User Manual tSENSE VAV Disp -, temperature- and relative humidity transmitter General tSENSE VAV for wall mounting measures indoor air carbon dioxide concentration, temperature and relative humidity in rooms. tSENSE VAV is available with colour touch display (LCD). The unit connects to Direct Digital Control (DDC).
Opening of housing Download of software UIP5 senseair.se/products/software/uip-5/ Figure 2: Connection to PC via phone jack Connect Interface cable USB – 3.5mm, Art. No.: 00-0-0070 Figure 1 Enter PIN code ⓿ Power ON byt bild PIN1 Access to display settings. Delivered product: Code Off PIN2 Access to meter settings.
The sensor is supplied with 0 ─ 10VDC linear analogue outputs for Out(1), Out(2) and Out(3) (see Table 1). Alternative output ranges can be configured via touch display and/or PC software UIP (version 5 or later). See information at senseair.com. Outputs Out1/Out2/Out3 ❸...
Page 5
e.g. The voltage level of OUT1 is the result of the largest demand from Proportional-bands. Out1_a/Out1_b/Out1_c => OUT1 The voltage level of the one of Out1_a, Out1_b or Out1_c which has the highest voltage level provides the voltage level of OUT1. The values below are defalt values.
Select source There are eight sources to choose among: CO (Ch0), Temp. (Ch1), Relative Humidity (Ch2) and Ch3 to 7 (contains no data) plus the Disable-button. ❼ ❽ ❾ ❿ Source ❶ ❷ UIP5 Source: CO selected Save Types Analogue/Analogue Invert (Analogue Invert is usable e.g. temp. protection page 6) ❼...
Low value can be changed, in steps of 100ppm, from 0ppm to set High value minus 100ppm. High value can be changed, in steps of 100ppm, from set Low value plus 100ppm. ─ (SenseAir guarantiees accuracy ±30ppm ±3% of reading, in the measurement range 0 2000ppm). Temperature:...
Communication settings Protocol When the sensors RS-485 Protocol parameter is set to “Auto”, the sensor selects protocol depending on the protocol used on the network it is connected to. After power on, the sensor then listens to the traffic on the RS-485 network.
Address/Baudrate Address can be changed from 1 to 253 Baudrate can be choosen as either 9600, 19200, 38400, 57600, 76800 or 115200 ❺ ❻ ❼ ❽ RS-485 ❾ ❶ ❷ ❸ NOTE! UIP5 Address ❶ ❷ ❸ UIP Baudrate Misc NOTE! UIP baudrate ≠...
Page 12
Connect meter ❶ ❷ ❸ Information Dokument Edition UMA0187 12 (26)
Check for updates ❶ ❷ ❷ New version available No new version ❷ ❸ ❹ New database downloaded Connection configurations ❶ ❷ ❸ ❹ ModBus COM13-USB Serial Port Save ❺ ❻ Lower right corner of screen NOTE! UIP baudrate ≠ RS-485 baudrate if tSENSE VAV is connected via phone jack (see fig.
Display settings Limits /(Temperature)/(Humidity) Yellow/Red limit (Temp./Humidity same method as for CO limit settings) Yellow limit can be changed, in steps of 100ppm, from 0ppm to set Red limit minus 100ppm. Red limit can be changed, in steps of 100ppm, from set Yellow limit plus 100ppm. Temperature: Yellow limit can be changed, in steps of 1 C (1.8...
Screen settings ❶ ❷ Brightness Brightness can be changed, in steps of 2%, from 0% to 10%, in steps of 10%, from 10% to 100% Energy save brightness can be changed, in steps of 2%, from 0% to 10%, in steps of 10%, from 10% to 40% ❸...
Toggle (Time and CO and/or Temperature and/or Humidity Toggle time Toggle time can be changed, in steps of 1s, from 1s to 99s. ❸ ❹ ❺ ❻ ❼ ❽ ❾ ❿ ⓫ ⓬ ⓭ Toggle CO and/or Temperature and/or Humidity ❸...
Calibration options CO Zero cal/Background/Target cal (Same display procedure for the three options. See Note!) ❹ ❺ ❻ ❼ ❽ ❾ ❿ ⓫ UIP: If reference meter shows e.g. CO -value 500ppm set Target to 500 Background calibration button ❷ Green LED blinks twice ❶...
Target Calibration (Background CO level): default value is 400ppm. e.g. The ABC requires that the sensor is exposed to fresh air (at background level of CO at least once per ABC period). If sensor is operated in environments that never reaches the background level, it might still be possible to benefit from ABC function by adjusting target level.
ABC period (ABC target / Altitude / Restore cal) (Same display procedure for the four options See Note!) ❺ ❻ ❼ ❽ See NOTE! ❾ ❿ ⓫ ⓬ 180, 181, 240hours Save ⓭ ❶❹ UIP5 NOTE! The ABC period is default set to 180 hours, which means that the sensor will make an adjustment once a week.
Automatic system test A full system test is executed automatically at every power-up. Sensor probes are checked constantly during operation against failure by checking valid dynamic measurement ranges. System checks returns error bytes to RAM. Error codes are available by connecting the sensors to a PC with a special USB cable (art.No.
Error codes and action plans Error symbol (a wrench appears when one or several error codes are active) Bit # Error code Error description Suggested action sensor No ability to communicate Try to restart sensor by power Com. error with CO2 sensor module. OFF/ON.
CO calibrations, unless some special situations have occurred. Software can be downloaded free at senseair.com. USB-cable and zero calibration kit can be ordered from SenseAir. Check can be done on site without interfering with ventilation system. Dokument Edition...