SenseAir aSENSE RL Installation Manual

Co2 / temperature transmitter for mounting in ventilation ducts

Advertisement

Quick Links

Gas and Air Sensors
aSENSE Duct Conduit RL
CO
/ temperature transmitter for mounting in
2
1
1 Sampling probe
2 Sealing gasket
3 Largest locking nob
4 2 washers
5 2 screws
Installation Manual
ventilation ducts
2
3
4
5
6
6 O-ring 29,2x3,53 (Factory supplied mounted in box)
7 PCB (Factory supplied mounted in box)
8 Snap-in lid
9 Set screw conduit connector
10 Temperature sensor
1
9
10
Document
IMA 259
2
7
8
Rev
Page
3
1 (5)

Advertisement

loading
Need help?

Need help?

Do you have a question about the aSENSE RL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SenseAir aSENSE RL

  • Page 1 Gas and Air Sensors Installation Manual aSENSE Duct Conduit RL / temperature transmitter for mounting in ventilation ducts 1 Sampling probe 6 O-ring 29,2x3,53 (Factory supplied mounted in box) 2 Sealing gasket 7 PCB (Factory supplied mounted in box) 3 Largest locking nob 8 Snap-in lid 4 2 washers 9 Set screw conduit connector...
  • Page 2: Mounting Instruction

    Mounting of aSENSE on to the duct. Hole with 25 mm diameter Temperature sensor with 135 mm cable mounted in the sampling probe Mounting Instruction Since there might be a substantial pressure difference in duct mounting applications, it is essential to avoid ambient air from suction into the duct mounting box. For correct function it is indispensable that the sealing of the box cover, the cable entry bushings, the cable feed through and the duct entrance are absolutely tight.
  • Page 3 3) Electrical cable entry: The box has a factory mounted set screw conduit connector. Place the cable into the foam plug. Insert the foam plug from below until it stops. Insert the EMT into the connector until it stops and tighten the screw.
  • Page 4: Electrical Connections

    If the analogue output is connected to a controller the same ground reference has to be used for the aSENSE RL unit and for the control system! Unless different transformers are used, special precautions need to be taken.
  • Page 5 Terminals and jumpers on aSENSE The darker positions are default settings. Dimensions Document Page IMA 259 5 (5)