate LC7-2 WALL CONTROL LC7-2 WALL CONTROL LC7-2 WALL CONTROL (OPTIONAL) (OPTIONAL) (OPTIONAL) INDOOR UNIT OUTDOOR UNIT LM-RS (OPTIONAL) DATA CONTROL AERSS CABLE (OPTIONAL) NOTES • Diagram shown above is a general representation only. Refer to individual unit wiring diagram for complete wiring connection details.
VARIABLE CAPACITY Installation and Commissioning Guide Accessing Service and Technical via NEO Special options are available via Advance Option menu. This must be accessed through Service and Technical section. Follow the steps as shown below: To access the Menu, touch on the hamburger icon ( ) on the NEO Controller.
Page 27
VARIABLE CAPACITY Installation and Commissioning Guide 4. The Service & Technical Section screen is as below: Installation and Commissioning Guide - Variable Capacity Commercial Package Ducted Units 72-96kW (R-410A Series) Doc. No. 0525-122 Ver. 9 241220...
VARIABLE CAPACITY Installation and Commissioning Guide After Hours Logic with Timeclock (Scheduler) After Hours is the duration (in minutes) in which the unit will turn ON when the After Hours is set. By default, this is set to 0 min. The Minimum Settable Value is 1 min and the Maximum Settable Value is 120 mins. Setting this will be accessible via Service &...
Page 29
VARIABLE CAPACITY Installation and Commissioning Guide 4. Activate the After Hours Mode by tapping on the check box. Tap on the check box 5. Make necessary changes as the settings will be automatically saved. Touch on the Home button on the top right corner to go back to the Home screen.
Page 30
VARIABLE CAPACITY Installation and Commissioning Guide 7. To view the new setting of the After Hours Mode, touch the Menu button on the Home screen. Tap on the Menu 8. Select the After Hours and the new settings will appear. Tap on After Hours Installation and Commissioning Guide - Variable Capacity Commercial Package Ducted Units 72-96kW (R-410A Series)
Variable Capacity Installation and Commissioning Guide Filter Alarm Configuration This gives the user an option to Enable and set the Air Filter Alarm . The setting is accessible via Service & Technical menu. Filter Alarm Configuration The filter timer can be set via the Control Interface as follow: 1.
Variable Capacity Installation and Commissioning Guide Indoor Drain Pan Overflow Sensor In a typical air conditioning setup, the drain pan serves a vital function by gathering and expelling water from the unit. This pan is typically linked to gravity-fed drain traps, commonly referred to as P-traps. These P-traps need to be carefully designed to match the specific negative pressure of the application to ensure proper functionality and effective drainage of condensate from the unit.
Page 33
3 minutes to automatically reset the error code. If the issue persists, it is suggested to inspect the overflow sensor as per the wiring diagram or get in touch with ActronAir support team at 1300 522 722.
Variable Capacity Installation and Commissioning Guide Maintenance Maintenance Procedures This section describes the procedures that must be performed as a part of normal maintenance program. Regular servicing of equipment by licensed technician is highly recommended. Regular servicing of your unit helps in maintaining its optimum performance and reliability.
Page 35
Variable Capacity Installation and Commissioning Guide WARNING Do Not Use High Alkaline Detergent! When using detergent for coil cleaning, ensure that the alkaline level is no higher than 8.5, which can cause corrosion damage to the coils. DANGER No Water into the Electrical Compartments! Ensure consideration is given to the possibility of water entering the electrical compartments during cleaning of the condenser coil.
Variable Capacity Installation and Commissioning Guide Maintenance Frequency Checklist Regular servicing of equipment by a qualified technician is recommended every 12 months for residential applications and every quarter for commercial applications. Regular servicing of your unit helps in maintaining its optimum performance and reliability.
Variable Capacity Installation and Commissioning Guide Start Up and Commissioning Report INSTALLATION INFORMATION Name: Tel. Number: CUSTOMER Address: Name: Tel. Number: INSTALLER Address: Site Address: Date Installed: Model: Serial Number: CIRCUIT TEMPERATURE SETTINGS Supply Air Temperature Return Air Temperature Suction Temperature Discharge Temperature Condenser Coil Temperature Ambient Temperature...
Variable Capacity Installation and Commissioning Guide Version History DOCUMENT VERSION BOM VERSION UPDATE HISTORY Ver 1 -0100 Released Ver 2 -0100 Included lower capacity models Ver 3 -0100 Phase 2 Ver 4 -0100 Included Neo Wall Controller Options Ver 5 -0100 Added Safety Precautions Information;...