Purpose
Staircase timer AS-224 serves to keep switch-ON lighting of stair-
case, corridor, or any other object for the set time and to switch-
OFF this lighting automatically, upon elapse of this set time.
Functioning
Turned ON staircase timer supports the lighting during set time
by potentiometer (from 0.5 min. to 10 min.) and upon elapse of
this set time a reduction by half of lighting brightness follows
for about 30 seconds, after that OFF follows (thus an occurrence
of a sudden darkness is avoided, enabling safe approach to the
switch). After switching OFF the lighting there is possibility to
switch it ON again. Function of counter blockade does not allow
to keep the light-ON in case of staircase switch blocking (after
blocking the pushbutton, for example by match, the timer will
count the set time and switch OFF the lighting). Next switching
ON can be after removing the blockade.
F&F Filipowski sp. j.
Konstantynowska 79/81, 95-200 Pabianice, POLAND
phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71
www.fif.com.pl; e-mail: biuro@fif.com.pl
- 1 -

Advertisement

loading

Summary of Contents for F&F AS-224

  • Page 1 Electro thrown in the trash or abandoned in nature, pose a threat to the environment and human health. Purpose Staircase timer AS-224 serves to keep switch-ON lighting of stair- case, corridor, or any other object for the set time and to switch- OFF this lighting automatically, upon elapse of this set time.
  • Page 2 Mounting 1. Take OFF the power. 2. Put on the relay on the rail in switchgear box. 3. Connect the power cable to terminals 1-3 in accordance with markings. 4. Timer switches which were connect with parallel, connect to terminal 6 and to cable which is connecting to terminal 3. 5.
  • Page 3 AS-224 can’t work with backlit buttons. power supply relay’s power supply 21÷27 V AC/DC control inputs control input contact output – COM power supply contact output – closing contact (active) Technial data power supply 21÷27 V AC/DC maximum load current (AC-1)
  • Page 4 Power table supply tungsten halogen fluorescent energy-saving 230 V 2000 W 1250 W 1000 W 500 W 250 W 24 V 350 W 200 W – – 150 W The above data are indicative and will heavily depend on the design of a specific receiver (that is especially important for LED bulbs, energy-saving lamps, electronic transformers and pulse power supply units), switching frequency and operating conditions.