Purpose
The dual-channel, programmable PCZ-526.4 control timer is
used for switching on and off lighting or other electrical applian-
ces in accordance with sunset and sunrise times, with the possi-
bility of programming a night break, i.e. temporary switching off
of appliances to save energy.
F&F Filipowski L.P.
Konstantynowska 79/81, 95-200 Pabianice, POLAND
phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71
www.fif.com.pl; e-mail: biuro@fif.com.pl
- 1 -

Advertisement

loading
Need help?

Need help?

Do you have a question about the PCZ-526.4 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for F&F PCZ-526.4

  • Page 1 Electro thrown in the trash or abandoned in nature, pose a threat to the environment and human health. Purpose The dual-channel, programmable PCZ-526.4 control timer is used for switching on and off lighting or other electrical applian- ces in accordance with sunset and sunrise times, with the possi- bility of programming a night break, i.e.
  • Page 2 Features » Based on information about the current date and the geo- graphical coordinates of its location, the astronomical timer automatically determines the daily programmed switch-on and switch-off points for the lighting. The exact switch-on and switch-off times are determined by calculating the position of the sun relative to the horizon.
  • Page 3 » Display contrast correction capability for clear LCD readouts for different viewing angles. Functioning Działanie The PCZ-526.4 timer controller can operate in one of three modes: » Automatic mode Automatic operation according to programmable switch-on and switch-off points of the contact.
  • Page 4 In semi-automatic mode, the contact position is oppo- site to that resulting from the programme cycle (i.e. the contact is off at night and on during the day). Semi- automatic operation only works until the end of the current automatic operation cycle, e.g. entering semi- -automatic mode during the day will switch the light on until the programmed switch-on time resulting from the astronomical cycle occurs.
  • Page 5 Display description Manual The full manual for the PCZ-526.4 timer can be down- loaded from www.fif.com.pl from the product sub-page or via the QR code below: - 5 -...
  • Page 6 Mobile app The control application is available free of charge in the App Store and Google Play: The NFC connection uses very short-range communica- tion, which means that you need to directly touch the phone to the front of the programmed controller. - 6 -...
  • Page 7 Working mode indication Display Mode Relay status Automatic Automatic Semi-automatic Semi-automatic Manual Manual Legend: Blinks/pulses - 7 -...
  • Page 8 Control buttons Button Description Pressing the button enters the controller’s configuration mode. In parameter edit mode, pressing Menu will MENU drop the parameter being edited (without storing the changes made) and return to the parent menu level. In edit mode, pressing the button moves to edit the next setting item.
  • Page 9 Control buttons cont. Button Description In automatic mode, when the button is pres- sed, the relay switches to the opposite state and transitions to a semi-automatic state. In edit mode, pressing the button increases the value of the edited parameter by 1. If the (Up) button is pressed for a long time, the value of the parameter will cyclically increase by 1.
  • Page 10 Mounting 1. Turn off the power. 2. Install the timer on the rail in the distribution box. 3. Connect the power cables according to the diagram. 4. Connect receivers according to the diagram. 5. Set the correct date and time. 6.
  • Page 11 Wiring diagram relay – COM1 common contact relay – COM2 common contact L power supply N power supply relay 1 – NO1 contact (normally open) relay 1 – NC1 contact (normally closed) relay 2 – NO2 contact (normally open) relay 2 – NC2 contact (normally closed) - 11 -...
  • Page 12 Technical data power supply 24÷264 V AC/DC maximum load current (AC-1) 2×16 A contact separated 2×NO/NC backup time timer operation 6 years* battery type 2032 (lithium) backup time display operation none accuracy of the timer error time ±1 s/ 24 h power consumption 1.5 W terminal...
  • Page 13 Warranty The F&F products are covered by a warranty of the 24 months from the date of purchase. Effective only with proof of purchase. Contact your dealer or directly with us. CE declaration F&F Filipowski L.P. declares that the device is in conformity with the essential requirements of Directive 2014/53/EU of the European Parliament and of the Council of 16 April 2014 on the harmonization of the laws of the Member States relating to the...